15. GAS VALVE CALIBRATION
To calibrate the gas valve, enable the calibration function as described in section 12.2 and
carry out the following operations:
1) Calibrating MAXIMUM heat output.
Check that the
measured on the flue duct, with the boiler operating at maximum heat
capacity, matches that indicated in table 2 (allowed tol/- 0.5%). If it does not, turn
the adjustment screw (
V
) on the gas valve. Turn the screw clockwise to decrease the level
of
and anti-clockwise to increase it (allowed tol/- 0.2%).
2) Calibrating REDUCED heat output
Check that the
measured on the flue duct, with the boiler operating at minimum heat
capacity, matches that indicated in table 2 (allowed tol/- 0.5%). If it does not, turn the
adjustment screw (
K
) on the gas valve. Turn the screw clockwise to increase the level of
and anticlockwise to decrease it (allowed tol/- 0.2%).
V
Gas flow adjustment screw
Pi
Gas supply pressure tap
K
OFFSET adjustment screw
15.1 GAS CONVERSION
When converting from natural gas to propane (LPG), before calibrating the gas valve as described above, replace the venturi
assembly (B) as indicated in the figure. To achieve this, release the gas pipe (fixed with clips for models 1.35 - 1.50 -1.60 and
threaded nut G1" for model 1.70) and remove the three screws securing the flange. Afterwards, make sure there are no gas
leaks. Modify the parameters (fan rpm) as indicated in table 2 following the procedure described in section 14.
LUNA DUO-TEC 1.35-1.50-1.60
LUNA DUO-TEC 1.70
TABLE 2
PARAMETERS - rpm
VENTURI
Ø (mm)
GAS NOZZLES
Ø (mm)
CO
2
Min
(%)
CO
2
Max
(%)
Max. CO
(ppm)
P60
**
P30 -
P61
**
P59
**
Boiler
model
Min. power
Max. power
Ignition power
G20
G31
G20
G31
G20
G31
G20-
G31
G20
G31
G20
G31
G20
G31 G20/G31
1.35
1500 1500 5000 4800
2300
3000
24
3.7
(n°2)
2.95
(n°2)
*8.5 *9.5 *9.0
*10
< 250
1.50
1500 1500 6650 6400
2300
3000
24
3.7
(n°2)
2.95
(n°2)
*8.5 *9.5 *9.0
*10
1.60
1420 1420 6750 6600
2000
2500
28
4.6
(n°2)
3.45
(n°2)
*9.0 *9.4 *9.0 *10.1
1.70
1270 1270 6450 6100
2100
2500
30
5.3
(n°2)
4.0 (n°2)
*8.5 *9.5 *9.0
*10
*
CO
2
with cover closed. Without cover (chamber open) the value is less than
0.2%.
*
*
value read on the boiler front panel display to multiply
x 10
(e.g.: 150 corresponds to 1500 rpm)
To simplify calibration of the gas valve, set the “calibration function” directly on the boiler control panel as described in
section 12.2.
For cascade ducts, change the parameter P60 increasing the number of fan revolutions by 200 (see table 1B in chapter 10.3).
Содержание Luna Duo-Tec MP Plus 1.35
Страница 24: ...7221369 01 1 03 15 90 S E C T I O N A 20...
Страница 29: ...95 S E C T I O N C 7221369 01 1 03 15 G 3 4 G 1 G 1 95 123 100 100 CR_0774 75 5 51 5 43 22 O...
Страница 32: ...7221369 01 1 03 15 98 S E C T I O N F AGU 2 550 CR_0349 CR_0349 AVS 75...
Страница 33: ...99 S E C T I O N F 7221369 01 1 03 15 CG_2482 Tmax 50 C...