and having a minimum
effective flue height of
3m (10ft). A masonry
chimney having a
correctly installed flue
liner to BS EN 1856 Part
1 or BS715 and with a
minimum flue diameter
of 125mm is also
acceptable. Chair brick
removal may not be
required providing at
least 50mm clearance is
available from the flue
outlet to any fireplace
component. The
appliance is designed to
cater for low lintel
installations (min height
505mm) providing a
minimum distance of 25mm is maintained between the lintel and the front face of the
fireplace (i.e. 25mm rebated fire surround).
3.2.1.1
‘Hole-in-the-wall’ Installations
!
It is recommended that a hearth should be
installed as in section 3.9 (See figure 1).
!
If no hearth or a reduced depth hearth is
fitted, the fire must be installed so that the
distance from the base of the fireplace
opening in the wall to the finished floor level
is at least 72mm. Where there is no floor
covering or carpet and the floor is of a type
that is likely to be covered in such a way in
the future then the distance from the base of
the fireplace opening in the wall to the
finished floor level should be increased to at
least 147mm.
!
If the lower part of the fascia (the
firefront) is free standing, the recommended
reduced hearth depth is 100mm. This is
necessary to support the firefront (See figure
Page 8
INSTALLER GUIDE
©
Baxi Heating U.K. Limited 2007.
Figure 2. Metal flue box
Figure 1. Hearth and fireplace opening dimensions (See
section 3.2.1.1)
See Section 3.14