Technical data
APEX / SILAS
Pressurized Cabinet
Page 38 of 40
01-3704_7D0001_Manual_APC-SPC_20200617_jrs_en.docx
Rev.-
11
Technical data
Product designation
: APC –
APEX pressurized cabinet
SPC –
SILAS pressurized cabinet
Generation
: 4th generation, Pro Series
4th generation, Pro Series
Explosion protection
Erection area
: Ex II 2G / Ex II 2D,
Zone 1 (Gb) / 21 (Db)
Ex II 3G / Ex II 3D,
Zone 2 (Gc) / 22 (Dc)
Protection type
: Ex pxb * IIC Gb
1
Ex pxb * IIIC Db
Ex pyb * IIC Gb
Ex pyb * IIIC Db
Ex pzb * IIC Gb
2
Ex pzb * IIIC Db
Temperature class
: Gas
Dust
T5, T4, T3
T95 °C, T130 °C
Test certificate ATEX
: BVS 20 ATEX E 060 X
BVS 20 ATEX E 061 X
Test certificate IECEx
: IECEx BVS 20.0048X
Ambient conditions
Ambient temperature
: max. -55 °C to + 70 °C (depending on application)
Storage temperature
: Depending on application
IP protection class
: Min. IP 4x
Purging and overpressure parameters
Dimensions
: max. 6000 B x 2400 H x 1200 D mm
Volumes
: max. 17300 dm³
Protective gas
: Instrument air or inert gas
Temperature of protective
gas
:
max. +40 °C
3
Protective gas prepressure
: constant
100… 2500 kPa (1…25 bar)
1
* = As an option, the marking of protection type can be extended by separately certified
components, such as "db", "eb", "ma/mb", "Ex II 2(1)G [ia Ga/Da]” or “Ex II 2(2)G [ib Gb/Db]”.
2
* = As an option, the marking of protection type can be extended by separately certified
components, such as "dc", "ec", "mc", "ic", “Ex II 3(3)G [ic Gc/Dc]”, “Ex II 3(1)G [ia Ga/Da]” or “Ex II
3(2)G [ib Gb/Db]”
3
In the case of higher purging air temperatures, the deviation must be specified on the type plate.
Maximum media temperatures of the components carrying the purging air and maximum operating
temperatures of the fitted components must be considered.