1-8
BE1-50/51B-General Information
Refer to Tables 1-3 and 1-4 for the time characteristic curve constants.
Constants have been selected to conform to the characteristics of
electromechanical relays over a range of pickup multiples from 1.3 to
40. Values of the constants are available for use in computer relay
setting programs. Timing accuracy is the sum of ±1 cycle and ±2%.
The fixed time characteristic provides delays of 0.0 to 9.9 seconds
corresponding to the time dial setting. The time set is constant over a
range of pickup multiples from 1.0 to 40. Accuracy is ±2% ±1 cycle for
time dial settings of 0.1 and greater.
Table 1-3. Time Characteristic Curve Constants
( Series 100 Relays or Series 200 Relays With SW8-3 Open (OFF) )
Curve Type
Figure
Constants
BE1
Similar To
Number
A
B
C
N
K
R
S
ABB CO-2
1-6
0.2663
0.03393
1.000
1.2969
0.028
0.500
L
ABB CO-5
1-7
5.6143
2.18592
1.000
1.000
0.028
15.750
D
ABB CO-6
1-8
0.4797
0.21359
1.000
1.5625
0.028
0.875
M
ABB CO-7
1-9
0.3022
0.12840
1.000
0.5000
0.028
1.750
I
ABB CO-8
1-10
8.9341
0.17966
1.000
2.0938
0.028
9.000
V
ABB CO-9
1-11
5.4678
0.10814
1.000
2.0469
0.028
5.500
E
ABB CO-11
1-12
7.7624
0.02758
1.000
2.0938
0.028
7.750
B
BS142-B*
1-13
1.4636
0.00000
1.000
1.0469
0.028
3.250
C
BS142-C*
1-14
8.2506
0.00000
1.000
2.0469
0.028
8.000
F
None**
None
0.0000
1.00000
0.000
0.0000
0.000
1.000
Table 1-4. Time Characteristic Curve Constants ( 200 Series Relays With SW8-3 Closed (ON)
Curve Type
Figure
Constants
BE1
Similar To
Number
A
B
C
N
K
R
S
GE IAC 55
1-15
0.0286
0.0208
1.000
0.9844
0.028
0.0940
L
GE IAC 66
1-16
2.3955
0.00000
1.000
0.3125
0.028
7.8001
D
ABB CO-6
1-8
0.4797
0.21359
1.000
1.5625
0.028
0.8750
M
ABB CO-7
1-9
0.3022
0.12840
1.000
0.5000
0.028
1.7500
I
GE IAC 51
1-17
0.2747
0.1042
1.000
0.4375
0.028
0.8868
V
GE IAC 53
1-18
4.4309
0.0991
1.000
1.9531
0.028
5.8231
E
GE IAC 77
1-19
4.9883
0.0129
1.000
2.0469
0.028
4.7742
B
BS142-B*
1-13
1.4636
0.00000
1.000
1.0469
0.028
3.2500
C
BS142-C*
1-14
8.2506
0.00000
1.000
2.0469
0.028
8.0000
F
None**
None
0.0000
1.00000
0.000
0.0000
0.000
1.0000
*
Curves B and C are defined in British Standard BS142 and IEC 255-4 (International
Electrotechnical Commission)
**
Fixed time from 0.1 to 9.9 seconds.
Содержание BE1-50B
Страница 5: ...iv BE1 50 51B Introduction Periodic Test 5 9...
Страница 39: ...BE1 50 51B Installation 4 3 Figure 4 3 Panel Drilling Diagram S1 Case Semi Flush Mount...
Страница 43: ...BE1 50 51B Installation 4 7 Figure 4 8 DC Control Connections And Jumper Configuration Terminals...
Страница 44: ...4 8 BE1 50 51B Installation Figure 4 9 BE1 50 51B Overcurrent Relay Rear View...
Страница 59: ...8 2 BE1 50 51B Relay Differences Figure 8 1 Location of Controls and Indicators 100 Series Relays...