BE1-79S Functional Description
2-7
Figure 2-4. Examples of Optional Voltage Monitor Live and Dead Zones Selection
POWER SUPPLY STATUS OUTPUT (Option 2-D or 2-F)
The power supply status output relay is energized and its NC output contact is opened when power is
applied to the relay. Normal internal relay operating voltage maintains the power supply status output relay
continuously energized with its output contact open. If the power supply output voltage falls below the
requirements of proper operation, the power supply output relay is deenergized, closing the NC output
contact.