Table L: Selecting the appropriate monitoring equipment:
Base your selection on the number and type of trace heating circuits to be installed, the type of continuity monitoring you need, and the area
classification:
TABLE L: Monitoring Equipment Selection Recommendations
Heating circuit type
Application
Monitoring options
Suitable BARTEC monitoring product
Quantity required
Self-regulating heating circuits on pipes
Freeze protection
High profile end seal or
signal light for indication
ELS-200
ELL-200
1 per circuit
Self-regulating heating circuits on pipes
Temperature maintenance or
tight temperature control
High profile end seal
ELS-200
1 per circuit
→ Example
▪
The application is temperature maintenance (25
°C) of a pipe in a hazardous area.
▪
The maintenance team wants to be able to quickly locate the end seal.
appropriate monitoring equipment = ELS
-
200
Step 13: Finalize the required Materials List (BOM):
Accessories including the glass tape for attachment and pipe straps for the components and electrical traced warning labels
→ Example
▪
Heating cable catalog no. (see
Step 1
-
5
beginning on page 6) and required length (see
Step 9
on page 16) =
▪
Temperature control device including power connection enclosure (see
Step 12
on page 18)
▪
High profile end seal for ease of maintenance (see
Step 12
on page 18) =
▪
Accessories (see section
Accessories
on page 27
-
30):
Glass cloth tape (see selection table in section
Accessories
)
Pipe straps (see selection table in section
Accessories
)
Electrically traced warning labels
10PSB2
-
CT
PBTW
-
200
-
E
ELS
-
200
GT
-
164
PC
-
01
HTWL
-
EN
64
m
1 pc.
1
pc.
2 rolls
4 pcs.
10 pcs.