7
912.807.1 - GB
INSTALLATION AND OPERATING MANUAL
0905_0501 / CR_0013
Figure 1b: Floor arrangement diagram
The indicative diagram in figure 1b only illustrates the feed pipes of the individual user modules.
The heating plant inside the zone controlled by the module must be realised by feeding the heating elements according
to normal methods.
The storage boiler for the production of domestic hot water must be installed inside the home (or zone) service by the
module.
A stub of the mains water supply must be connected to the domestic hot water inlet connector of the storage boiler. The
storage boiler hot water outlet must feed all the user hot water take-off points.
SIRIUS SAT
SIRIUS SAT
SIRIUS SAT
HOME A
HOME B
HOME C
- Water temperature range in centralised plant:
60 - 75 °c
- Maximum water pressure in centralised plant:
4 bar
- Module feed flow rate (nominal):
700 ÷ 1500 l/h
- Maximum recommended speed of heat transfer fluid:
1 ÷ 1.5 m/s
- Pressure drop in module
20 KPa at 700 l/h
Some purely indicative general sizing data is shown below:
TABLE: HEAT DEMAND – HEATED AREA
Area to heat
(m
2
)
Heat demand (*)
with F1 = 20 W/m
3
(kW)
Heat demand (*)
with F2 = 30 W/m
3
(kW)
Heat demand (*)
with F3 = 45 W/m
3
(kW)
60
3,6
5,4
8,1
70
4,2
6,3
9,5
80
4,8
7,2
10,8
90
5,4
8,1
12,2
100
6,0
9
13,5
110
6,6
9,9
14,9
120
7,2
10,8
16,2
130
7,8
11,7
17,6
140
8,4
12,6
18,9
150
9,0
13,5
20,3
(*)
Volumetric heat load “F”: 20 - 30 - 45 W/m
3
with ∆t = 25 K;
height of volume to be heated =
3 m
∆t =
internal and external temperature difference (internal T = 20 °C, external = - 5°C)
F1 = 20 W/m
3
buildings with an excellent level of insulation
F2 = 30 W/m
3
buildings with an good level of insulation
F3 = 45 W/m
3
buildings with an low level of insulation
3.1 GENERAL SIZING DATA