7219717 - 02 (08/15)
EcoBlue Heat
15
Technical Specification
3
3.2
Technical Parameters
Technical parameters for boiler space heaters
Condensing boiler
Low-temperature boiler
(1)
B1 boiler
Cogeneration space heater
Combination heater
Useful heat output at rated heat output
and high temperature regime
Useful heat output at 30% of rated heat
output and low temperature regime
(1)
Useful efficiency at rated heat output and
high temperature regime
(2)
Useful efficiency at 30% of rated heat
output and low temperature regime
(1)
Full load
Part load
Standby mode
Standby heat loss
Ignition burner power consumption
Annual energy consumption
Sound power level, indoors
Emissions of nitrogen oxides
(1) Low temperature means for condensing boilers 30°C, for low temperature boilers 37°C and for other heaters 50°C return temperature (at
heater inlet).
(2) High temperature regime means 60°C return temperature at heater inlet and 80°C feed temperature at heater outlet.
See
The back cover for contact details.
Baxi EcoBlue Heat ErP
Rated heat output
Seasonal space heating energy efficiency
Auxiliary electricity consumption
Other items
Prated
kW
P
4
kW
P
1
kW
Š
s
%
Š
4
%
Š
1
%
elmax
kW
elmin
kW
P
SB
kW
P
stby
kW
P
ign
kW
Q
HE
kWh
GJ
L
WA
dB
NO
X
mg/kWh
12
15
18
21
24
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
13
16
19
21
25
13.0
16.0
19.0
21.0
25.0
4.3
5.4
6.4
7.0
8.4
93
93
93
93
93
88.0
87.9
87.8
87.8
87.7
98.0
98.0
98.0
98.0
98.0
0.017
0.020
0.023
0.025
0.033
0.014
0.014
0.014
0.014
0.014
0
0
0
0
0
0.028
0.028
0.028
0.028
0.028
-
-
-
-
-
11183
13764
16344
18065
21506
40
50
59
65
77
32
33
34
35
37
18
20
21
23
24