background image

Manual 2100-654C 

Page 

19 of 34

START UP

THESE UNITS REQUIRE R-410A 

REFRIGERANT AND POLYOL ESTER OIL.

GENERAL

1.  Use separate service equipment to avoid cross 

contamination of oil and refrigerants.

2.  Use recovery equipment rated for R-410A 

refrigerant.

3.  Use manifold gauges rated for R-410A (800 

psi/250 psi low).

4.  R-410A is a binary blend of HFC-32 and HFC-

125.

5.  R-410A is nearly azeotropic—similar to R-22 and 

R-12.  Although nearly azeotropic, charge with 
liquid refrigerant.

6.  R-410A operates at 40-70% higher pressure 

than  R-22 and systems designed for R-22 cannot 
withstand this higher pressure.

7.  R-410A has an ozone depletion potential of zero, 

but must be reclaimed due to its global warming 
potential.

8.  R-410A compressors use Polyol Ester oil.

9.  Polyol Ester oil is hygroscopic; it will rapidly absorb 

moisture and strongly hold this moisture in the oil.

10. A liquid line dryer must be used—even a deep 

vacuum will not separate moisture from the oil.

11. Limit atmospheric exposure to 15 minutes.

12. If compressor removal is necessary, always plug 

compressor immediately after removal.  Purge with 
small amount of nitrogen when inserting plugs.

TOPPING OFF SYSTEM CHARGE

If a leak has occurred in the system, Bard 
Manufacturing recommends reclaiming, evacuating 
(see criteria above) and charging to the nameplate 
charge.  If done correctly, topping off the system 
charge can be done without problems.

With R-410A, there are no significant changes in the 
refrigerant composition during multiple leaks and 
recharges.  R-410A refrigerant is close to being an 
azeotropic blend (it behaves like a pure compound 
or single component refrigerant).  The remaining 
refrigerant charge, in the system, may be used after 
leaks have occurred and then “top-off” the charge by 
utilizing the pressure charts on the inner control panel 
cover as a guideline.

REMEMBER: 

 When adding R-410A refrigerant, it 

must come out of the charging cylinder/tank as a 

liquid to avoid any fractionation, and to ensure optimal 

system performance.  Refer to instructions for the 

cylinder that is being utilized for proper method of 

liquid extraction.

SAFETY PRACTICES

1.  Never mix R-410A with other refrigerants.

2.  Use gloves and safety glasses.  Polyol Ester oils 

can be irritating to the skin, and liquid refrigerant 
will freeze the skin.

3.  Never use air and R-410A to leak check; the 

mixture may become flammable.

4.  Do not inhale R-410A—the vapor attacks 

the nervous system, creating dizziness, loss 
of coordination and slurred speech.  Cardiac 
irregularities, unconsciousness and ultimately 
death can result from breathing this concentration.

5.  Do not burn R-410A.  This decomposition 

produces hazardous vapors.  Evacuate the area if 
exposed.

6.  Use only cylinders rated DOT4BA/4BW 400.

7.  Never fill cylinders over 80% of total capacity.

8.  Store cylinders in a cool area, out of direct 

sunlight.

9.  Never heat cylinders above 125°F.

10. Never trap liquid R-410A in manifold sets, gauge 

lines or cylinders.  R-410A expands significantly 
at warmer temperatures.  Once a cylinder or line is 
full of liquid, any further rise in temperature will 
cause it to burst.

        WARNING

Failure to conform to these practices 

could lead to damage, injury or death.

Содержание W18HA-A

Страница 1: ...HA B W36HA C Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 654C Supersedes 2100 654B Date 7 26 17 W42HA A W42HA B W42HA C W48HA A W48HA B W48HA C W60HA A W60HA B W60HA C...

Страница 2: ...mmended Airflow 31 Table 10 Indoor Blower Performance 31 Table 11 Maximum ESP of Operation Electric Heat Only Tables 32 Table 12 Electric Heat 32 Table 13 Optional Accessories 33 Table 14 Vent and Con...

Страница 3: ...Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contrac...

Страница 4: ...ioning Contractors of America ACCA The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilatin...

Страница 5: ...ficient size to allow a maximum velocity of 400 fpm NOTE If no return air duct is used applicable installation codes may limit this cabinet to installation only in a single story structure FILTERS A 1...

Страница 6: ...y wall mounting brackets which secure the unit to the outside wall surface at both sides A bottom mounting bracket attached to skid for shipping is provided for ease of installation but is not require...

Страница 7: ...42 075 22 432 93 000 9 88 29 88 15 88 29 88 43 88 13 56 37 00 30 00 40 81 35 06 42 81 40 56 3 37 43 00 31 00 10 00 1 44 16 00 10 00 FIGURE 2 All dimensions are in inches Dimensional drawings are not t...

Страница 8: ...ING HEATER ACCESS MIS 3157 A Wall Opening and Hole Location View Right Side View RETURN AIR TOP FLASHING AT TIME OF INSTALLATION OPENING THE SIDE MOUNTING FLANGES AND UNDER SEAL WITH BEAD IT IS RECOMM...

Страница 9: ...LACED BEHIND RETURN AIR Right Side View MIS 3158 A AIR DUCT IS REQUIRED OPENING THE SIDE MOUNTING FLANGES AND UNDER SEAL WITH BEAD IT IS RECOMMENDED THAT A BEAD OF WALL Wall Opening and Hole Location...

Страница 10: ...AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM THE SIDE MOUNTING FLANGES AND UNDER TOP FLASHING AT TIME OF...

Страница 11: ...TO MAINTAIN OPENING COMBUSTIBLE MATERIALS B D E PANEL AIR DUCT IS REQUIRED 32 10 1 2 Right Side View SUPPLY AIR RECOMMENDED 1 CLEARANCE FROM MIS 3789 RAIN FLASHING REQUIRED DIMENSIONS TO MAINTAIN 12 T...

Страница 12: ...bustible materials This is required for the first 3 of ducting It is important to insure that the 1 4 minimum spacing is maintained at all points Failure to do this could result in overheating the com...

Страница 13: ...NIT RETURN AIR WALL STRUCTURE RETURN AIR SUPPLY AIR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT...

Страница 14: ...IC SUPPLYAIRDUCT SUPPLYAIRDUCT SUPPLYAIRDUCT RETURNAIR OPENINGW GRILLE OUTSIDE W GRILLE FALSEWALLINSTALLATION CEILING RAIN FLASHING RAIN FLASHING SUPPLYDUCTMAYBELOCATEDINANATTIC ORBELOWCEILINGRAFTERSA...

Страница 15: ...208V tap The acceptable operating voltage range for the 240 and 208V taps are TAP RANGE 240 253 216 208 220 187 NOTE The voltage should be measured at the field power connection point in the unit and...

Страница 16: ...arning Control BACnet compatible CS9BE THO 3 Stage Heat 3 Stage Cool Programmable Non Programmable HP or Conventional Auto or Manual Changeover Humidity Sensor w dehumidification Motion Sensor wIntell...

Страница 17: ...eded below 15KW 2 Wire required for dehumidification models only Do not add these wires if setting up for modulating control See note 7 W1 E SC SC SC Completestat Model CS9B THO or Model CS9BE THO W2...

Страница 18: ...ntrol signal for modulating ventilation control Optional for ECON Only See vent installation manual 6 Factory installed jumper Remove jumper and connect to N C fire alarm circuit if emergency shutdown...

Страница 19: ...ple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be u...

Страница 20: ...eversing any two line connections to the unit PHASE MONITOR All units with three phase scroll compressors are equipped with a three phase line monitor to prevent compressor damage due to phase reversa...

Страница 21: ...of the outdoor coil Once coil temperature reaches 30 F or below the coil temperature sensor sends a signal to the control logic of the heat pump control and the defrost timer will start accumulating...

Страница 22: ...o the service technician to override or speed up this timing period and shorting out the SPEEDUP terminals for a few seconds can do this Low Pressure Switch Bypass Operation The control has a selectab...

Страница 23: ...SW 1 SW 2 TIME SEC OFF OFF ON ON OFF ON OFF ON 30 60 180 MIS 2668 A OFF LOW PRESSURE BYPASS TIMER SWITCH FACTORY SETTING 120 SECONDS ACCUMULATED DEFROST TIME TIMER FACTORY SETTING 60 MIN ON Model Sett...

Страница 24: ...rmer is bad or the unit wiring is incorrect 10 Check for Compressor output signal Is there 24 volts AC between CC C Yes go to Step 12 No go to Step 13 11 No Y compressor input signal Check thermostat...

Страница 25: ...144374 22 0 43554 60 0 15310 98 0 6098 15 0 139576 23 0 42295 61 0 14921 99 0 5961 14 0 134956 24 0 41077 62 0 14544 100 0 5827 13 0 130506 25 0 39898 63 0 14177 101 0 5697 12 0 126219 26 0 38757 64 0...

Страница 26: ...PA13302 PA13362 A B PA13422 A B C PA13482 A B C PA13602 A B C contain the X13 Series Motors TROUBLESHOOTING GE X13 SERIES ECM2 3 MOTORS If the Motor is Running 1 It is normal for the motor to rock bac...

Страница 27: ...r is failed and will require replacement 24VAC R Signal through thermostat output 24VAC Common 24VAC Common 24VAC R Signal through thermostat output 2 If the motor has proper high voltage and ground a...

Страница 28: ...igerant charge quantity The following pressure tables show nominal pressures for the units Since many installation specific situations can affect the pressure readings this information should only be...

Страница 29: ...143 349 145 373 147 396 149 421 151 448 153 476 155 505 157 535 159 566 161 598 164 632 W42HA 75 62 Low Side High Side 131 319 133 339 135 361 137 384 137 409 139 434 141 460 143 488 145 517 147 547 1...

Страница 30: ...or 2 35 56 61 87 87 110 50 60 70 90 90 125 8 6 6 3 3 2 10 10 8 8 8 6 35 35 35 58 26 52 52 52 50 50 50 60 30 60 60 60 8 8 8 6 10 6 6 6 10 10 10 10 10 10 10 10 W48HA B00 B0Z B06 B09 l B15 l B18 230 208...

Страница 31: ...O Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil 0 1 2 3 4 5 980 9...

Страница 32: ...50 40 35 35 Model ESP W18H W24H A00 A04 A08 50 40 35 W24H B00 B06 50 40 W24H C00 C06 50 40 Model Front Outlet Low Speed High Speed W30H W36H A00 A05 A10 A15 50 40 35 35 50 50 40 40 W30H W36H B00 B06 B...

Страница 33: ...A10 X EHW3TH A15 X EHWH03 B06 X EHW36H B06 X EHWH03 B09 X X EHW3TH B15 X EHW3TH C06 X X EHW3TA C09 X X EHW3TH C15 X X EHW4TH A05 X EHWH42 A05B X EHW4TH A10 X X EHW4TH A15 X EHWH42 A15B X X EHWH04 A20B...

Страница 34: ...art Relay PTCR based X X X SK 111 Start Kit Hard Start X X X BFAD 2 Barometric Fresh Air Damper Standard X BOP 2 Blank Off Plate X WMFADP2 Motorized Fresh Air Damper X WCRVPS2 Commercial Ventilator Sp...

Отзывы: