Manual 2100-749
Page
59 of 68
Issue
Possible
Cause
Possible Remedy
Impeller/fan not
running smoothly
Imbalance in
rotating parts
Clean the device (make sure weight clips are not removed during cleaning);
replace if imbalance persists after cleaning.
Motor not
turning
Mechanical
blockage
Switch off unit, isolate from power supply and remove blockage.
Line voltage faulty
Check line voltage, restore power supply.
WARNING:
Line Voltage error resets
automatically and motor will start without warning.
Faulty
connection
Switch off, isolate from power supply and correct connection. See connection
table on page 58.
Broken motor winding Replace motor.
Inadequate cooling
Allow motor to cool down, clean or improve cooling.
High ambient
temperature
Allow motor to cool down.
Impermissible
operating point
(e.g., back pressure
too high)
Correct static issue, allow motor to cool down.
TABLE 18
Blower/Condenser Fan Troubleshooting
LED Warning/Status Codes
The LED shows the blower/fan motor status with
various colors and flash codes and is visible through a
small window on the terminal cover of the blower/fan
assembly.
Green: No warning of fault.
# of
Pulses
Motor Status
Manual Reset
Required
Possible Cause
Possible Remedy
1
Phase Failure/Line
Under Voltage
No
Missing phase/poor line
voltage quality
Check line voltage.
3
Inverter Output
Overheating
Yes
Dirty electronics
housing
Clean inverter housing/improve cooling.
4
Communication Error
No
External power supplied
to V out for setting
parameters (internal error)
Remove power to unit. Wait. Switch power back on.
6
Motor Overheating
Yes
-
-
7
Hall Sensor Fault
Yes
Internal error
Remove power to unit. Wait. Switch power back on.
8
Motor Locked
No
Mechanical blockage
Remove power. Verify rotor is free to turn. Re-apply
power and verify operation.
9
Speed Limit Exceeded
No
-
-
11
Rotor Position Sensor
Calibration Error
No
Rotor position sensor
needs calibration
Replace and return to manufacturer.
13
DC-Link Under Voltage
No
Line voltage incorrect
Check applied line voltage to motor.
TABLE 19
Blower/Condenser Fan Motor Flash Codes
Orange: Warning. Device is operating out of range but
no user action is required.
Red (flashing): There is at least one fault. Flash codes
are displayed as on/off pulse at 2Hz. Each code is
followed by a 3-second pause. Multiple flash codes will
be displayed in succession.