APEX / SILAS
Pressurized Cabinet
Safety
Rev. -
01-3704_7D0001_Manual_APC-SPC_20200617_jrs_en.docx
Page 7 of 40
2
Safety
Intended use
Exclusive purpose
The APEX pressurized cabinet serves exclusively as pressurized enclosure to
EN/IEC 60079-2 and is intended for use in explosion group II, category 2G,
category 2GD or category 2D.
The SILAS pressurized cabinet serves exclusively as pressurized enclosure to
EN/IEC 60079-2 and is intended for use in explosion group II, category 3G,
category 3GD or category 3D.
The permissible operating data of the device used must be observed.
Improper use
Any other use is not in accordance with the intended purpose and may lead to
damage and accidents. The manufacturer will not be liable for any use beyond
that of its intended purpose.
Safety instructions
General
No technical modifications may be performed on the APEX (SILAS)
pressurized cabinet
Do not dry wipe or clean devices in hazardous areas!
Do not open devices in hazardous areas.
The general statutory regulations or guidelines relating to safety at work,
accident prevention and environmental protection legislation must be
observed, e.g. the German Industrial Health and Safety Ordinance
(BetrSichV) or the applicable national regulations.
Wear suitable clothing and footwear in view of the risk of dangerous
electrostatic charges.
Avoid exposure to heat outside the specified temperature range (see
Chapter “General technical data”).
Avoid exposure to moisture.