14. PARAMETERS SETTING
To programme the parameters of the boiler electronic board, proceed as follows:
•
Press
together and hold them down for 6 seconds until programme row “
P02
” appears on the display alternated with
the set value (°C);
•
Press and hold down for 6 seconds until "
On
" appears on the display. Release the button and "
P01
" appears on the display;
•
Press
to scroll the list of parameters;
•
Press
, the value of the selected begins flashing, press
to change the value;
•
press
to confirm the value or press
to exit without saving.
Further information concerning the parameters listed in the following table are supplied together with the required
accessories.
(a)
(b)
ZONE 1 HEATING PARAMETERS (main zone)
Factory
setting
Minimum Maximum
P01
700
*Operating mode (0=Frost Protection, 1=Timed, 3=T.comfort)
-
3
0
3
P02
712
*Reduced ambient temperature
°C
16
4
35
P03
720
*“Kt” curve slope
-
1,5
0,1
4
P04
721
*“Kt” curve drift
-
0
- 4,5
4,5
P05
726
*“Kt” curve adaptation (0=off)
-
1
0
1
P06
740
Flow temperature setpoint (minimum value)
°C
25
8
80
P07
741
Flow temperature setpoint (maximum value)
°C
80
25
80
P08
742
*Enable modulating temperature if set = “---”
°C
80
25
80
P09
750
*Room influence (“---” = disabled)
%
50
1
100
P10
834
*Opening/Closing speed of mix valve
S
30
30
873
ZONE2 HEATING PARAMETERS (with accessory Expansion Unit)
P11
1000
*Operating mode (0= Frost Protection, 1=Timed, 3=T.comfort)
°C
3
0
3
P12
1010
*Comfort room temperature
°C
20
4
35
P13
1012
*Reduced room temperature
°C
16
4
35
P14
1020
*“Kt” curve slope
-
1,5
0,1
4
P15
1021
*“Kt” curve drift
-
0
- 4,5
4,5
P16
1026
*“Kt” curve adaptation (0=off)
-
1
0
1
P17
1040
Flow temperature setpoint (minimum value)
°C
25
8
80
P18
1041
Flow temperature setpoint (maximum value)
°C
80
25
80
P19
1042
*Enable modulating temperature if set = “---” (flow temp. setpoint if P63=0)
°C
80
25
80
P20
1050
*Room influence (“---” = disabled)
%
50
1
100
P21
1134
*Opening/Closing speed of mix valve
s
30
30
873
DHW PARAMETERS
P22
1620
Operating mode in DHW (with Remote Control)
-
2
0
2
0=always enabled, 1=according to hourly heating programme,
2= according to hourly DHW programme.
P23
1640
Anti-legionella function Disabled
-
0
0
1
0=disabled, 1=periodic (depending on P24)
P24
1641
Periodic anti-legionella function enable (only if P23 =1)
-
7
1
7
1=daily, 2..6=intervals of 2..6 days, 7=once a week
P25
1663
Circulation temperature setpoint (additional DHW pump)
°C
45
8
80
P26
5470
Preheating time for DHW circuit (1=10’ -- 144=1440’)
min
0
0
144
BOILER PARAMETERS
P27
2243
Minimum boiler off time
min
3
0
20
P28
2217
Frost Protection setpoint
°C
5
-20
20
P29
2250
Pump post-circulation time
min
3
0
240
P30
2441
Max. fan speed (heating)
rpm
xxx
0
8000
P31
2455
Minimum boiler off differential
°C
5
0
20
P32
2720
Not used (Do NOT change this parameter)
-
0
0
1
P33
2721
Not used (Do NOT change this parameter)
-
1
1
2
SOLAR PLANT PARAMETERS (with accessory Expansion Unit)
P34
3810
Temperature - on differential
°C
8
0
40
P35
3811
Temperature - off differential
°C
4
0
40
P36
3830
Pump start function (“---” = disabled)
min
---
5
60
P37
3850
Solar panel manifold overheating protection (“---“ = disabled)
°C
---
30
350
P38
5050
DHW boiler tank charging temperature max
°C
65
8
95
P39
5051
Maximum temperature of storage tank
°C
90
8
95
Содержание Luna Duo-Tec MP Plus 1.35
Страница 24: ...7221369 01 1 03 15 90 S E C T I O N A 20...
Страница 29: ...95 S E C T I O N C 7221369 01 1 03 15 G 3 4 G 1 G 1 95 123 100 100 CR_0774 75 5 51 5 43 22 O...
Страница 32: ...7221369 01 1 03 15 98 S E C T I O N F AGU 2 550 CR_0349 CR_0349 AVS 75...
Страница 33: ...99 S E C T I O N F 7221369 01 1 03 15 CG_2482 Tmax 50 C...