Baumer_GIM700DR_CANopen_EN_V1.00_MNL.docx
www.baumer.com
27.04.21
16/32
Value
Setting via LSS (Standard CiA bit timing table)
Setting baud rate via object 2100h
0
1000
kbits/s
10
kbits/s (not supported)
1
800
kbits/s
20
kbits/s
2
500
kbits/s
50
kbits/s
3
250
kbits/s
100
kbits/s
4
125
kbits/s
125
kbits/s
5
100
kbits/s
250
kbits/s
6
50
kbits/s
500
kbits/s
7
20
kbits/s
800
kbits/s
8
10
kbits/s (not supported)
1000
kbits/s
9
Automatic bit rate detection (not supported)
Automatic bit rate detection (not supported)
Note:
For setting bit timing via LSS, use values according to standard CiA bit timing table.
New baud rate has to be saved to non-volatile memory by using object 1010h.
New baud rate will take effect after restart of the device. Baud rate 10 kbits/s is not supported.
Saving configuration protocol
This protocol saves the configuration parameters in the EEPROM.
7E5h
17h
reserved
7E4h
17h
ErrCode SpecError reserved
Error code
: 0=OK; 1=Saving not supported; 2=Access error; 3…254=reserved; 255
Specific
error
Specific error
: If error code=255
Application-specific error code.
Activate bit timing parameters
The new bit timing parameters are activated with the command specifier 15h.
7E5h
15h
Switch delay
reserved
Switch Delay
: Reset delay in the producer in msec.
After the delay, the sensor logs on with the new baud rate.
Request vendor ID
Requesting the vendor ID of a selected sensor
7E5h
5Ah
reserved
7E4h
5Ah
32-bit vendor ID
reserved
Vendor ID
: = ECh
Request product code
Request product code of a selected sensor
7E5h
5Bh
reserved