Manual 2100-752C
Page
38 of 41
TABLE 9
Electrical Specifications − Q**A4D Series
Model
Rated Volts
& Phase
Single Circuit
Multiple Circuit
No.
Field
Power
Circuits
Minimum
Circuit
Ampacity
Maximum
External
Fuse or
Ckt. Brkr.
Field
Power
Wire
Size
Ground
Wire
Size
Minimum
Circuit
Ampacity
Maximum
External Fuse
or
Ckt. Brkr.
Field Power
Wire Size
Ground
Wire Size
Ckt.
A
Ckt.
B
Ckt.
A
Ckt.
B
Ckt.
A
Ckt.
B
Ckt.
A
Ckt.
B
Q36A4DA0Z
-A05
-A10
230/208-1
1
1
1
26
31
57
40
40
60
8
8
6
10
10
10
Q36A4DB0Z
-B06
-B09
-B15
230/208-3
1
1
1
1
20
23
32
50
25
25
35
50
10
10
8
8
10
10
10
10
Q36A4DC0Z
-C06
-C09
-C15
460-3
1
1
1
1
11
12
16
25
15
15
20
25
14
14
12
10
14
14
12
10
Q42A4DA0Z
-A05
-A10
230/208-1
1
1
1
31
31
57
50
50
60
8
8
6
10
10
10
Q42A4DB0Z
-B06
-B09
-B15
230/208-3
1
1
1
1
24
24
32
51
35
35
35
60
8
8
8
6
10
10
10
10
Q42A4DC0Z
-C06
-C09
-C15
460-3
1
1
1
1
11
12
16
25
15
15
20
25
14
14
12
10
14
14
12
10
Q48A4DA0Z
-A05
-A10
-A15
230/208-1
1
1
1
1 or 2
33
33
57
85
40
40
60
90
8
8
6
4
10
10
10
8
57
26
60
30
6
10
10
10
Q48A4DB0Z
-B06
-B09
-B15
230/208-3
1
1
1
1
25
25
33
51
30
30
40
60
10
10
8
6
10
10
10
10
Q48A4DC0Z
-C06
-C09
-C15
460-3
1
1
1
1
12
12
16
25
15
15
20
30
14
14
12
10
14
14
12
10
These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical code
(latest version), Article 310 for power conductor sizing.
CAUTION:
When more than one field power circuit is run through one
conduit, the conductors must be derated. Pay special attention to note 8 of Table 310 regarding Ampacity Adjustment Factors
when more than three (3) current carrying conductors are in a raceway.
Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors.
Based on 75°copper wire. All wiring must conform to the National Electrical Code and all local codes.
NOTE:
The Maximum Overcurrent Protection (MOCP) value listed is the maximum value as per UL 1995 calculations for MOCP
(branch-circuit conductor sizes in this chart are based on this MOCP). The actual factory-installed overcurrent protective
device (circuit breaker) in this model may be lower than the maximum UL 1995 allowable MOCP value, but still above the
UL 1995 minimum calculated value or Minimum Circuit Ampacity (MCA) listed.
IMPORTANT:
While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and
conductor wires in accordance with the National Electrical Code and all local codes.
Содержание Q-TEC Q A4D Series
Страница 2: ......
Страница 24: ......
Страница 41: ...Manual 2100 752C Page 17 of 41 MIS 2471 A REMOVE KNOCK OUT FOR INDOOR DRAIN HOSE CONNECTOR FIGURE 18C If used ...
Страница 64: ...Manual 2100 752C Page 40 of 41 GRAPH 2 Q42A4D FAD Ventilation Delivery GRAPH 1 Q36A4D FAD Ventilation Delivery ...
Страница 65: ...Manual 2100 752C Page 41 of 41 GRAPH 3 Q48A4D FAD Ventilation Delivery ...
Страница 66: ......
Страница 81: ...Manual 2110 1568G Page 15 of 17 This page intentionally left blank ...
Страница 84: ......
Страница 95: ......