BE1-50/51B-217 General Information
1-3
Load Demand Curve
Scenario
Configure the relay such that when the sensed current is:
1.05 times pickup
Time to trip
1.0 hour
1.2 times pickup
Time to trip
1.0 hour
1.5 times pickup
Time to trip
2.0 minutes
4.0 times pickup
Time to trip
0.2 seconds
6.0 times pickup
Time to trip
0.2 seconds
Settings
Position the following switches as designated. (Switch locations are shown in Section 2,
Controls And
Indicators.) Figure 1-2 is a graph showing the timing for the application scenario.
SW8-1
Select nominal operating frequency
SW8-2
OFF (open) no instantaneous delay
SW8-3
OFF (open) no instantaneous delay
SW8-4
ON (closed) integrating reset selected
TIME DIAL
4.0
CURVE
S
TIME PICKUP
Select preferred time pickup level
INST PICKUP
Select preferred instantaneous pickup level
SPECIFICATIONS
BE1-50/51B-217 Overcurrent Relay has the following features and capabilities.
Current Sensing Input
Continuous current: 14 amperes. One second current: 400 amperes.
TIME PICKUP Range
0.5 to 15.9 amperes in 0.1 ampere steps. Setting the TIME PICKUP to
the minimum pickup (0.5 ampere), places the relay in the most sensitive
state and may be used as a safety setting.
TIME Dropout
Dropout occurs at 95% of pickup value.
TIME PICKUP
Accuracy
±2% ±25 milliamperes at or above 0.5 ampere settings.
Frequency Response
A change of ±5 hertz from the nominal 50/60 hertz current causes less
than 0.5% change in the current required for pickup.
TIME DIAL Range
0.0 to 9.9, in 0.1 steps.
INST PICKUP Range
1 to 99 amperes in 1 ampere steps. Setting the INST PICKUP to the
minimum pickup (1.0), places the relay in the most sensitive state and
may be used as a safety setting.
INST Dropout
Dropout occurs at 95% of pickup value.
Содержание BE1-50/51B-217
Страница 19: ...BE1 50 51B 217 General Information 1 14 MULTIPLES OF PICK UP Figure 1 11 Time Characteristic Curve I Inverse...
Страница 26: ...BE1 50 51B 217 Controls and Indicators 2 3 Figure 2 2 Location of Controls and Indicators...
Страница 29: ...BE1 50 51B 217 Functional Description 3 3 Figure 3 1 Functional Block Diagram...
Страница 31: ...BE1 50 51B 217 Installation 4 2 Figure 4 1 Panel Drilling Diagram S1 Case Semi Flush Mount...
Страница 33: ...BE1 50 51B 217 Installation 4 4 Figure 4 3 Panel Drilling Diagram S1 Case Projection Mount...
Страница 35: ...BE1 50 51B 217 Installation 4 6 Figure 4 4 Outline Dimensions BE1 50 51B S1 Case Projection Mount...
Страница 37: ...BE1 50 51B 217 Installation 4 8...
Страница 38: ...BE1 50 51B 217 Installation 4 9 Figure 4 6 DC Control Connections And Jumper Configuration Terminals...
Страница 39: ...BE1 50 51B 217 Installation 4 10 9 8 10 7 5 3 1 6 4 2 CT GND 51 50 AUX D1146 16 04 23 96 OVERCURRENT...
Страница 40: ...BE1 50 51B 217 Installation 4 11 Figure 4 7 BE1 50 51B 217 Overcurrent Relay Rear View...