BE1-50/51B-Testing
5-1
CAUTION
When testing units with integrating reset characteristics selected, timing may be
affected by the integrating reset.
SECTION 5 • TESTING
GENERAL
When not shipped as part of a control or switchgear panel, the relays are shipped in sturdy cartons to
prevent damage during transit. Immediately upon receipt of a relay, check the model and part number
against the requisition and packing list to see that they agree. Visually inspect the relay for damage that may
have occurred during shipment. If there is evidence of damage, immediately file a claim with the carrier and
notify the Regional Sales Office, or contact the Sales Representative at Basler Electric, Highland, Illinois.
Proper operation of the relay may be confirmed by performing the operational test procedures in this Section.
In the event the relay is not to be installed immediately, store the relay in its original shipping carton in a
moisture and dust free environment.
DIELECTRIC TEST
Meets IEC 255-5 and exceeds IEEE C37.90-1989, one-minute dielectric (high potential) tests as follows:
All circuits to ground:
2828 Vdc.
Input to output circuits:
2000 Vac or 2828 Vdc.
Output contacts are surge protected.
OPERATIONAL TEST PROCEDURE
The following procedure verifies operation of the relay. The test setup of Figures 5-1 and 5-2 are intended
primarily as an illustration of the principles involved. Other test setups known to be capable of testing with
the stated and implied tolerances (including equipment specifically designed for testing relays) may be used.
Test Equipment Required
Current source with a range from 0 to 20 amperes ac (sensing input current).
Current source 0.2 to 3 amperes ac (target operation).
Timer or counter.
Содержание BE1-50B
Страница 5: ...iv BE1 50 51B Introduction Periodic Test 5 9...
Страница 39: ...BE1 50 51B Installation 4 3 Figure 4 3 Panel Drilling Diagram S1 Case Semi Flush Mount...
Страница 43: ...BE1 50 51B Installation 4 7 Figure 4 8 DC Control Connections And Jumper Configuration Terminals...
Страница 44: ...4 8 BE1 50 51B Installation Figure 4 9 BE1 50 51B Overcurrent Relay Rear View...
Страница 59: ...8 2 BE1 50 51B Relay Differences Figure 8 1 Location of Controls and Indicators 100 Series Relays...