SDO Abort Message
If the SDO communication is not carried out problem-free, an Abort Code is transmitted as the SDO
response:
05040001h
: Command byte is not supported
06010000h
: Incorrect accessing of an object
06010001h
: Read access to Write Only
06010002h
: Write access to Read Only
06020000h
: Object is not supported
06090011h
: Subindex is not supported
06090030h
: Value outside limits
06090031h
: Value too large
08000000h
: General error
08000020h
: Incorrect memory signature ("save")
08000021h
: Data cannot be saved
4.3. Important information on sensor
Set new Node-ID
1. A new Node-ID is set with the IVO-specific Object 2100h.
2. After the Node-ID is set, it must be saved in the EEPROM with Object 1010h.
3. During the next initialization the sensor will report with the new Node-ID.
Set new baud rate
1. A new baud rate is set with the IVO-specific Object 2101h.
2. After the baud rate is set, it must be saved in the EEPROM with Object 1010h.
3. During the next initialization the sensor will report at the new baud rate.
4. ! REMEMBER TO SET THE MASTER TO THE NEW BAUD RATE !
Shielding
As, depending on the installation position, the encoder is not always connected to a defined ground potential,
the encoder flanges should also always be connected to ground potential. The encoder should always be
connected via a shielded cable.
If possible, the cable shield should be connected on both sides. It must be ensured that no transient currents
are discharged via the encoder.