Manual 2100-752C
Page
24 of 41
FIGURE 21
Thermostat Connections
Thermostat
W1/E
A
YO/D
L
O/B
Y2
Y1
R
G
C
W2
Bard #8403-060
6
10
12
11
9
4
12-Pin
Vent Plug
2
3
5
7
CO2 OUT
Optional CO2 Controller
Bard Part #8403-096
6
5
4
3
2
1
TEMP-OUT
24VAC
W3
6
5
4
2
1
R
Unit Low
Voltage
Term. Strip
W2
C
G
RT
Y1
Y2
B/W1
L
D
A
3
not present if economizer is factory installed. Units with economizers have balanced
Install jumper for 1 stage electric heat on units with more than 10KW
Y1 Y2 jumper
climate jumper in economizer, refer to economizer manual.
Factory installed jumper. Remove jumper to activate Balanced Climate™ mode.
8
7
6
Do not connect "A" from thermostat if optional CO2 controller is used
0-10 VDC modulating C02 control signal for modulating ventilation
control (optional for ECON only - see vent instruction manuals)
5
Change model configuration from heat pump to heat/cool. Must be configured to programmable
and fan set to be programmed fan for the "A" output to function during scheduled occupied
periods. Must be configured for multi-stage for Y1 output to be active 1st stage cooling. For
dehumidification, must be configured for "No Economizer" for YO/D to be active for humidity
control.
4
Factory installed jumper. Remove jumper and connect
to N.C fire alarm circuit if emergency shutdown required.
3
Wire not needed below 15KW.
2
Wire required for dehumidification models only.
1
Do not add these wires if setting up for modulating control. See note 5.
9 A 2-stage thermostat is recommended for Balanced Climate mode.
W1/E
SC
SC
SC
Completestat
Model #CS9B-THOA or
Model #CS9BE-THOA
W2
COM
G
24V
Y1
Y2
O/B
L
D
A
GND
MIS-3974
ALL VENT OPTIONS PLUG IN HERE
2
3
3
1
6
D
4
5
7
If not equipped with a ventilation option to plug in, a jumper plug must be installed.
4
2
8
9
Содержание Q-TEC Q A4D Series
Страница 2: ......
Страница 24: ......
Страница 41: ...Manual 2100 752C Page 17 of 41 MIS 2471 A REMOVE KNOCK OUT FOR INDOOR DRAIN HOSE CONNECTOR FIGURE 18C If used ...
Страница 64: ...Manual 2100 752C Page 40 of 41 GRAPH 2 Q42A4D FAD Ventilation Delivery GRAPH 1 Q36A4D FAD Ventilation Delivery ...
Страница 65: ...Manual 2100 752C Page 41 of 41 GRAPH 3 Q48A4D FAD Ventilation Delivery ...
Страница 66: ......
Страница 81: ...Manual 2110 1568G Page 15 of 17 This page intentionally left blank ...
Страница 84: ......
Страница 95: ......