background image

Manual

2100-317J

Page

9 of 39

APPLICATION AND LOCATION

GENERAL

Units are shipped completely assembled and internally
wired, requiring only duct connections, thermostat
wiring, 230/208 volt AC power wiring, and water
piping.  The equipment covered in this manual is to be
installed by trained, experienced service and installation
technicians.  Any heat pump is more critical of proper
refrigerant charge and an adequate duct system than a
cooling only air conditioning unit.

These instructions and any instructions packaged with
any separate equipment required to make up the entire
heat pump system should be carefully read before
beginning the installation.  Note particularly any tags
and/or labels attached to the equipment.

While these instructions are intended as a general
recommended guide, they do not in any way supersede
any national and/or local codes.  Authorities having
jurisdiction should be consulted before the installation
is made.

SHIPPING DAMAGE

Upon receipt of the equipment, the carton should be
checked for external signs of shipping damage.  If
damage is found, the receiving party must contact the
last carrier immediately, preferably in writing,
requesting inspection by the carrier’s agent.

APPLICATION

Capacity of the unit for a proposed installation should
be based on heat loss calculations made in accordance
with methods of the Air Conditioning Contractors of
America, formerly National Warm Air Heating and Air
Conditioning Association.  The air duct system should
be sized and installed in accordance with Standards of
the National Fire Protection Association for the
Installation of Air Conditioning and Venting systems of
Other than Residence Type NFPA No. 90A, and
residence Type Warm Air Heating and Air Conditioning
Systems, NFPA No. 90B.

LOCATION

The unit may be installed in a basement, closet, or
utility room provided adequate service access is insured.
The unit is shipped from the factory as a right hand
return and requires 

access clearance of two feet

minimum to the access panels on this side of the
unit. 

 If unit is to be field converted to left hand return

the opposite side will require access clearance of two
feet minimum.

Unit may be field converted to left hand return by
removing four (4) screws that secure the control panel
cover, removing two (2) screws that hold the control
panel in place, sliding the control panel through the

compressor compartment and re-securing the control
panel on the opposite side of the water coil.  (See Figure
2.)  The two (2) access doors from the right hand return
can be transferred to the left-hand return side and the
one (1) left hand panel can be transferred to the right
hand side.

Unit casing suitable for 0 inch clearance with 1-inch
duct clearance for at least the first 4 feet of duct.  These
units are not approved for outdoor installation and
therefore must be installed inside the structure being
conditioned.  

Do not locate in areas subject to freezing

in the winter or subject to sweating in the summer.

Before setting the unit, consider ease of piping, drain
and electrical connections for the unit.  Also, for units
which will be used with a field installed heat recovery
unit, consider the proximity of the unit to the water
heater or storage tank.  Place the unit on a solid base,
preferably concrete, to minimize undesirable noise and
vibration.  

DO NOT 

elevate the base pan on rubber or

cork vibration eliminator pads as this will permit the
unit base to act like a drum, transmitting objectionable
noise.

DUCTWORK

If the unit is to be installed in a closet or utility room
which does not have a floor drain, a secondary drain pan
under the entire unit is highly recommended.

DO NOT

 install the unit in such a way that a direct path

exists between any return grille and the unit.  Rather,
insure that the air entering the return grille will make at
least one turn before entering the unit or coil.  This will
reduce possible objectionable compressor and air noise
from entering the occupied space.

Design the ductwork according to methods given by the
Air Conditioning Contractors of America.  When duct
runs through unconditioned spaces, it should be
insulated with vapor barrier.  It is recommended that
flexible connections be used to connect the ductwork to
the unit in order to keep the noise transmission to a
minimum.

     WARNING

Failure to provide the 1-inch clearance
between the supply duct and a combustible
surface for the first 3 feet of duct can result in
a fire.

Содержание GSVS242-A

Страница 1: ...ures 45 75 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned Manual 2100 317J Supersedes 2100 317I File Volume I Tab 8 Date 05 16 08 INSTALLATION INSTRUCTIONS WAT...

Страница 2: ...rvice Service Hints 32 Unbrazing System Components 32 Troubleshooting GE ECM Motors 33 34 Accessories Add On DPM26A Pump Module Kit 35 General 35 Installation 35 Ground Source Heat Pump Performance Re...

Страница 3: ...rocedures for Ground Source IGSHPA Heat Pump Systems Soil and Rock Classification for IGSHPA the Design of Ground Coupled Heat Pump Systems Ground Source Installation Standards IGSHPA Closed Loop Geot...

Страница 4: ...1 1 0 6 S V S G 0 2 0 0 6 0 0 0 9 0 0 6 1 0 0 6 1 0 0 9 1 1 Motor will deliver consistent CFM through voltage supply range with no deterioration 197 253V for all 230 208V models 2 Continuous CFM is th...

Страница 5: ...m A t i u c r i C m u m i n i M 0 5 1 0 7 1 0 0 2 0 4 2 0 6 2 0 5 3 e z i S e r i W d l e i F 4 1 4 1 2 1 0 1 0 1 8 r e k a e r B t i u c r i C r o x a M e s u F y a l e D 0 2 5 2 0 3 5 3 0 4 5 5 8 0...

Страница 6: ...H t F 3 0 0 1 1 3 2 4 2 4 1 8 2 3 0 0 1 1 3 2 5 3 8 1 2 2 4 3 4 1 0 3 3 0 8 1 5 1 4 6 4 2 2 7 1 5 6 8 1 9 2 4 8 2 3 7 5 7 7 8 2 2 6 6 7 6 6 2 4 1 6 0 3 2 1 3 5 7 7 4 1 0 1 1 3 3 4 0 0 0 1 8 3 7 2 0 3...

Страница 7: ...86 F FIGURE 1 UNIT DIMENSIONS s t i n U h t d i W h t p e D t h g i e H y l p p u S n r u t e R t c u D e g n a l F h t d i W t h g i e H A B C D E F G H I J K L M N O P Q R S T U V W 2 4 4 2 S V S G...

Страница 8: ...C 4 1 A A V S G 3 H E 1 8 0 2 0 4 2 3 6 5 5 3 1 5 3 0 6 4 7 8 4 3 1 0 1 3 4 5 4 3 4 0 7 0 8 4 y l n O 0 6 8 4 S V S G s e g a k c a P r e t a e H d e l l a t s n I d l e i F l a n o i t p O s n o i t...

Страница 9: ...ire access clearance of two feet minimum Unit may be field converted to left hand return by removing four 4 screws that secure the control panel cover removing two 2 screws that hold the control panel...

Страница 10: ...LE DOORS ARE ON CONTROL PANEL SIDE AND SINGLE DOOR ON OPPOSITE SIDE 1 REMOVE 4 SCREWS SECURING COVER 2 REMOVE 2 SCREWS HOLDING CONTROL BOX TO CORNER PANEL REMOVE 2 SCREWS SECURING PANEL TO BASE 3 PASS...

Страница 11: ...on the pipe and dripping on finished floors or the ceiling under the unit A trap MUST BE installed in the drain line and the trap filled with water prior to start up The use of plugged tees in place o...

Страница 12: ...IGURE 4 PIPING ACCESS TO UNIT WATER IN CONNECTION 3 4 FPT GSVS24 42 MODELS 1 FPT GSVS48 60 MODELS PUMP MODULE CONNECTIONS 1 2 COPPER STUB WATER OUT CONNECTION 3 4 FPT GSVS24 42 MODELS 1 FPT GSVS48 60...

Страница 13: ...the control circuit transformer 2 The maximum total distance of the control circuit wiring Table 6 should be used to determine proper gauge of control circuit wring required Example 1 Control Circuit...

Страница 14: ...airflow in the dehumidify mode By reducing the airflow about 15 the air coil runs colder and thus extracts more moisture This can increase latent capacity from 5 to 13 based on the R H conditions of...

Страница 15: ...Manual 2100 317J Page 15 of 39 FIGURE 5 BLOWER CONTROL BOARD SEE HUMIDITY CONTROL SEE TABLE 8 SEE TABLE 8 SEE TABLE 8 SEE TABLE 8 SEE CFM LIGHT...

Страница 16: ...Manual 2100 317J Page 16 of 39...

Страница 17: ...Manual 2100 317J Page 17 of 39...

Страница 18: ...r system to overcome the pressure of head loss in 1 2 inch or 3 4 inch household plumbing A closed loop earth coupled heat pump system however is separated from the pressure of the household supply an...

Страница 19: ...ne the actual flow rate If the flow rate is too low recheck the selection of the loop pump module model for sufficient capacity If the module selection is correct there is probably trapped air or a re...

Страница 20: ...GPM 2 LOOP PUMP MODULE 0 5 10 15 20 25 30 35 0 5 10 15 20 25 30 35 Flow GPM Head Feet FIGURE 8 PERFORMANCE MODEL GPM 1 LOOP PUMP MODULE FIGURE 7 TEST PLUG CAP PETE S TEST PLUG SELF SEALING DIAL FACE...

Страница 21: ...ter lines to permit isolation of the unit from the plumbing system should future service work require this Globe valves should not be used as shutoff valves because of the excessive pressure drop inhe...

Страница 22: ...flow rate through the pipe The worksheet included in manual 2110 078 should guarantee that the well pump has enough capacity It should also ensure 5 8 9 6 7 12 10 11 that the piping is not undersized...

Страница 23: ...application Will there be enough water And how will the water quality affect the system Water quantity is an important consideration and one which is easily determined The well driller must perform a...

Страница 24: ...he rest of the system by the coil The acid should be pumped from a bucket into the hose bib and returned to the bucket through the other hose bib B Follow the manufacturer s directions for the product...

Страница 25: ...rom the dry well location J The drain line should be installed with a slope of 2 inches per 10 feet of run to provide complete drainage of the line when the ground water heat pump is not operating Thi...

Страница 26: ...rcuit with the electric heater time delay relay and the blower control The electric heater elements will remain energized until the second stage bulb is satisfied at which time the circuit between R a...

Страница 27: ...39 FIGURE 13 DESUPERHEAT COIL LOW PRESSURE SWITCHES REVERSING VALVE EXPANSION VALVE HIGH VOLTAGE IN LOW VOLTAGE IN WATER COIL DISCHARGE SERVICE PORT HIGH PRESSURE SWITCH COMPRESSOR SUCTION SERVICE PO...

Страница 28: ...Manual 2100 317J Page 28 of 39 FIGURE 15...

Страница 29: ...2 9 8 0 5 2 1 9 1 6 2 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 3 8 0 2 1 4 8 2 3 1 4 8 4 4 1 6 8 5 5 1 7 8 7 6 1 8 8 9 7 1 9 8 0 9 1 0 9 2 0 2 1 9 4 1 2 2 9 5 2 2 3 9 7 3 2 4 9 9 4 2...

Страница 30: ...1 2 3 8 9 1 2 8 8 5 2 2 3 9 0 3 2 A 2 0 3 S V S G B D g e d 0 7 e d i S w o L e d i S h g i H 5 3 1 8 1 0 4 7 8 1 5 4 4 9 1 0 5 1 0 2 6 5 7 0 2 1 6 4 1 2 6 6 1 2 2 2 7 7 2 2 7 7 4 3 2 2 8 1 4 2 7 8 7...

Страница 31: ...Defective Air Volume Low Air Filters Dirty Undersized or Restricted Ductwork Auxillary Heat Upstream of Coil Compressor Will Not Run No Power at Contactor Compressor Will Not Run Power at Contactor Co...

Страница 32: ...ressure the pressurized refrigerant and oil mixture could ignite when it escapes and contacts the brazing flame To prevent this occurrence it is important to check both the high and low side with mani...

Страница 33: ...motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check filter Use low pressure drop...

Страница 34: ...st aluminum can with air vents on the back of the can WITH AN ECM 2 3 CONTROL control containing black potting for water protection in black deep drawn steel case with no vents in the bottom of the ca...

Страница 35: ...l kit allows for heat recovery for hot water heating when connected to a home water heater The amount of annual hot water supplied and thus additional energy cost savings will depend on the amount of...

Страница 36: ...nstalled 5 User s Owner s Name Address 6 Unit Location WATER SYSTEM INFORMATION 7 Open Loop System Water Well Closed Loop System A If Open Loop where is water discharged 8 The following questions are...

Страница 37: ...contactor A 19 Amperage at compressor common terminal A 20 Suction line temperature 6 from compressor F 21 Superheat at compressor F 22 Liquid line temperature at metering device F 23 Coil subcooling...

Страница 38: ...Manual 2100 317J Page 38 of 39...

Страница 39: ...Manual 2100 317J Page 39 of 39...

Отзывы: