Horizontal Flues
NOTE: Horizontal flue pipes should always be installed with at least 1.5° fall from
the terminal to allow condensate to run back to the boiler.
Total equivalent length = A+B+C+2x90°Bends
page 24
8.2 Twin & Vertical Flue Systems
1. Maximum permissible equivalent flue lengths are:
Vertical Concentric (60/100) 5 metres
Vertical Twin Pipe (80/80)
10 metres
2. Any additional "in line" bends in the flue system must be taken into consideration.
Their equivalent lengths are:
Concentric Pipes:
135° bend 0.5 metres
93° bend
1.0 metres
Twin Flue Pipe
135° bend 0.25 metres
91.5° bend 0.50 metres
The elbow supplied with the standard horizontal telescopic flue kit is not included in any equivalent length calculations
NOTE: Flue length is measured from point X to Y as shown.
IMPORTANT:
Содержание ECOGEN 24/1.0
Страница 69: ...Fig 77 Fig 78 Fig 79 page 69 16 0 Schematic Wiring 16 1 Burner Control Units BCU Connections...
Страница 70: ...page 70 16 2 Milligrid 24 way Connector...
Страница 71: ...page 71 16 3 14 way Connector...
Страница 72: ...page 72 16 4 Engine Circuit...
Страница 73: ...page 73 16 5 Power Monitoring 24Vdc Power Supply...
Страница 74: ...page 74 16 6 External Connections External Wiring...
Страница 85: ...page 87...
Страница 86: ...page 88...
Страница 87: ...page 89 Section P...
Страница 88: ...page 90...
Страница 89: ...page 91 Section Q Engine developing less than 950W after 15 minutes running at maximum rate...
Страница 91: ...page 93 page 94 page 95 page 96 MICRO CHP SYSTEM COMMISSIONING CHECKLIST...
Страница 92: ...page 97...