27
912.807.1 - GB
INSTALLATION AND OPERATING MANUAL
SWITCH 6: EXTERNAL PROBE ENABLE (only for models RSP-R2Z-RS2Z)
External probe enable table
EXTERNAL PROBE
Switch 6
With probe
ON
Without probe (*)
OFF
(*) factory setting
SELECTOR 7 : PUMP POST-CIRCULATION TIME
Pump post-circulation time selection table
POST-CIRCULATION TIME
Switch 7
4 HOURS
ON
5 MINUTES (*)
OFF
(*) factory setting
0904_2602 / CR_0028
Figure 14 E: External probe switch
Figure 14 F: Pump post-circulation switch
0904_2603 / CR_0028
Figure 14 G: Anti-legionellosis switch
0702_2403 / CR_0088
SWITCH 8: ANTI-LEGIONELLOSIS FUNCTION
Anti-legionellosis function selection table
ANTI-LEGIONELLOSIS
Switch 8
ENABLED (*)
ON
DISABLED
OFF
(*) factory setting
With the anti-legionellosis function enabled, the system heats the storage boiler to a temperature of 65°C every seven
days if the storage boiler has not been heated during that period of time.
Anti-Legionellosis
External probe