Manual 2100-749
Page
12 of 68
FIGURE 11
Restoring Factory Default Settings
FIGURE 12
Restoring Factory Default Settings
–
Remove USB Device
Self Test Off
Initializing...
Opening Economizer
Closing Economizer
Compressor 1 On
Compressor 1 & 2 On
C1 Full Load + C2 On
Turning Comp. Off....
Electric Heat 1 On
Electric Heat 1 & 2 On
Turning Heat Off...
End
The unit will determine which items to test based on
the unit model number.
Reset to Factory Defaults
To reset to factory default settings:
1. Press MENU key to go to the Main Menu screen.
2. Use UP or DOWN keys and ENTER key to enter
ENGINEER password 9254.
3. Press UP or DOWN keys to scroll to
Settings
; press
ENTER key.
4. Press UP or DOWN keys to scroll to
Initialization
;
press ENTER key.
5. Press UP or DOWN keys to scroll to the
DEFAULT
INSTALLATION
screen.
6. Press ENTER key to scroll to
Reset to Factory
Defaults:
(see Figure 11).
7. Press UP or DOWN key to change value to
YES
;
press ENTER key.
8. System will restart with default values.
The controller can only be factory reset when the
USB port is not in use. When the USB port is in use,
a message will appear and the option to reset factory
defaults will not be available (see Figure 12).
Configuration File
The controller will automatically save all of the
configured parameters to a file that can be accessed by
connecting a laptop to the controller with a micro USB
cable. This file can be used to copy the setting of one
board to another board.
The file is located in the main directory of the
controller and is labeled "MG_Config". Copy this file to
a location on the laptop and then disconnect from the
first board. Connect to the second board and copy the
file to the second board. Disconnect the laptop from
the second board and power cycle the controller. The
second board will now have the same settings as the
first board.