Manual 2100-752C
Page
36 of 41
FIGURE 29
Fan Blade Setting
TABLE 7
Fan Blade Dimensions
R-410A Refrigerant Charge
This unit was charged at the factory with the quantity of
refrigerant listed on the serial plate. AHRI capacity and
efficiency ratings were determined by testing with this
refrigerant charge quantity.
The following pressure tables show nominal pressures
for the units. Since many installation specific situations
can affect the pressure readings, this information
should only be used by certified technicians as a guide
for evaluating proper system performance. They shall
not be used to adjust charge. If charge is in doubt,
reclaim, evacuate and recharge the unit to the serial
plate charge
.
Removal of Fan Shroud
1. Disconnect all power to the unit before servicing.
2. The unit can be rolled into the room, or the wall
sleeve louver can be removed from outside of the
building to access the condenser coil for cleaning
or to service the outdoor fan.
3. The fan shroud and motor assembly can be
removed from the unit by four (4) screws and the
coil top fill, then the six (6) screws from the shroud
sides. Fan motor must be unplugged from motor
controller. The assembly can now be lifted/slid out
from the condenser section (see Figure 30).
4. The fan assembly or coil can now be serviced.
5. Reverse the steps to reassemble.
MIS-983
FIGURE 30
Fan Shroud Removal
MIS-4215
COND. COIL COVER
HAS TO BE REMOVED TO
FAN ASSEMBLY
SLIDE OUT FAN ASSEMBLY
(SLIDE UP TO REMOVE)
BEFORE REMOVING, UNPLUG
FAN MOTOR WIRE FROM
FAN MOTOR CONTROL
Condenser coil
cover has to be
removed to slide
out fan assembly.
MIS-4215
Before removing, unplug
fan motor wire from fan
motor control.
Fan assembly (slide
up to remove).
Model
Dimension
A
Q36A4
Q42A4
Q48A4
.50"
Fan Blade Setting Dimensions
The correct fan blade setting for proper air delivery
across the outdoor coil is shown in Figure 29. Refer to
Table 7 for unit specific dimension.
Any service work requiring removal or adjustment in the
fan and/or motor area will require that the dimensions
below be checked and blade adjusted in or out on the
motor shaft accordingly.
Содержание Q-TEC Q A4D Series
Страница 2: ......
Страница 24: ......
Страница 41: ...Manual 2100 752C Page 17 of 41 MIS 2471 A REMOVE KNOCK OUT FOR INDOOR DRAIN HOSE CONNECTOR FIGURE 18C If used ...
Страница 64: ...Manual 2100 752C Page 40 of 41 GRAPH 2 Q42A4D FAD Ventilation Delivery GRAPH 1 Q36A4D FAD Ventilation Delivery ...
Страница 65: ...Manual 2100 752C Page 41 of 41 GRAPH 3 Q48A4D FAD Ventilation Delivery ...
Страница 66: ......
Страница 81: ...Manual 2110 1568G Page 15 of 17 This page intentionally left blank ...
Страница 84: ......
Страница 95: ......