Before Installation
5
Under car ports we recommend the use of the plume
displacement kit. The terminal position must ensure the
safe and nuisance - free dispersal of combustion
products.
2. If the terminal discharges onto a pathway or passageway,
check that combustion products will not cause a nuisance and
that the terminal will not obstruct the passageway.
3. If a terminal is less than 2 metres above a balcony, above
ground or above a flat roof to which people have access, then a
suitable terminal guard must be provided.
*4. Reduction to the boundary is possible down to 25mm but
the flue deflector must be used (see 5.3.12).
The distance from a fanned draught appliance terminal
installed parallel to a boundary may not be less than
300mm in accordance with the diagram opposite
(Fig. 9).
Fig. 9
300 mi
n
Termi
n
al
A
ss
embl
y
Top View Rear Flue
Propert
y
B
ou
n
dar
y
Li
n
e
Opening
Window or Door
150mm
MIN.
If fitting a Plume Displacement Flue Kit, the air inlet
must be a minimum of 150mm from any opening
windows or doors (see Fig. 10).
Plume
Displacement
Kit
Air Inlet
Fig. 10
*
The Plume Displacement flue gas discharge terminal
and air inlet must always terminate in the same
pressure zone i.e. on the same facing wall.