SECTION 4 • INSTALLATION
GENERAL
When not shipped as part of a control or switchgear panel, the relays are shipped in sturdy cartons to prevent
damage during transit. Immediately upon receipt of a relay, check the model and part number against the
requisition and packing list to see that they agree. Visually inspect the relay for damage that may have occurred
during shipment. If there is evidence of damage, immediately file a claim with the carrier and notify the Regional
Sales Office, or contact the Sales Representative at Basler Electric, Highland, Illinois.
Proper operation of the relay may be confirmed by performing the operational test procedure (Page 4-6). In the
event the relay is not to be installed immediately, store the relay in its original shipping carton in a moisture and
dust free environment.
DIELECTRIC TEST
Meets IEC 255-5 and exceeds IEEE C37.90-1989, one-minute dielectric (high potential) tests as follows:
All circuits to ground:
2828 Vdc
Input to output circuits:
2000 Vac or 2828 Vdc
Output contacts are surge protected.
MOUNTING
Because the relay is of solid state design, it does not have to be mounted vertically. Any convenient mounting
angle may be chosen. Relay outline dimensions and panel drilling diagrams are shown in Figures 4-1 through
4-6. Dimensions in parentheses are in millimeters.
Содержание BE1-50B
Страница 5: ...iv BE1 50 51B Introduction Periodic Test 5 9...
Страница 39: ...BE1 50 51B Installation 4 3 Figure 4 3 Panel Drilling Diagram S1 Case Semi Flush Mount...
Страница 43: ...BE1 50 51B Installation 4 7 Figure 4 8 DC Control Connections And Jumper Configuration Terminals...
Страница 44: ...4 8 BE1 50 51B Installation Figure 4 9 BE1 50 51B Overcurrent Relay Rear View...
Страница 59: ...8 2 BE1 50 51B Relay Differences Figure 8 1 Location of Controls and Indicators 100 Series Relays...