7.6.3
Scales
menu
The functionality and available capabilities of the flow
sensor vary depending on the order configuration and
type code.
Depending on the configuration of the flow sensor or
activated functions, individual menus and selection
functions may differ from the representations or be
hidden.
Menu
Description
Password level /
BCP command
FS1
Flow - scale end value 1
With scale end value 1, the maximum flow rate
is set in volume per time.
The scale end value must be between
4 and 100% of the maximum possible flow rate.
For the automatic change of the measuring
range
Autorange
it must be ensured that
Scale end value 2
FS2
is larger than the
Scale end value 1
FS1
.
L 2
FRFS1
FS2
Flow - scale end value 2
With scale end value 2, the maximum flow rate
is set in volume per time.
The scale end value must be between
4 and 100% of the maximum possible flow rate.
For the automatic change of the measuring
range
Autorange
it must be ensured that
Scale end value 2
FS2
is larger than the
Scale end value 1
FS1
.
L 2
FRFS2
Pls1
Pulse Channel 1
The value defines the measured flow rate for
which a pulse is generated at Channel 1.
L 2
OP1PV
Tpls1
Duration of the pulse generated at Channel
1
The value sets the duration of the pulse gener-
ated at Channel 1.
It can be anywhere between 0.4 and 9999.99.
L 2
OP1PT
Operation
Menu navigation > Scales menu
05.03.2020
Flow sensor PF55S
66