VISTA-20BAY Installation & Setup Guide
14–2
Entering Program Mode
You may use one of the following methods:
a) Press both [
✱
] and [#] at the same time within 50 seconds after power is applied to the
control, or
b) After power-up, enter
Installer code (4 1 1 2) + 8 0 0
.
This method is disabled if you exit the program mode using
✱
98 instead of
✱
99. See
Exiting the Program Mode
paragraph later in this section.
If a different Installer code is subsequently programmed, use it instead of 4112 to gain
access to the Programming mode.
When you enter the Program mode, data field
✱
20 is displayed (this is the first data field in
the system). The system now accepts entries for field
✱
20.
Programming a Data Field
1. Press
[
✱
]
. The display shows
Field ?
. Make the required entry (for example, 21).
2. When you have completely programmed a data field, the keypad beeps three times and
then automatically displays the next data field in sequence. To go to a different field, press
[
✱
] plus the desired field number.
3. If the number of digits that you need to enter in a data field is less than the maximum
digits available (for example, the phone number field), enter the desired data, then press
[
✱
] and the next data field number to be programmed.
4. If you try to enter a nonexistent field, the keypad doesn’t change and continues to display
Field ?
. Simply re-enter a valid field number.
Reviewing a Data Field/Erasing an Entry
Press
[#] + Field No.
. Data is displayed for that field number.
No changes are accepted
in this mode.
To delete an entry in a field,
press
[
✱
] + Field No. + [
✱
]
.
(
Applies only to fields
✱
40-
✱
44 and
✱
94.)
Interactive Mode Programming (
✱
56,
✱
58,
✱
80,
✱
81, and
✱
82)
Typical prompt displayed
during interactive mode
programming
Enter Zn Num.
(00 = Quit)
01
Press
[
✱
]
+
Interactive Mode Field No.
(for example,
✱
56). The
alpha keypad displays the first of a series of prompts requesting
entries.
A detailed procedure (with displays of prompts) is provided in
later sections of this manual.
Zone Number
Ç
Interactive Mode
Used to Program
✱
56 Zone Programming
Zone characteristics, report codes,
alpha descriptors, and serial numbers
✱
58 Expert Mode
Programming
Zone characteristics, report codes, and
serial numbers
✱
80 Relay Programming
4204 or 4229 Relay modules, or
Powerline Carrier devices
✱
81 Zone List
Programming
Zone Lists for relay/powerline carrier
and activation
✱
82 Alpha Programming
Zone alpha descriptors
Содержание Vista-20Bay
Страница 2: ......
Страница 22: ...VISTA 20BAY Installation Setup Guide 3 4 ...
Страница 28: ...VISTA 20BAY Installation Setup Guide 4 6 ...
Страница 32: ...VISTA 20BAY Installation Setup Guide 5 4 ...
Страница 40: ...VISTA 20BAY Installation Setup Guide 6 8 ...
Страница 64: ...VISTA 20BAY Installation Setup Guide 14 4 ...
Страница 68: ...VISTA 20BAY Installation Setup Guide 15 4 ...
Страница 82: ...VISTA 20BAY Installation Setup Guide 16 14 ...
Страница 92: ...VISTA 20BAY Installation Setup Guide 17 10 ...
Страница 98: ...VISTA 20BAY Installation Setup Guide 18 6 ...
Страница 100: ...VISTA 20BAY Installation Setup Guide 19 2 ...
Страница 110: ...VISTA 20BAY Installation Setup Guide 22 4 ...
Страница 116: ...VISTA 20BAY Installation Setup Guide 23 6 ...
Страница 122: ...VISTA 20BAY Installation Setup Guide 25 4 NOTES ...
Страница 128: ...VISTA 20BAY Installation Setup Guide A 2 ...
Страница 130: ...VISTA 20BAY Installation Setup Guide B 2 ...
Страница 138: ... 1 9 l N7526 4V1 5 00 SINCE 1946 BAY ALARM 925 Ygnacio Valley Road Walnut Creek CA 94596 ...