![BayTech MRPr Скачать руководство пользователя страница 13](http://html.mh-extra.com/html/baytech/mrpr/mrpr_manual_2713163013.webp)
Page
13
SERIAL
SETUP
Operation
Important:
Outlet
Status
Connect the
9FRJ45PC-1
adapter to the user’s computer
Connect the RPC EIA-232 port to the adapter via the
RJ08X007
rolled flat ribbon cable.
Use terminal emulation software to access the unit,
9600 bps, 8 data bits, 1stop bit, no parity,
no flow control, and B/C switch set to ‘B’
.
NOTE:
At any time during the session you need to go to another menu, use the
Attention
Character = semi-colon (;)
. Press the attention character key 5-times to get back to the
main status menu.
IMPORTANT:
If a device, other than a PC, is used to connect to the serial EIA232 port, a
custom cable is needed; see
Serial 1 figure above
, for serial port pin out.
IMPORTANT:
Do not connect both ends of the 8” serial cable until after the MASTER
unit has been configured.
When operating remotely, do not send the command to turn “off” a receptacle that has a host terminal
or modem attached. Doing so will result in the host terminal or modem being powered down creating
a “locked-out” condition. You will not be able to reestablish a connection until the receptacle has
been turned “on” through the serial port.
The green LED’s correspond to the unit’s receptacles. An illuminated LED signifies the
corresponding outlet has power turned on, thus the attached equipment has power to it. No lit LED
signifies no power to the receptacle.
IMPORTANT:
If you send the command to “reboot” a receptacle with a host terminal or
modem attached, active connection to that terminal or modem is lost and will have to be
reestablished.
IMPORTANT:
An assigned user is allowed one active session. The admin user is allowed
four sessions running concurrently.
The Modular Series are multi-user units, supporting one admin user and up to Thirty-two outlet users.
The admin user has access to all outlets, user and system configuration options, unit status, and unit
reset capabilities. The outlet user’s status menu displays only those outlets assigned to the user’s
outlet list, as set by the admin user.
NOTE:
The Modular Series supports one admin user. The admin user may have four sessions
running concurrently. Default user name is ‘
root
’. User names are case sensitive.
NOTE:
Each session has an inactivity timeout of ten minutes, if there is no option to set the
timeout. After ten minutes of no activity elapses, the session terminates.
NOTE:
The Modular Series menu is used for demonstration throughout this manual. There will
be some differences in the menus dependent on the firmware revision and the number of outlets
on your unit.