background image

Manual 2100-654C 

Page 

6 of 34

Clearances Required for Service Access

and Adequate Condenser Airflow

MODELS

LEFT SIDE

RIGHT SIDE

W18H, W24H, W30H, W36H

15"

20"

W42H, W48H, W60H

20"

20"

Minimum Clearances Required to

Combustible Materials

MODELS

SUPPLY AIR DUCT

FIRST 3'

CABINET

W18H/W24H

0"

0"

W30H/W36H

1/4"

0"

W42H/W48H/W60H

1/4"

0"

INSTALLATION

        WARNING

Failure to provide the 1/4" clearance between 

the supply duct and a combustible surface 

for the first 3' of duct can result in fire causing 

damage, injury or death.

WALL MOUNTING INFORMATION

1.  Two holes for the supply and return air openings 

must be cut through the wall as shown in Figures 
3A – D.

2.  On wood frame walls, the wall construction must 

be strong and rigid enough to carry the weight of 
the unit without transmitting any unit vibration.

3.  Concrete block walls must be thoroughly inspected 

to insure that they are capable of carrying the 
weight of the installed unit.

NOTE:

 

Before mounting the heat pump unit, 

consideration should be given to the 

condensate removal from the outdoor coil 

when in heating mode.  The unit must be 

mounted high enough above grade to ensure 

that ice will not build up under the unit and 

come into contact with the base of the unit.  If 

allowed, this could cause damage to the coil 

and other base components.  Also, be sure 

there are no air obstructions to the sides or 

front of the unit, such as bushes or fences, 

that would inhibit condenser airflow.

MOUNTING THE UNIT

1.  These units are secured by wall mounting brackets 

which secure the unit to the outside wall surface at 
both sides.  A bottom mounting bracket, attached 
to skid for shipping, is provided for ease of 
installation, but is not required.

2.  The unit itself is suitable for 0" clearance, but the 

supply air duct flange and the first 3' of supply 
air duct require a minimum of 1/4" clearance to 
combustible material for model series W30, W36, 
W42, W48 and W60.  However, it is generally 
recommended that a 1" clearance is used for 
ease of installation and maintaining the required 
clearance to combustible material.  See Figures 3A 
– D for details on opening sizes.

3.  Locate and mark lag bolt locations and bottom 

mounting bracket location (see Figures 3A – D).

4.  Mount bottom mounting bracket.

5.  Hook top rain flashing, attached to front - right of 

supply flange for shipping, under back bend of top.

 6.  Position unit in opening and secure with fasteners 

sufficient for the application such as 5/16" lag/
anchor/carriage bolts; use 7/8" diameter flat washers 
on the bolts.

7.  Secure rain flashing to wall and caulk across entire 

length of top (see Figures 3A – D).

8.  For additional mounting rigidity, the return air 

and supply air frames or collars can be drilled 
and screwed or welded to the structural wall itself 
(depending upon wall construction).  Be sure to 
observe required clearance if combustible wall.

9.  On side-by-side installations, maintain a minimum 

of 20" clearance on right side to allow access to 
control panel and heat strips, and to allow proper 
airflow to the outdoor coil.  Additional clearance 
may be required to meet local or national codes.

NOTE:

 

Refer to Figures 2 

 7 for dimensions and   

 

various mounting configurations.

Содержание W18HA-A

Страница 1: ...HA B W36HA C Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 654C Supersedes 2100 654B Date 7 26 17 W42HA A W42HA B W42HA C W48HA A W48HA B W48HA C W60HA A W60HA B W60HA C...

Страница 2: ...mmended Airflow 31 Table 10 Indoor Blower Performance 31 Table 11 Maximum ESP of Operation Electric Heat Only Tables 32 Table 12 Electric Heat 32 Table 13 Optional Accessories 33 Table 14 Vent and Con...

Страница 3: ...Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contrac...

Страница 4: ...ioning Contractors of America ACCA The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilatin...

Страница 5: ...ficient size to allow a maximum velocity of 400 fpm NOTE If no return air duct is used applicable installation codes may limit this cabinet to installation only in a single story structure FILTERS A 1...

Страница 6: ...y wall mounting brackets which secure the unit to the outside wall surface at both sides A bottom mounting bracket attached to skid for shipping is provided for ease of installation but is not require...

Страница 7: ...42 075 22 432 93 000 9 88 29 88 15 88 29 88 43 88 13 56 37 00 30 00 40 81 35 06 42 81 40 56 3 37 43 00 31 00 10 00 1 44 16 00 10 00 FIGURE 2 All dimensions are in inches Dimensional drawings are not t...

Страница 8: ...ING HEATER ACCESS MIS 3157 A Wall Opening and Hole Location View Right Side View RETURN AIR TOP FLASHING AT TIME OF INSTALLATION OPENING THE SIDE MOUNTING FLANGES AND UNDER SEAL WITH BEAD IT IS RECOMM...

Страница 9: ...LACED BEHIND RETURN AIR Right Side View MIS 3158 A AIR DUCT IS REQUIRED OPENING THE SIDE MOUNTING FLANGES AND UNDER SEAL WITH BEAD IT IS RECOMMENDED THAT A BEAD OF WALL Wall Opening and Hole Location...

Страница 10: ...AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM THE SIDE MOUNTING FLANGES AND UNDER TOP FLASHING AT TIME OF...

Страница 11: ...TO MAINTAIN OPENING COMBUSTIBLE MATERIALS B D E PANEL AIR DUCT IS REQUIRED 32 10 1 2 Right Side View SUPPLY AIR RECOMMENDED 1 CLEARANCE FROM MIS 3789 RAIN FLASHING REQUIRED DIMENSIONS TO MAINTAIN 12 T...

Страница 12: ...bustible materials This is required for the first 3 of ducting It is important to insure that the 1 4 minimum spacing is maintained at all points Failure to do this could result in overheating the com...

Страница 13: ...NIT RETURN AIR WALL STRUCTURE RETURN AIR SUPPLY AIR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT...

Страница 14: ...IC SUPPLYAIRDUCT SUPPLYAIRDUCT SUPPLYAIRDUCT RETURNAIR OPENINGW GRILLE OUTSIDE W GRILLE FALSEWALLINSTALLATION CEILING RAIN FLASHING RAIN FLASHING SUPPLYDUCTMAYBELOCATEDINANATTIC ORBELOWCEILINGRAFTERSA...

Страница 15: ...208V tap The acceptable operating voltage range for the 240 and 208V taps are TAP RANGE 240 253 216 208 220 187 NOTE The voltage should be measured at the field power connection point in the unit and...

Страница 16: ...arning Control BACnet compatible CS9BE THO 3 Stage Heat 3 Stage Cool Programmable Non Programmable HP or Conventional Auto or Manual Changeover Humidity Sensor w dehumidification Motion Sensor wIntell...

Страница 17: ...eded below 15KW 2 Wire required for dehumidification models only Do not add these wires if setting up for modulating control See note 7 W1 E SC SC SC Completestat Model CS9B THO or Model CS9BE THO W2...

Страница 18: ...ntrol signal for modulating ventilation control Optional for ECON Only See vent installation manual 6 Factory installed jumper Remove jumper and connect to N C fire alarm circuit if emergency shutdown...

Страница 19: ...ple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be u...

Страница 20: ...eversing any two line connections to the unit PHASE MONITOR All units with three phase scroll compressors are equipped with a three phase line monitor to prevent compressor damage due to phase reversa...

Страница 21: ...of the outdoor coil Once coil temperature reaches 30 F or below the coil temperature sensor sends a signal to the control logic of the heat pump control and the defrost timer will start accumulating...

Страница 22: ...o the service technician to override or speed up this timing period and shorting out the SPEEDUP terminals for a few seconds can do this Low Pressure Switch Bypass Operation The control has a selectab...

Страница 23: ...SW 1 SW 2 TIME SEC OFF OFF ON ON OFF ON OFF ON 30 60 180 MIS 2668 A OFF LOW PRESSURE BYPASS TIMER SWITCH FACTORY SETTING 120 SECONDS ACCUMULATED DEFROST TIME TIMER FACTORY SETTING 60 MIN ON Model Sett...

Страница 24: ...rmer is bad or the unit wiring is incorrect 10 Check for Compressor output signal Is there 24 volts AC between CC C Yes go to Step 12 No go to Step 13 11 No Y compressor input signal Check thermostat...

Страница 25: ...144374 22 0 43554 60 0 15310 98 0 6098 15 0 139576 23 0 42295 61 0 14921 99 0 5961 14 0 134956 24 0 41077 62 0 14544 100 0 5827 13 0 130506 25 0 39898 63 0 14177 101 0 5697 12 0 126219 26 0 38757 64 0...

Страница 26: ...PA13302 PA13362 A B PA13422 A B C PA13482 A B C PA13602 A B C contain the X13 Series Motors TROUBLESHOOTING GE X13 SERIES ECM2 3 MOTORS If the Motor is Running 1 It is normal for the motor to rock bac...

Страница 27: ...r is failed and will require replacement 24VAC R Signal through thermostat output 24VAC Common 24VAC Common 24VAC R Signal through thermostat output 2 If the motor has proper high voltage and ground a...

Страница 28: ...igerant charge quantity The following pressure tables show nominal pressures for the units Since many installation specific situations can affect the pressure readings this information should only be...

Страница 29: ...143 349 145 373 147 396 149 421 151 448 153 476 155 505 157 535 159 566 161 598 164 632 W42HA 75 62 Low Side High Side 131 319 133 339 135 361 137 384 137 409 139 434 141 460 143 488 145 517 147 547 1...

Страница 30: ...or 2 35 56 61 87 87 110 50 60 70 90 90 125 8 6 6 3 3 2 10 10 8 8 8 6 35 35 35 58 26 52 52 52 50 50 50 60 30 60 60 60 8 8 8 6 10 6 6 6 10 10 10 10 10 10 10 10 W48HA B00 B0Z B06 B09 l B15 l B18 230 208...

Страница 31: ...O Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil 0 1 2 3 4 5 980 9...

Страница 32: ...50 40 35 35 Model ESP W18H W24H A00 A04 A08 50 40 35 W24H B00 B06 50 40 W24H C00 C06 50 40 Model Front Outlet Low Speed High Speed W30H W36H A00 A05 A10 A15 50 40 35 35 50 50 40 40 W30H W36H B00 B06 B...

Страница 33: ...A10 X EHW3TH A15 X EHWH03 B06 X EHW36H B06 X EHWH03 B09 X X EHW3TH B15 X EHW3TH C06 X X EHW3TA C09 X X EHW3TH C15 X X EHW4TH A05 X EHWH42 A05B X EHW4TH A10 X X EHW4TH A15 X EHWH42 A15B X X EHWH04 A20B...

Страница 34: ...art Relay PTCR based X X X SK 111 Start Kit Hard Start X X X BFAD 2 Barometric Fresh Air Damper Standard X BOP 2 Blank Off Plate X WMFADP2 Motorized Fresh Air Damper X WCRVPS2 Commercial Ventilator Sp...

Отзывы: