background image

Manual 2100-654C 

Page 

15 of 34

WIRING – MAIN POWER

Refer to the unit rating plate for wire sizing information 
and maximum fuse or circuit breaker size.  Each 
outdoor unit is marked with a “Minimum Circuit 
Ampacity”.  This means that the field wiring used must 
be sized to carry that amount of current. Depending 
on the installed KW of electric heat, there may be 
two field power circuits required.  If this is the case, 
the unit serial plate will so indicate.  All models are 
suitable only for connection with copper wire. Each 
unit and/or wiring diagram will be marked “Use Copper 
Conductors Only”.  These instructions 

must be

 

adhered 

to.  Refer to the National Electrical Code (NEC) for 
complete current carrying capacity data on the various 
insulation grades of wiring material.  All wiring must 
conform to NEC and all local codes.

The electrical data lists fuse and wire sizes (75°C 
copper) for all models including the most commonly 
used heater sizes.  Also shown are the number of field 
power circuits required for the various models with 
heaters.

The unit rating plate lists a maximum fuse or circuit 
breaker that is to be used with the equipment.  The 
correct size must be used for proper circuit protection 
and also to assure that there will be no nuisance 
tripping due to the momentary high starting current of 
the compressor motor.

The disconnect access door on this unit may be locked 
to prevent unauthorized access to the disconnect.  To 
convert for the locking capability, bend the tab located 
in the bottom left-hand corner of the disconnect 
opening under the disconnect access panel straight 
out.  This tab will now line up with the slot in the door.  
When shut, a padlock may be placed through the hole 
in the tab preventing entry.

See page 20 for important information on three phase 
scroll compressor start ups.

See Table 8 on page 30 for electrical specifications.

WIRING – LOW VOLTAGE WIRING 

All 230/208V 1 phase and 3 phase equipment have 
dual primary voltage transformers.  All equipment 
leaves the factory wired on 240V tap.  For 208V 
operation, reconnect from 240V to 208V tap.  The 
acceptable operating voltage range for the 240 and 
208V taps are:

 

TAP RANGE

 

240 

253 – 216

 

208 

220 – 187

NOTE:

  The voltage should be measured at the field 

power connection point in the unit and while 

the unit is operating at full load (maximum 

amperage operating condition).

For low voltage wiring, an 18 gauge copper, color-coded 
cable is recommended. See Table 4 on page 16 for 
more information.

Low Voltage Connections

These units use a 24-volt AC low voltage circuit.  
The “

RT

” terminal is the 24V transformer output, 

and the “

R

” terminal is the 24VAC 

hot

 terminal 

for the operation of the equipment.  “

RT

” and “

R

” 

are connected with brass jumper bar which can be 
removed and “

RT

” and “

R

” connected to external 

NC (normally closed) contact such as a fire/smoke 
detector that will cause immediate shutdown of the 
equipment upon activation.

C

” terminal is 

24VAC common and is grounded

.

G

” terminal is the 

fan input

.

Y1

” terminal is the 

1st Stage input for cooling.

Y2

” terminal is the 

2nd Stage compressor input for 

cooling (if equipped with an economizer).

B/W1

” terminal is the 

reversing valve input.  

The 

reversing valve must be energized for heating mode.

W2

” terminal is the 

2nd stage heat

 (if equipped).

W3

” terminal is the 

emergency heat input. 

 This 

terminal energizes the emergency heat relay.  This is 
not applicable on units with dehumification.

A

” terminal is the 

ventilation input

.  This terminal 

energizes any factory-installed ventilation option and 
indoor blower.

D

” terminal is the dehumidification input.  If 

installed, this terminal energizes any factory-installed 
dehumidification option.
"L/1" terminal is the 

compressor lockout output

.  This 

terminal is activated on a high or low pressure trip by 
the electronic heat pump control.  This is a 24VAC 
output.

LOW VOLTAGE CONNECTIONS FOR DDC CONTROL

Standard Units

Units w/

Economizers

Fan Only

Energize G

Energize G

1st Stage 
Cooling Mode

Energize Y1, G

Energize Y1, G

2nd Stage 
Cooling Mode

Energize Y1, Y2, G

Heat Pump Heating

Energize Y1, G, 
B/W1

Energize Y1, G, 
B/W1

2nd Stage Heating

w/heat pump  
(if employed)

Energize Y1, G,  
B/W1, W2

Energize Y1, G,  
B/W1, W2

Ventilation

Energize A

Energize A

Dehumidification

(if employed)

Energize D

Energize D

Emergency Heat*

Energize G, W2, 
W3

Energize G, W2, 
W3

* Not applicable on units with dehumidification

Содержание W18HA-A

Страница 1: ...HA B W36HA C Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 654C Supersedes 2100 654B Date 7 26 17 W42HA A W42HA B W42HA C W48HA A W48HA B W48HA C W60HA A W60HA B W60HA C...

Страница 2: ...mmended Airflow 31 Table 10 Indoor Blower Performance 31 Table 11 Maximum ESP of Operation Electric Heat Only Tables 32 Table 12 Electric Heat 32 Table 13 Optional Accessories 33 Table 14 Vent and Con...

Страница 3: ...Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contrac...

Страница 4: ...ioning Contractors of America ACCA The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilatin...

Страница 5: ...ficient size to allow a maximum velocity of 400 fpm NOTE If no return air duct is used applicable installation codes may limit this cabinet to installation only in a single story structure FILTERS A 1...

Страница 6: ...y wall mounting brackets which secure the unit to the outside wall surface at both sides A bottom mounting bracket attached to skid for shipping is provided for ease of installation but is not require...

Страница 7: ...42 075 22 432 93 000 9 88 29 88 15 88 29 88 43 88 13 56 37 00 30 00 40 81 35 06 42 81 40 56 3 37 43 00 31 00 10 00 1 44 16 00 10 00 FIGURE 2 All dimensions are in inches Dimensional drawings are not t...

Страница 8: ...ING HEATER ACCESS MIS 3157 A Wall Opening and Hole Location View Right Side View RETURN AIR TOP FLASHING AT TIME OF INSTALLATION OPENING THE SIDE MOUNTING FLANGES AND UNDER SEAL WITH BEAD IT IS RECOMM...

Страница 9: ...LACED BEHIND RETURN AIR Right Side View MIS 3158 A AIR DUCT IS REQUIRED OPENING THE SIDE MOUNTING FLANGES AND UNDER SEAL WITH BEAD IT IS RECOMMENDED THAT A BEAD OF WALL Wall Opening and Hole Location...

Страница 10: ...AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM THE SIDE MOUNTING FLANGES AND UNDER TOP FLASHING AT TIME OF...

Страница 11: ...TO MAINTAIN OPENING COMBUSTIBLE MATERIALS B D E PANEL AIR DUCT IS REQUIRED 32 10 1 2 Right Side View SUPPLY AIR RECOMMENDED 1 CLEARANCE FROM MIS 3789 RAIN FLASHING REQUIRED DIMENSIONS TO MAINTAIN 12 T...

Страница 12: ...bustible materials This is required for the first 3 of ducting It is important to insure that the 1 4 minimum spacing is maintained at all points Failure to do this could result in overheating the com...

Страница 13: ...NIT RETURN AIR WALL STRUCTURE RETURN AIR SUPPLY AIR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT...

Страница 14: ...IC SUPPLYAIRDUCT SUPPLYAIRDUCT SUPPLYAIRDUCT RETURNAIR OPENINGW GRILLE OUTSIDE W GRILLE FALSEWALLINSTALLATION CEILING RAIN FLASHING RAIN FLASHING SUPPLYDUCTMAYBELOCATEDINANATTIC ORBELOWCEILINGRAFTERSA...

Страница 15: ...208V tap The acceptable operating voltage range for the 240 and 208V taps are TAP RANGE 240 253 216 208 220 187 NOTE The voltage should be measured at the field power connection point in the unit and...

Страница 16: ...arning Control BACnet compatible CS9BE THO 3 Stage Heat 3 Stage Cool Programmable Non Programmable HP or Conventional Auto or Manual Changeover Humidity Sensor w dehumidification Motion Sensor wIntell...

Страница 17: ...eded below 15KW 2 Wire required for dehumidification models only Do not add these wires if setting up for modulating control See note 7 W1 E SC SC SC Completestat Model CS9B THO or Model CS9BE THO W2...

Страница 18: ...ntrol signal for modulating ventilation control Optional for ECON Only See vent installation manual 6 Factory installed jumper Remove jumper and connect to N C fire alarm circuit if emergency shutdown...

Страница 19: ...ple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be u...

Страница 20: ...eversing any two line connections to the unit PHASE MONITOR All units with three phase scroll compressors are equipped with a three phase line monitor to prevent compressor damage due to phase reversa...

Страница 21: ...of the outdoor coil Once coil temperature reaches 30 F or below the coil temperature sensor sends a signal to the control logic of the heat pump control and the defrost timer will start accumulating...

Страница 22: ...o the service technician to override or speed up this timing period and shorting out the SPEEDUP terminals for a few seconds can do this Low Pressure Switch Bypass Operation The control has a selectab...

Страница 23: ...SW 1 SW 2 TIME SEC OFF OFF ON ON OFF ON OFF ON 30 60 180 MIS 2668 A OFF LOW PRESSURE BYPASS TIMER SWITCH FACTORY SETTING 120 SECONDS ACCUMULATED DEFROST TIME TIMER FACTORY SETTING 60 MIN ON Model Sett...

Страница 24: ...rmer is bad or the unit wiring is incorrect 10 Check for Compressor output signal Is there 24 volts AC between CC C Yes go to Step 12 No go to Step 13 11 No Y compressor input signal Check thermostat...

Страница 25: ...144374 22 0 43554 60 0 15310 98 0 6098 15 0 139576 23 0 42295 61 0 14921 99 0 5961 14 0 134956 24 0 41077 62 0 14544 100 0 5827 13 0 130506 25 0 39898 63 0 14177 101 0 5697 12 0 126219 26 0 38757 64 0...

Страница 26: ...PA13302 PA13362 A B PA13422 A B C PA13482 A B C PA13602 A B C contain the X13 Series Motors TROUBLESHOOTING GE X13 SERIES ECM2 3 MOTORS If the Motor is Running 1 It is normal for the motor to rock bac...

Страница 27: ...r is failed and will require replacement 24VAC R Signal through thermostat output 24VAC Common 24VAC Common 24VAC R Signal through thermostat output 2 If the motor has proper high voltage and ground a...

Страница 28: ...igerant charge quantity The following pressure tables show nominal pressures for the units Since many installation specific situations can affect the pressure readings this information should only be...

Страница 29: ...143 349 145 373 147 396 149 421 151 448 153 476 155 505 157 535 159 566 161 598 164 632 W42HA 75 62 Low Side High Side 131 319 133 339 135 361 137 384 137 409 139 434 141 460 143 488 145 517 147 547 1...

Страница 30: ...or 2 35 56 61 87 87 110 50 60 70 90 90 125 8 6 6 3 3 2 10 10 8 8 8 6 35 35 35 58 26 52 52 52 50 50 50 60 30 60 60 60 8 8 8 6 10 6 6 6 10 10 10 10 10 10 10 10 W48HA B00 B0Z B06 B09 l B15 l B18 230 208...

Страница 31: ...O Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil 0 1 2 3 4 5 980 9...

Страница 32: ...50 40 35 35 Model ESP W18H W24H A00 A04 A08 50 40 35 W24H B00 B06 50 40 W24H C00 C06 50 40 Model Front Outlet Low Speed High Speed W30H W36H A00 A05 A10 A15 50 40 35 35 50 50 40 40 W30H W36H B00 B06 B...

Страница 33: ...A10 X EHW3TH A15 X EHWH03 B06 X EHW36H B06 X EHWH03 B09 X X EHW3TH B15 X EHW3TH C06 X X EHW3TA C09 X X EHW3TH C15 X X EHW4TH A05 X EHWH42 A05B X EHW4TH A10 X X EHW4TH A15 X EHWH42 A15B X X EHWH04 A20B...

Страница 34: ...art Relay PTCR based X X X SK 111 Start Kit Hard Start X X X BFAD 2 Barometric Fresh Air Damper Standard X BOP 2 Blank Off Plate X WMFADP2 Motorized Fresh Air Damper X WCRVPS2 Commercial Ventilator Sp...

Отзывы: