c) Smoke alarm device placement in large corridors 

d) Smoke alarm device placement in corridors with corner areas

6. Structural features

•  If the height of a room is separated by a platform or gallery, a smoke alarm device must be 

installed below these features if their area exceeds 16 m

2

 and their length and width each 

exceed 2 m.

•  In rooms with a ceiling slope of > 20° with respect to the horizontal, heat pockets can form 

under the top of the ceiling, which prevent smoke reaching the smoke alarm device.

•  Therefore, smoke alarm devices must be installed at least 0.5 m and at most 1 m from the top 

of the ceiling in these room, see figure below.

•  In rooms with a ceiling slope of ≤ 20°, smoke alarm devices must be installed in the middle 

of the ceiling.

Installation example for a slanted roof with an angle of > 20°

Note: Smoke alarm devices can be placed either in the left position (1) or right position (2).

7. Notes for installation at the ceiling

For ceiling with bearer – (height (h) of the bearer ≤ 0.20 m and with a ceiling area of > 36 m

2

 

and ≤ 36 m

2

, respectively)

a) Example for a ceiling > 36 m

2

Key: 

1 = smoke alarm device

Key: 

1 = ceiling area 

2 = bearer

b) Example for ceiling area ≤ 36 m

2

c) Example for ceiling with bearer (height (h) of the bearer > 0.20 m)

In corridors with a max. width of 3 m, the distance between two smoke alarm devices must 

not be more than 15 m. The distance of the smoke alarm device to the short side of the cor-

ridor must not be more than 7.5 m. In areas of crossings, junctions and corners (mitre line) of 

corridors, one smoke alarm device must be installed each. A placement example is shown in 

section 4.

8. Installation

•  Loosen the mounting plate at the back of the device by turning it counter-clockwise
•  Fasten the mounting plate on the ceiling or wall using the enclosed mounting material. Before 

doing so, ensure that the enclosed mounting material is suitable for the structural character-

istics of the ceiling or wall.

•  Place the smoke alarm device into the mounting plate and turn it counter-clockwise until you 

can hear it click into place.

•  Caution: Smoke alarm devices with replaceable battery can only be fastened when the bat-

tery is inserted, because they have a locking mechanism.

The battery pin (red) set to OFF before the device is used (photo on the left). When the device 

is switched on, the battery pin moves (photo on the right).
Make a test after installation

Key: 

1 = ceiling area 

2 = bearer

Ceiling

Ceiling

Ceiling

Ceiling

Ceiling

OFF

ON

OFF

ON

Red battery pin - OFF

Battery pin after installation

Содержание 1697473

Страница 1: ... dB 3m Temperaturbereich 10 C 40 C Luftfeuchtigkeit 95 RH LED Leuchtanzeige Rauchwarnmelder funktioniert ordnungsgemäß LED rotes blinkt alle 344 Sekunden Alarm Modus oder Prüftaste gedrückt Blinken der roten LED und Warnung wird gestartet Stummschaltung des Alarms Stummschaltmodus Die rote LED wird dann einmal alle 10 Sekunden blinken um anzuzeigen dass sich der Alarm des Rauchwarnmel ders im Stum...

Страница 2: ...eckenfeld 36 m2 c Beispiel für Decke mit Unterzug Höhe h des Unterzugs 0 20 m In Fluren mit einer max Breite von 3 m darf der Abstand zwischen zwei Rauchwarnmeldern max 15 m betragen Der Melderabstand zur Stirnfläche des Flures darf nicht mehr als 7 5 m betragen In Kreuzungs Einmündungs und Eckbereichen Gehrungslinie von Fluren ist je weils ein Melder anzuordnen Ein Beispiel für die Anordnung ist ...

Страница 3: ...e elektromagnetische Einflüsse Temperaturfluktuationen die zu die Kondensation der Feuchtigkeit im Rauchmelder führen Im Falle der Arbeiten in der Umgebung des installierten Rauchmelders die falsche Warnungen starten z B Erneuerung der Rauchwarnmelder sollte vorübergehend bedeckt werden oder gelöscht werden Nach Vollendung von der Arbeit muss die ursprüngliche Funktionalität des installierten Rauc...

Страница 4: ...mA 2 μA Sound power level 85 dB 3m Temperature range 10 C 40 C Humidity 95 RH LED indicator Smoke alarm device works correctly LED red flashes every 344 seconds Alarm mode or test button pressed Flashing of the red LED and alarm is started Muting of alarm mute mode The red LED will then flash every 10 seconds to indicate that the alarm of the smoke alarm device is in mute mode Press the test butto...

Страница 5: ...eiling area 36 m2 c Example for ceiling with bearer height h of the bearer 0 20 m In corridors with a max width of 3 m the distance between two smoke alarm devices must not be more than 15 m The distance of the smoke alarm device to the short side of the cor ridor must not be more than 7 5 m In areas of crossings junctions and corners mitre line of corridors one smoke alarm device must be installe...

Страница 6: ...s instruc tions If the smoke alarm device shows damage that will impair its function it must be replaced If the required area around the smoke alarm device is not kept free from objects the installation location must be checked and a new one selected if applicable Test LED 13 Erroneous alarms Erroneous alarms may be caused by welding and cutting soldering and other hot works sawing and grinding wo...

Страница 7: ...rme Stand by 120 mA 2 μA Niveau de puissance acoustique 85 dB 3m Plage de températures 10 C 40 C Humidité relative de l air 95 RH Témoin LED Le détecteur de fumée fonctionne de manière appropriée LED rouge clignote toutes les 344 secondes Mode alarme ou touche de contrôle appuyée La LED rouge clignote et l alerte est lancée Mise en sourdine de l alarme mode silencieux La LED rouge clignote ensuite...

Страница 8: ...lace photo de droite Vérifiez après l installation Légende 1 Zone de plafond 2 solive Plafond Plafond Plafond Plafond Plafond OFF ON OFF ON Broche de pile rouge ETEINT Broche de pile après installation c Disposition du détecteur dans les grands couloirs d Disposition du détecteur dans les grands couloirs avec des zones d angle 6 Spécificités de construction Si une pièce est subdivisée en hauteur p...

Страница 9: ...Si il n y a pas l espace libre nécessaire autour du détecteur de fumée installé il faut vérifier le lieu de montage et le cas échéant décider d un nouvel endroit Test LED 13 Fausses alarmes Les fausse alarmes peuvent se déclencher par Des travaux de soudure ou découpe de brasage ou d autre travaux à chaud des travaux de sciage ou de ponçage de la poussière à cause de la structure ou du nettoyage d...

Страница 10: ...idsvermogens niveau 85 dB 3m Temperatuurbereik 10 C 40 C Luchtvochtigheid 95 RH Led lichtaanduiding Rookmelder werkt normaal Led rood knippert elke 344 seconden Alarm modus of testknop ingedrukt Knipperen van de rode led en waarschuwing wordt gestart Dempen van het alarm dempmodus De rode led zal dan één keer elke 10 seconden knippe ren om aan te duiden dat het alarm van de rookmelder zich in de d...

Страница 11: ...alk b Voorbeeld voor plafond 36 m2 c Voorbeeld voor plafonds met draagbalk hoogte van de draagbalk 0 20 m In gangen met een maximale breedte van 3 m mag de afstand tussen twee rookmelders max 15 m bedragen De afstand van de melder tot het buitenvlak van de gang met niet meer dan 7 5 m bedragen In kruisingen mondingen en hoeken versteklijn van gangen moet telkens een melder aangebracht worden Een v...

Страница 12: ...nigd worden Is er een functionele beschadiging van de rookmelder dan moet hij vervan gen worden Is de vereiste vrije ruimte rond de geïnstalleerde rookmelder niet aanwezig dan moet de montageplaats gecontroleerd worden en indien nodig gewijzigd worden Test LED 13 Valse waarschuwingen Valse alarmen kunnen veroorzaakt worden door Lassen en snijden en ander werk bij hoge temperaturen zagen en schuren...

Отзывы: