It is important to check the software version
during installation to ensure that the latest
version has been installed. Current software
versions and installation instructions are
available on the Bard website at
http://www.
bardhvac.com/software-download/
NOTICE
FIGURE 9
Software Version
X: The letter X represents a major change to the
software effecting product compatibility or function
of the equipment.
Y: The letter Y represents a minor change to the
software that either adds, removes or alters a feature
of the equipment.
Z: The letter Z represents a change to the software that
fixes existing features or user interface.
Product
Software Name
MULTI-TEC
MTS1000
FUSION-TEC (WR)
WTS1000
MEGA-TEC
MGS1000
LC6000
LCS6000
TABLE 4
Software Versioning Guide
Alarm Log
The alarm log screens show a log of each alarm. There
will be a log for when alarm occurred and if the alarm
auto clears, it will show when the alarm cleared. See
page 13 for information on clearing alarms.
Executing a Self Test
This unit has the ability to perform a self test that will
operate all available unit functions in order to quickly
determine unit operation. With the exception of step
times, self test parameters are not adjustable.
The self test will automatically skip sections of the test
based on the model number entered into the controller.
If position 10 of the model number is B (to indicate
"no vent" option), the economizer open and close steps
will be skipped. If positions 8 and 9 of the model
number indicate a 0Z (0 kW) option, steps G,H and I
will be skipped. If position 8 and 9 indicate a 09 (9
kW) option, step H will be skipped.
To execute a self test:
1. Press MENU key to access the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to
Sys Config
;
press ENTER key.
4. Press UP or DOWN keys to scroll to
Self Test A11
screen.
5. Press ENTER key to scroll to
Enable
parameter
(see Figure 10).
6. Press UP or DOWN key to change value to
Yes
. The
self test will begin.
FIGURE 10
Executing Self Test
Software Versioning Guide
MGS1000.X.Y.Z
Software Name: The name of the software is the
base part number used to identify which product the
software is used in.
Self Test Parameter Descriptions
Damper Time: This is the time (in seconds) allowed for
both the opening sequence and closing sequence.
Heat/Cool Time: This is the time (in seconds) allowed
for cooling sequence and heating sequence.
Status: This will display what the unit is doing as
the self test progresses. The following messages may
appear: