Manual 2100-749
Page
48 of 68
8301-089 Outdoor Temperature/Humidity Sensor
FIGURE 72
8301-089 Sensor Electrical Connections and DIP Switches
8301-089 Sensor Connections
This unit utilizes a two-wire 4-10mA signal from
the 8301-089 sensor to communicate outdoor
humidity and a 10KΩ Type III (AN) thermocouple
from the 8301-089 sensor to communicate outdoor
temperature. The humidity sensor is connected to
the sensor control board via the J13 connector. The
thermocouple wires are loose in the sensor housing and
require a butt splice connector or wire nut to connect
to the main unit wiring harness. See Figures 72 and 73
for sensor wiring and terminal location.
Tables 13 and 14 on pages 50 and 52 are correlation
charts for troubleshooting the sensor with a test meter:
Table 13: Temperature to Thermocouple Resistance
Table 14: Relative Humidity to Humidity Sensor
Current Output
8301-089 temperature/humidity sensor
located on upper right side of unit. Remove
cover by turning counter clockwise. Be sure
to replace cover after accessing.
FIGURE 73
8301-089 Sensor Terminal Connections