background image

BE1-79S Functional Description

2-1

SECTION 2 • FUNCTIONAL DESCRIPTION

GENERAL

The functional description contained in this section applies to the BE1-79S Single Shot Reclosing Relays
with all combinations of available options.

The reclosing relay, functionally shown in Figure 2-1, provides automatic reclosure of circuit breakers that
have been tripped by a protective relay. The relay uses a Form B auxiliary contact of the controlled circuit
breaker  to  detect  the  position  of  the  breaker.  A  reclose  initiate  (RI)  signal  must  be  received  from  the
protective system prior to the closure of the breaker auxiliary contact. Closure of this contact indicates that
automatic reclosing is to be permitted.

A reclose cancel (RC) signal may be generated by the protective system. The RC signal must remain at
least 8 milliseconds before it is recognized by the relay. When RC is recognized, the relay is inhibited from
reclosing the controlled breaker. Following an RC signal, the controlled breaker must be closed by other
means. This permits the relay to be automatically reset by its internal reset timer as described below.

Contact sensing (52b, RI, and RC) is provided in one of two configurations. If isolated contact sensing
(Option 1-5) is specified, current is supplied to the contacts by the relay. If non-isolated contact sensing
(Option 1-4) is specified, direct current is supplied by the protective system through the contacts to the
polarity sensitive relay inputs. If the relay is equipped with the Type X power supply, these configurations
must be modified to accommodate an essential external sensing input module. (See Figure 4-9).

When Option 2-D or 2-S is included, a voltage monitor circuit compares the line and bus voltage levels
against  pre-selected  live-line/live-bus,  live-line/dead-bus,  dead-line/live-bus  and  dead-line/dead-bus
reclosing conditions. The reclosing conditions' voltage levels are established by adjustable controls on the
front panel. LB, DB/OV, LL and DL/OV. (The overvoltage limit (OV) mode allows an upper voltage limit to
be set for the recognition of a live-line or live-bus condition.) If the measured voltages are not correct for the
selected reclosing conditions, breaker closing is inhibited.

In some units (those with Reset Timer B or C) there is a Maximum Trial Timer on the voltage monitor board
that limits the opportunity for reclosing to either 95 or 15 seconds (for B and C respectively) after an open
breaker is sensed at the 52b input. If the required line and/or bus voltages have not been detected during
the specified time, the relay is inhibited from issuing a reclosing signal. The inhibit remains in effect until the
breaker is closed by other means, there-by circumventing the somewhat precarious situation that could
result from a relay poised to issue a reclose signal long after the instigating event has passed. (Like a loaded
gun with its safety off.)

When the controlled breaker is closed, the reset timer begins to measure a programmed interval. If the
breaker remains closed for this interval, the relay resets and is ready to perform an automatic reclosing
operation following a subsequent breaker trip by the protective system. If the breaker opens before the
programmed interval has expired,  the  relay is disabled (locked out) and will not respond further to the
breaker position until it is reset. Resetting is accomplished by closing the breaker by other means and its
remaining closed for the duration of the reset interval.

A red LOCKOUT indicator on the relay front panel lights when the relay generates the reclose command or
the breaker opens prior to expiration of the reset timer. It goes out when the reset time expires. A Form C
lockout relay is slaved to the LOCKOUT indicator and provides output contacts for monitoring the state of
the reclosing relay.

Содержание BE1-79S

Страница 1: ...INSTRUCTION MANUAL FOR SINGLE SHOT RECLOSING RELAY BE1 79S Publication Number 9 1410 00 990 Revision B 02 2001...

Страница 2: ...ould perform the procedures presented in this manual INTRODUCTION This Instruction Manual provides information concerning the operation and installation of BE1 79S Single Shot Reclosing Relay To accom...

Страница 3: ...tric Co Highland IL 62249 February 2001 It is not the intention of this manual to cover all details and variations in equipment nor does this manual provide data for every possible contingency regardi...

Страница 4: ...c 2 3 Reclose Timer 2 3 Reclose Fail Timer 2 3 Reset Timer 2 3 Voltage Monitor 2 4 Power Supply Output 2 7 SECTION 3 HUMAN MACHINE INTERFACE 3 1 Controls and Indicators 3 1 Switches 3 4 SECTION 4 INST...

Страница 5: ...ng closed for the reset interval Automatic reclosing of a tripped breaker requires that a reclose initiate signal RI be generated by the protective system and received by the reclosing relay prior to...

Страница 6: ...side the case assembly Upon receipt of a reclosing relay be sure to check relay style number against the requistion and packing list to see that they agree Style Number Example The Style Number Identi...

Страница 7: ...ble 1 1 Power Supplies Type Nominal Input Voltage Input Voltage Range Burden at Nominal B Mid Range 48 Vdc 24 to 150 Vdc 5 5 W C Mid Range 125 Vdc 120 Vac 24 to 150 Vdc 90 to 132 Vac 4 0 W 10 0 VA D L...

Страница 8: ...polarity sensitive and requires 24 60 Vdc at a burden of 3 5 W for a Type B power supply 62 150 Vdc at 4 5 W for a Type C power supply 12 32 Vdc at 2 0 W for a Type D power supply and 140 280 Vdc at...

Страница 9: ...uracy Either 95 10 0 seconds with Reset Timer B or 15 2 0 seconds with Reset Timer C for a nominal input frequency of 50 60 Hz at 25 C Non adjustable Temperature Operating Temperature Storage Temperat...

Страница 10: ...bus and dead line dead bus reclosing conditions The reclosing conditions voltage levels are established by adjustable controls on the front panel LB DB OV LL and DL OV The overvoltage limit OV mode a...

Страница 11: ...necessary Specific voltage ranges for the three new power supplies and a cross reference to the style number identifiers are shown in the following table Table 2 1 Wide Range Power Supply Voltage Rang...

Страница 12: ...s expired Option 3 2 or 3 3 RECLOSE FAIL TIMER Option 3 2 or 3 3 A RECLOSE FAIL signal is generated by the reclose fail timer if the reclose command from the relay does not cause the controlled breake...

Страница 13: ...ls for the line and bus inputs over the range of 10 to 135 volts This scheme establishes precise voltage conditions under which reclosing can occur Non selection of specific closing conditions prevent...

Страница 14: ...BE1 79S Functional Description 2 5 Figure 1 1 Figure 2 2 Voltage Monitor Conditions Modes and Voltage Levels Diagram Option 2 D or 2 S Only...

Страница 15: ...bus are provided by the dual function front panel controls DL OV and DB OV When the situation occurs in which both a live zone and a dead zone are elected and OV is selected for the live zone the dea...

Страница 16: ...relay is energized and its NC output contact is opened when power is applied to the relay Normal internal relay operating voltage maintains the power supply status output relay continuously energized...

Страница 17: ...BE1 79S Human Machine Interface 3 3 Figure 3 1 Location of Controls and Indicators Figure 3 2 Optional Voltage Monitor Board CONDITION and MODE Switches Location...

Страница 18: ...less than the overvoltage limit setting during the overvoltage limit mode E DB OV Control Option 2 S D This multi turn screw accessible through the front panel provides continuous selection over a ran...

Страница 19: ...This multi turn screw accessible through the front panel provides continuous selection over a range of 10 to 135 volts of the live line voltage monitoring level Adjustment is by small screwdriver Min...

Страница 20: ...BE1 79S Human Machine Interface 3 3 Figure 3 1 Location of Controls and Indicators Figure 3 2 Optional Voltage Monitor Board CONDITION and MODE Switches Location...

Страница 21: ...on disables live line dead bus reclosing On down position enables live line dead bus reclosing CONDITION Switch No 5 Option 2 S D Off up position disables dead line dead bus reclosing On down position...

Страница 22: ...lay model and style number against the requisition and packing list to see that they agree MOUNTING The relay is intended to be vertically mounted in a location relatively free of moisture dust and ex...

Страница 23: ...torage life can be extended if at 1 one year intervals power is applied to the relay for a period of 30 thirty minutes 2 02 01 D1427 01 Removal of the connecting plugs opens the reclosing contact and...

Страница 24: ...ETAIL A A SHOWING THE ADDITION OF WASHERS OVER THE BOSS TO TIGHTEN THE RELAY AGAINST THE PANEL CAS E Figure 4 2 S1 Case Double Ended Semi Flush Mounting Outline Dimensions Side View Figure 4 3 S1 Case...

Страница 25: ...4 4 BE1 79S Installation Figure 4 4 S1 Case Double Ended Projection Mount Outline Dimensions Rear View...

Страница 26: ...BE1 79S Installation 4 5 Figure 4 5 S1 Case Panel Drilling Diagram Semi Flush Mounting...

Страница 27: ...4 6 BE1 79S Installation Figure 4 6 S1 Case Double Ended Projection Mounting Panel Drilling Diagram Rear View Figure 4 7 Control Circuit Connections Typical...

Страница 28: ...BE1 79S Installation 4 7 Figure 4 8 Voltage Sensing Circuit Connections...

Страница 29: ...4 8 BE1 79S Installation Figure 4 9 RI RC and 52b Sensing Circuit Connections...

Страница 30: ...BE1 79S Installation 4 9 Figure 4 10 Internal Connection Diagram With Power Supply Status...

Страница 31: ...5 2 If equipped with Power Supply Status Output Option 2 F and with the unit in a powered up condition verify that the power supply status output contact is energized open terminals 11 and 16 Remove...

Страница 32: ...5 2 BE1 79S Operational Test Figure 5 1 Test Setup Diagram Typical Figure 5 2 Test Setup Diagram Voltage Monitor Option 2 S D...

Страница 33: ...ess to the voltage monitor board CONDITION and MODE switches remove the connecting plugs and remove the cradle assembly from the relay Step 15 Select the LL DB condition by setting CONDITION switch no...

Страница 34: ...50 and 150 milliseconds Step 29 About one minute after S2 was depressed LOCKOUT LED goes out and RESET LED lights Step 30 Set RECLOSE TIME fully clockwise 2 seconds to test maximum reclose time operat...

Страница 35: ...and RESET LED lights Step 46 Press and release S2 and immediately press S3 to simulate a breaker trip followed by an RC signal Step 47 Observe RESET LED goes out No automatic reclosure occurs Step 48...

Страница 36: ...ead line dead bus condition set CONDITION switch no 5 to the on down position Step 4 To select the overvoltage limit OV mode for the live line and or live bus conditions perform one or both of the fol...

Страница 37: ...tions until the associated indicator just lights To check the operation of the relay with the resulting set up perform the following steps Step 11 Momentarily press switch S1 to energize relay K1 Step...

Страница 38: ...operational check The procedures in Section 5 of this manual provide an adequate check to verify proper operation of the relay If the relay fails to function and factory repair is desired contact the...

Страница 39: ...Option 3 from 0 None to 0 No reclose fail timer continuous reclose output until breaker closes Added Option 2 D when Option 2 S is referred to in the manual Added new power supply information to Spec...

Отзывы: