Manual 2100-752C
Page
8 of 41
Minimum Installation Height
The minimum installation height of the unit with a free
blow plenum is 8' 6". This provides enough clearance
for the plenum to be removed (see Figure 5).
The minimum installation height for ducted
applications is 8' 4-1/2". This provides enough
clearance to install the duct work (see Figure 6).
FIGURE 5
Installation with Duct-Free Plenum
8 FT. - 5 IN.
8 FT. - 6 IN.
MINIMUM REQUIRED
INSTALLATION HEIGHT
MIS-4174
FLOOR
MIS-4174
FIGURE 6
Ducted Application
7 FT. - 4 IN.
UNIT HEIGHT
8 FT. - 7 IN.
MINIMUM RECOMENDED
CEILING HEIGHT
MIS-4175
12 IN.
MINIMUM
BOTTOM
TO DUCT
2 IN. MINIMUM
FROM DUCT
FLANGE
8 FT. - 4.5 IN.
MINIMUM REQUIRED
INSTALLATION HEIGHT
DUCT FLANGE
DUCT
FLOOR
20 IN.
MINIMUM
FIXED CEILING
SUSPENDED CEILING
MIS-4175