The codes for using the
Diagnostic function
feature are
listed in the following table:
Function
Description
Code (decimal)
Code (hexadec-
imal)
NORMAL WORKING
NORMAL WORKING MODE
0
0
FORCE PHASE A
FORCE COIL EXCITATION TO
PHASE A
1
1
FORCE PHASE B
FORCE COIL EXCITATION TO
PHASE B
2
2
FORCE COILS OFF
FORCE COIL EXCITATION TO OFF
3
3
COILS DIAG BITS
DIAGNOSTIC BITS FOR EXCITA-
TION CONTROL
3
3
FORCE OUT1 ON
FORCE OUT 1 TO ON STATE
16
10
FORCE OUT1 OFF
FORCE OUT 1 TO OFF STATE
32
20
FORCE OUT1 FREQ
FORCE OUT 1 TO OUTPUT 1KHZ
SIGNAL
48
30
FORCE OUT1 INP1
FORCE OUT 1 TO COPY THE
STATE OF THE IN1
64
40
FORCE OUT1 INP2
FORCE OUT 1 TO COPY THE
STATE OF THE IN2
80
50
FORCE OUT1 FREQ2
FORCE OUT 1 TO OUTPUT 64 HZ
(SUB-CLOCK CHECK)
96
60
OUT1 DIAG BITS
DIAGNOSTIC BITS FOR OUT1
CONTROL
240
000000F0
FORCE OUT2 ON
FORCE OUT 2 TO ON STATE
256
100
FORCE OUT2 OFF
FORCE OUT 2 TO OFF STATE
512
200
FORCE OUT2 FREQ
FORCE OUT 2 TO OUTPUT 1KHZ
SIGNAL
768
300
FORCE OUT2 INP1
FORCE OUT 2 TO COPY THE
STATE OF THE IN1
1024
400
FORCE OUT2 INP2
FORCE OUT 2 TO COPY THE
STATE OF THE IN2
1280
500
FORCE OUT2 FREQ2
FORCE OUT 2 TO OUTPUT 64 HZ
(SUB-CLOCK CHECK)
1536
600
OUT2 DIAG BITS
DIAGNOSTIC BITS FOR OUT2
CONTROL
3840
00000F00
FORCE OUT3 ON
FORCE OUT 3 TO ON STATE
4096
1000
FORCE OUT3 OFF
FORCE OUT 3 TO OFF STATE
8192
2000
Operation
Menu navigation > Diagnostic menu
05.03.2020
Flow sensor PF55S