TEMPERATURE ADJUSTMENT ON

 

LOW TEMPERATURE HEATING SYSTEM

For a low temperature system (such as underfloor heating), reduce the maximum CH temperature setpoint on the boiler by setting 

parameter 

741

 (point B

)

 to a value not greater than 45°C. 

 

 

 

11.2.2  EXTERNAL SENSOR

To connect this accessory, see figure to side (terminals 

4

-

5

and the instructions supplied with the sensor.

  

With the External Sensor connected, 

 

 on the boiler 

control panel move the set climate curve 

Kt

 in parallel (see 

annex 

"SECTION" E

 and parameter 

P03

 in the table in section 

14). To increase room temperature press 

+

, to decrease press 

-

.

  

SETTING THE "Kt" CLIMATE CURVE

To set the required kt climate curve, proceed as follows:

  

• 

Access the menu as described in section 14.

• 

Select parameter 

P03

.

• 

Select the climate curve from among those available, see the curve chart in annex 

"SECTION" E

 at the end of this manual 

(the preset curve is 1.5).

  

KEY TO CURVE CHART Kt - 

"SECTION" E

 

Flow temp

Outside temp

  

11.2.3  HEATING SYSTEM PUMP

Install the system pump downline from the hydraulic separator. Choose the pump according to the required system capacity/head 

characteristics (see annex 

"SECTION" F

). 

  

A  250Vac/250Vac  relay  with  a  minimum  current  rating  of  16A  and  able  to  withstand  a  starting  current  of  above  100A  is 

required to connect the external pumps.

  

11.2.4  EXTERNAL STORAGE BOILER

The boiler can be electrically connected to an external storage boiler. A diagram of the hydraulic connection of the external storage 

boiler is shown in annex 

"SECTION" F

. Connect the storage boiler pump to terminals 

4-5

 of the 

M3

 terminal block (see annex 

"SECTION" B

). Install the storage boiler downline from the hydraulic separator. Use the sensor supplied as an accessory and 

connect it to terminals 

9-10

 of terminal block 

M2

 (see annex 

"SECTION"

 

B

). Make sure that the exchange capacity of the storage 

boiler coil is appropriate for the power of the boiler. 

  

A  250Vac/250Vac  relay  with  a  minimum  current  rating  of  16A  and  able  to  withstand  a  starting  current  of  above  100A  is 

required to connect the external pumps.

  

EXTERNAL SYSTEM MANAGEMENT MODULES

The boiler can independently manage up to three heating circuits by using external accessories such as room units, remote 

controls and external modules (AGU 2.550 and AVS 75). The boiler electronics also comprises a wide range of functions for 

personalising and managing various system types. To assure correct system operation, a number (from 1 to 3) must be assigned 

to each accessory in order to allow the boiler board to recognise it. Consequently, carefully read the instructions provided with the 

accessories. 

  

11.2.5  MIXED ZONES ("SECTION" F)

A mixed zone can be managed using the 

AVS75

 external module, supplied as an accessory. This accessory can manage: a zone 

pump, a mixing valve, a temperature sensor, a limit thermostat and a room thermostat. To connect the components and adjust the 

system read the manual provided with the accessory. 

  

11.2.6  BOILERS IN A CASCADE CONNECTION ("SECTION" F)

The 

AVS75

 external unit, supplied as an accessory, is used to manage a heating system with up to 16 boilers connected in a 

cascade arrangement and a possible separate storage boiler providing domestic hot water. This accessory, connected to one of 

the cascade boilers, can directly control the circuit components up to a maximum of 3 independent relay outlets, 2 temperature 

sensors, 1 high voltage limit thermostat connector and one 1 control input (e.g.: room thermostat). The system also requires an 

OCI 345

 interface on each boiler comprising in the cascade arrangement. To adjust boiler parameters see section "PARAMETER 

SETTINGS". To connect the components and adjust the system read the manual provided with the accessory.

  

11.2.7  SOLAR PLANT ("SECTION" F)

Use the 

AGU 2.550

 external unit, supplied as an accessory, to manage a solar plant. To connect the plant, see the instructions 

supplied with the accessory.

  

THE HYDRAULIC DIAGRAMS OF THE CASES DESCRIBED CAN BE CONSULTED IN ANNEX "SECTION" F AT THE END OF 

THIS MANUAL 

  

  

  

  

 

 

  

Содержание Luna Duo-Tec MP Plus 1.35

Страница 1: ...all utente e all installatore en CONDENSING GAS WALL HUNG BOILERS Instructions manual for users and installers de AT KONDENSATIONS WANDGASHEIZKESSEL Gebrauchsanleitung f r den Benutzer und Installate...

Страница 2: ...its intrinsic hazards Children must not play with the appliance The cleaning and maintenance operations reserved to the user must not be performed by unsupervised children CONTENT DESCRIPTION OF SYMB...

Страница 3: ...n all the doors and windows to ventilate the room Call an Authorised Service Centre FLAMMABLE MATERIAL Do not use and or store highly flammable material thinners paper etc near the boiler SERVICING AN...

Страница 4: ...ating system can adversely affect boiler operation e g overheating and excessive noise of the heat exchanger Initial lighting of the boiler must be carried out by an authorised Service Engineer who mu...

Страница 5: ...d Boiler system water pressure low Heating mode enabled Technical Service Centre call in Programming menu Manually resettable fault Boiler information menu Fault in progress Set unit of measurement SI...

Страница 6: ...vertemperature 40 NTC flow sensor 133 Ignition failure 4 attempts 50 NTC DHW sensor only for heating only model with storage boiler 151 Boiler board internal fault 52 Solar DHW sensor if connected to...

Страница 7: ...are displayed alternatively with the gas energy consumption value expressed in millions thousands and units of kWh e g 21 033 145 827 corresponds to a gas energy consumption in HEATING of 33 145 827 k...

Страница 8: ...ning torque 30 Nm The template outline is shown in annex SECTION C at the end of this manual After deciding the exact location of the boiler fix the template to the wall Connect the system to the gas...

Страница 9: ...of 5 cm per metre of duct towards the boiler SOME OUTLET DUCT INSTALLATION EXAMPLES AND THEIR RELATIVE MAXIMUM LENGTHS ARE SHOWN IN ANNEX SECTION D AT THE END OF THIS MANUAL 10 1CONCENTRIC DUCTS This...

Страница 10: ...cable with a maximum diameter of 8 mm To access the terminal block remove the front boiler panel fixed with two screws at the bottom turn the control box downwards and access terminal blocks M1 M2 M3...

Страница 11: ...Room Thermostat Switch on the boiler and make sure the Room Thermostat works correctly 11 2ACCESSORIES NOT INCLUDED IN THE SUPPLY 11 2 1 REMOTE CONTROL The wire 1 from the boiler terminal block M2 pow...

Страница 12: ...uring the reduced time band it is necessary to set the parameter 5977 none B FLOW TEMPERATURE MODULATION To set flow temperature modulation disable parameter 742 HC1 Proceed as follows Access menu 2 B...

Страница 13: ...he power of the boiler A 250Vac 250Vac relay with a minimum current rating of 16A and able to withstand a starting current of above 100A is required to connect the external pumps EXTERNAL SYSTEM MANAG...

Страница 14: ...of the cycle To manually exit this function press the above buttons together for 6 seconds once again 12 2CALIBRATION FUNCTION To calibrate the gas valve proceed as follows Press buttons and together...

Страница 15: ...C 16 4 35 P14 1020 Kt curve slope 1 5 0 1 4 P15 1021 Kt curve drift 0 4 5 4 5 P16 1026 Kt curve adaptation 0 off 1 0 1 P17 1040 Flow temperature setpoint minimum value C 25 8 80 P18 1041 Flow temperat...

Страница 16: ...Pt 1000 2 1 2 P52 6110 Building time constant depending on the insulations of the building h 15 0 50 P53 6220 Software version 0 99 P54 6600 LPB device address BUS connection 1 16 P55 6601 LPB segment...

Страница 17: ...venturi assembly B as indicated in the figure To achieve this release the gas pipe fixed with clips for models 1 35 1 50 1 60 and threaded nut G1 for model 1 70 and remove the three screws securing t...

Страница 18: ...pressure switch This device allows the main burner to be ignited only if system pressure is higher than 0 5 bars Pump post circulation The electronically controlled pump post circulation function last...

Страница 19: ...ted Do not operate the boiler with empty condense trap to avoid risk of poisoning through the gas combustions 18 2CLEANING THE HEAT EXCHANGER FUMES SIDE Before starting to clean the heat exchanger wai...

Страница 20: ...combustion products and the combustion efficiency The other is connected to the combustion air intake circuit B allowing checking of any recycling of the combustion products in case of coaxial pipeli...

Страница 21: ...43 C53 C63 C83 C93 B23 Coaxial flue duct diameter mm 80 125 Diameter of separate outlets mm 80 80 Max mass flow rate of flue kg s 0 016 0 021 0 026 0 031 Min mass flow rate of flue kg s 0 002 0 002 0...

Страница 22: ...ime 1 1 97 97 1 96 8 96 5 Auxiliary electricity consumption Full load elmax kW 0 070 0 080 0 095 0 095 Part load elmin kW 0 020 0 020 0 020 0 020 Standby mode PSB kW 0 003 0 003 0 003 0 003 Other item...

Страница 23: ...ed load profile Seasonal space heating energy efficiency class A A A A Water heating energy efficiency class Rated heat output Prated or Psup kW 34 45 55 65 Space heating Annual energy consumption GJ...

Страница 24: ...7221369 01 1 03 15 90 S E C T I O N A 20...

Страница 25: ...ldamento Heating flow connection D Attacco ritorno acqua riscaldamento Heating return connection de es 1 Ventilator Ventilador 2 Sammelrohr Luft Gasgemisch Colector de mezcla aire gas 3 Prim r Tausche...

Страница 26: ...42 X41 X40 X30 X21 X20 B B V N R C C R R B B C M V N M N C V N V M C C C C C N V b a M C G V G V G V G V G V G V G V G V G V G V 1 15 M N P Y B R L N 1 2 M C G V G V G V N M N C M C M 10 9 8 7 6 5 4 3...

Страница 27: ...Remote Control FERNBEDIENUNG Control Remoto 13 Pompa Pump Pumpe Bomba 14 Elettrodo di rivelazione fiamma Flame sensor electrode Flammen berwachungselektrode Electrodo de detecci n de llama 15 Elettro...

Страница 28: ...01 1 03 15 94 S E C T I O N C G 3 4 G 1 G 1 Ed 1 02 2015 7221122 01 12 O 12 O 225 120 210 120 704 59 51 5 75 5 100 100 123 35 38 450 763 763 140 225 225 450 229 505 377 225 144 140 229 G 3 4 G 1 G 1...

Страница 29: ...95 S E C T I O N C 7221369 01 1 03 15 G 3 4 G 1 G 1 95 123 100 100 CR_0774 75 5 51 5 43 22 O...

Страница 30: ...C D Lmax 9 m 80 125 mm E F Lmax 10 m 80 125 mm G Lmax 8 m 80 125 mm H Lmax 9 m 80 125 mm I L1 L2 max 60 m 80 mm 1 35 MP L1 L2 max 60 m 80 mm 1 50 MP L1 L2 max 40 m 80 mm 1 60 MP L1 L2 max 30 m 80 mm...

Страница 31: ...97 S E C T I O N E 7221369 01 1 03 15 MP 1 35 1 50 MP 1 60 MP 1 70 0 1 2 3 4 5 6 7 8 9 10 11 H mH 2 O Q l h Q l h 0 1 2 3 4 5 6 7 8 9 10 11 0 1 2 3 4 5 6 7 8 9 10 11 Q l h H mH 2 O H mH 2 O...

Страница 32: ...7221369 01 1 03 15 98 S E C T I O N F AGU 2 550 CR_0349 CR_0349 AVS 75...

Страница 33: ...99 S E C T I O N F 7221369 01 1 03 15 CG_2482 Tmax 50 C...

Страница 34: ...TI MODIFIED PARAMETERS MODIFIZIERTE PARAMETER PARAMETROS MODIFICADOS N Nr N m VALORE VALUE WERT VALOR NOTA NOTE ANMERKUNG 36061 Bassano del Grappa VI ITALIA Via Trozzetti 20 Servizio clienti tel 0424...

Отзывы: