Manual 7960-923
Page
9 of 10
Energize on Unit
Terminal Strip
Mode
Occupied/
Unoccupied
Inputs to the Board
Outputs
from the
Board
Y
W2
A1
D
TWV
YO
G1
Y1, G
Cooling
Unoccupied
X
X
X
Y1, G, A
Cooling
Occupied
X
X
X
X
Y1, G, A, D
Cooling w/Dehum
Occupied
X
X
X
X
X
Y1, G, D
Cooling w/Dehum
Unoccupied
X
X
X
X
G, B/W1
1st Stage Electric Heat
Unoccupied
X
X
G, B/W1, A
1st Stage Electric Heat
Occupied
X
X
X
G, B/W1, A, D
1st Stage Electric Heat w/Dehum
Occupied
X
X
X
G, B/W1, D
1st Stage Electric Heat w/Dehum
Unoccupied
X
X
G, B/W1, W2
2nd Stage Electric Heat
Unoccupied
X
X
G, B/W1, W2, A
2nd Stage Electric Heat
Occupied
X
X
X
G, B/W1, W2, A, D
2nd Stage Electric Heat and Dehum
Occupied
X
X
X
G, B/W1, W2, D
2nd Stage Electric Heat and Dehum
Unoccupied
X
X
D
Dehum
Unoccupied
X
X
X
X
D, A
Dehum
Occupied
X
X
X
X
X
TABLE 3
Dehumidification Relay Logic Board
Cooling takes precedence over dehumidification. A cooling call cancels dehumidification.
The dehumidification input “D” is not received by the board because of an isolation relay that is energized by the call for heating (B/
W1). Thus, the heating call (B/W1) always takes precedence over dehumidification.
The relay logic board has a jumper (J1) on it to choose between “any-time dehumidification” and “occupied dehumidification”. The
factory default is P1-P2. With the jumper in the P1-P2 position, dehumidification is available any time there is a “D” input to the
relay logic board. With the jumper in the P2-P3 position, dehumidification is available when there is an occupancy signal to the “A1”
terminal, “D” would also need to be energized to dehumidify.
Refer to sequence of operation. In most cases cooling and heating modes take priority over dehumidification.
Содержание Q-TEC Q A4D Series
Страница 2: ......
Страница 24: ......
Страница 41: ...Manual 2100 752C Page 17 of 41 MIS 2471 A REMOVE KNOCK OUT FOR INDOOR DRAIN HOSE CONNECTOR FIGURE 18C If used ...
Страница 64: ...Manual 2100 752C Page 40 of 41 GRAPH 2 Q42A4D FAD Ventilation Delivery GRAPH 1 Q36A4D FAD Ventilation Delivery ...
Страница 65: ...Manual 2100 752C Page 41 of 41 GRAPH 3 Q48A4D FAD Ventilation Delivery ...
Страница 66: ......
Страница 81: ...Manual 2110 1568G Page 15 of 17 This page intentionally left blank ...
Страница 84: ......
Страница 95: ......