Install the trace heater beginning at the supply point.
▪
Fix it at the distances specified in the project planning documentation. Use the pre-mounted fixing straps to hold the trace heaters in place.
▪
Allow for material addition for the bases.
▪
Align the trace heater exactly and fix it firmly to the bases and the cylinder using additional fixing straps.
▪
To avoid damage to the trace heater, make sure that the fixing straps are not tightened too firmly. It should be possible to move the trace heater
slightly under the fixing straps.
▪
The distances between the fixing straps should not exceed 250 mm.
▪
Finally, place aluminium tape on areas of loose contact of the trace heater.
▪
This step improves heat transfer and prevents insulating material being trapped between the trace heater and the tank.
19
20
21