TABLE 2
Temperature Sensor Table
Value measured at sensor connections to the main controller board with controller powered up
F
Kelvin
VDC
60
288.7056
2.887
61
289.2611
2.893
62
289.8167
2.898
63
290.3722
2.904
64
290.9277
2.909
65
291.4832
2.915
66
292.0387
2.920
67
292.5942
2.926
68
293.1497
2.931
69
293.7052
2.937
70
294.2607
2.943
71
294.8162
2.948
72
295.3717
2.954
73
295.9272
2.959
74
296.4827
2.965
75
297.0382
2.970
76
297.5937
2.976
77
298.1492
2.981
78
298.7047
2.987
79
299.2602
2.993
80
299.8157
2.998
81
300.3712
3.004
82
300.9267
3.009
F
Kelvin
VDC
83
301.4822
3.015
84
302.0377
3.020
85
302.5932
3.026
86
303.1487
3.031
87
303.7042
3.037
88
304.2597
3.043
89
304.8152
3.048
90
305.3707
3.054
91
305.9262
3.059
92
306.4817
3.065
93
307.0372
3.070
94
307.5927
3.076
95
308.1482
3.081
96
308.7037
3.087
97
309.2592
3.093
98
309.8147
3.098
99
310.3702
3.104
100
310.9257
3.109
101
311.4812
3.115
102
312.0367
3.120
103
312.5922
3.126
104
313.1477
3.131
105
313.7032
3.137
NOTES
1. If sensor is connected in reverse (copper wire to AG terminal and silver wire to CU terminal), the voltage across the two
terminals will measure approximately .7vDC. Controller must be "On".
2. If sensor connected with reverse polarity, the display should read 00.
3. Cannot check sensor by disconnecting leads and measuring ohms, but ohmmeter can be used to check for bad sensor
(infinity would = open and continuity = shorted).
4. If sensor is open or lead broken/disconnected, the display will show the setpoint.
5. If sensor appears to be OK, try reconnecting to either R1 or R2 input terminals. If controller now works OK, something
wrong with "Loc" input circuit. OK to leave this way.
6. If more than one sensor is connected and one fails, the controller will operate OK from the functional sensor.
7. If only one sensor and it fails or is disconnected, 1st stage cooling will default "On" if it was calling for cooling when
sensor went out. If additional stages were on at the time, they will turn off.