BE1-50/51B-Testing
5-9
Periodic Test
Periodic testing should consist of the following procedures.
Step 1. Verify that the instantaneous pickup is within ±2% of the value set on the dials. Pickup occurs when
the INST output contacts close.
Step 2. Verify that the time pickup is within ±2% of the value set on the dials. Pickup occurs when the LED
turns ON.
Step 3. Verify that the time to trip for the curve and time dial settings at a multiple of six is the same as the
time given on the characteristic curve. Refer to Section 1 for the characteristics curves.
Step 4. Verify that the time to trip for the instantaneous element at a pickup multiple of 2 is not greater than
the time given on the instantaneous characteristic curve. Refer to Section 1 for the instantaneous
characteristic curve.
Step 5. Verify that the 51 AUX contacts close when the time overcurrent element trips.
Step 6. Verify that the targets operate with one ac ampere of trip current in the trip circuits and that they can
be reset using the RESET LEVER.
This completes the periodic test.
Содержание BE1-50B
Страница 5: ...iv BE1 50 51B Introduction Periodic Test 5 9...
Страница 39: ...BE1 50 51B Installation 4 3 Figure 4 3 Panel Drilling Diagram S1 Case Semi Flush Mount...
Страница 43: ...BE1 50 51B Installation 4 7 Figure 4 8 DC Control Connections And Jumper Configuration Terminals...
Страница 44: ...4 8 BE1 50 51B Installation Figure 4 9 BE1 50 51B Overcurrent Relay Rear View...
Страница 59: ...8 2 BE1 50 51B Relay Differences Figure 8 1 Location of Controls and Indicators 100 Series Relays...