Manual 2100-614K
Page
22 of 61
Folder
SNMP Points List
Description
AlarmStatus
HighTempAlarm2
High temperature 2 alarm
AlarmStatus
PowerLossUnit1
Power loss alarm for unit 1
AlarmStatus
PowerLossUnit2
Power loss alarm for unit 2
AlarmStatus
Unit1Lockout
Unit 1 lockout alarm
AlarmStatus
Unit2Lockout
Unit 2 lockout alarm
Temperatures
LocalRoomTemp
Local room temperature
Temperatures
RemoteSensor1Temp
Remote sensor 1 temperature
Temperatures
RemotesSensor2Temp
Remote sensor 2 temperature
Setpoints
CoolingSetpoint
Cooling Setpoint
Setpoints
HeatingSetpoint
Heating Setpoint
Setpoints
HighTempAlarm1Setpoint
High Temperature alarm 1 setpoint
Setpoints
HighTempAlarm2Setpoint
High temperature 2 alarm setpoint
Setpoints
LowTempAlarmSetpoint
Low temperature alarm setpoint
GeneralStatus
GeneratorRunning
Generator run status
GeneralStatus
AlarmBoardConnected
Alarm board connected status
GeneralStatus
ComfortMode
Comfort mode status
GeneralStatus
ControllerLocked
Controller Locked Status
SystemStatus
LeadUnitHVAC1
Lead unit is HVAC 1
SystemStatus
LeadUnitHVAC2
Lead unit is HVAC 2
SystemStatus
Unit1Fan
Unit 1 fan status
SystemStatus
Unit2Fan
Unit 2 fan status
Operation Status
CoolingStage1
Stage 1 cooling status
Operation Status
CoolingStage2
Stage 2 cooling status
Operation Status
CoolingStage3
Stage 3 cooling status
Operation Status
CoolingStage4
Stage 4 cooling status
Operation Status
HeatingStage1
Stage 1 heating status
Operation Status
HeatingStage2
Stage 2 heating status
Operation Status
HeatingStage3
Stage 3 heating status
Operation Status
HeatingStage4
Stage 4 heating status
Operation Status
DehumidificationActive
Dehumidificaiton status
Events
trapFireSmokeShutdown
Fire smoke shutdown trap
Events
trapControllerFailure
Controller failure trap
Events
trapHighTempAlarm1
High temperature alarm 1 trap
Events
trapHighTempAlarm2
High temperature alarm 2 trap
Events
trapPowerLossUnit1
Power loss alarm for unit 1 trap
Events
trapPowerLossUnit2
Power loss alarm for unit 2 trap
Events
trapUnit1Lockout
Unit 1 Lockout alarm trap
Events
trapUnit2Lockout
Unit 2 lockout alarm trap
Events
trapGeneratorRunning
Generator running trap