5.4.3 Making the Water Connections (
Fig. 22
)
There are two water connections at the top of the boiler. The left connection is the return pipe (indicated with blue label) and the flow the right hand one (indicated with red
label). Remove the sealing caps from the boiler connections.
1.
It is essential that the flow and return pipes are connected to the boiler correctly. The boiler connections will accept 22mm compression fittings.
2.
For a top flue installation make sure the water connections do not clash with the flue position.
3.
When soldering of joints is to be performed under the boiler the condensate trap must be removed to prevent damage.
5.4.4 Filling the Condensate Trap
The condensate trap must be filled with water before the boiler is commissioned.
1.
If access to the condensate trap is impeded remove the facia panel with the User Interaction Controller.
2.
Disengage the condensate trap retaining clip and carefully pull out the trap. Remove and discard the sealing cap.
3.
Fill the condensate trap with tap water to a depth of approximately 75mm.
4.
Carefully relocate the condensate trap in the boiler ensuring all seals are located properly and reattach the retaining clip.
5.
If necessary remove the boiler front panel to inspect that the seals are located properly and refit the facia panel with the User Interaction Controller.
6.
5.4.5 Connecting the Condensate Drain (
Fig. 23
)
Using the 90° rubber hose supplied, connect the condensate drain pipework to the boiler condensate trap outlet pipe.
1.
Ensure the discharge of condensate complies with any national or local regulations in force
(see British Gas "Guidance Notes for the Installation of Domestic Gas Condensing Boilers" & HHIC recommendations) and
Section 5.3.5.
The hose will accept 21.5mm (3/4in) plastic overflow pipe which should generally discharge internally into the household drainage system. If this is not possible, discharge
into an outside drain is acceptable.
2.