Installation
Preparation
Before installing any electric trace heating, the person installing must check if the trace heating has been designed and planned correctly. It is
particularly essential to verify the following points:
▪
complete project planning documentation, operating instructions and installation instructions.
▪
correct selection of the trace heater and accessories with respect to:
calculation of heat losses
max. permissible operating temperature
max. permissible ambient temperature
temperature class
heating circuit length
Before installing, make sure that all piping and equipment is properly installed and pressure tested.
Required tools / equipment
The following tools are required for installation of the BARTEC Self
regulating trace heating systems:
▪
Wire cutters
▪
Insulation resistance meter with a minimum testing voltage of
500 Vdc and a maximum testing voltage of 2500 Vdc.
Unrolling the trace heater
WARNING
Risk of short circuit and/or material damage. Keep the trace
heater ends dry before and during installation.
▪
Unroll the required trace heater in a straight line and cut to the
correct length. Cut off the trace heater ensuring a straight cut.
▪
Do not bend or pinch the trace heater, or pull it over sharp edg-
es.
Installation on pipes
This step is necessary for plastic pipes only since plastic pipes
conduct heat less efficiently than metal pipes do. For metal pipes
continue with step 4.
▪
Place aluminium tape where the trace heater will be attached for
better heat distribution.
CAUTION
Risk of injury and/or material damage. Never step on or drive over
the trace heater. Do not use it as a loop for stepping on.
▪
Install the trace heater in a straight line along the pipe. This
saves time, helps to avoid installation mistakes and prevents
damage to the trace heater during the thermal insulation work.
▪
Preferably install the trace heater in the lower half of the pipe,
but not on the lowest point
. This prevents mechanical damage
and allows for better heat distribution.
▪
If you use multiple trace heaters, position them with an offset of
90°.