background image

Manual 2100-317J
Page

24 of 39

FIGURE  11

CLEANING WATER COIL

4.

Scale Formation.

  Of all the water problems, the

formation of scale by ground water is by far the most
common.  Usually this scale is due to the formation of
calcium carbonate by magnesium carbonate or
calcium sulfate may also be present.  Carbon dioxide
gas (CO

2

), the carbonate of calcium and magnesium

carbonate, is very soluble in water.  It will remain
dissolved in the water until some outside factor upsets
the balance.  This outside influence may be a large
change in water temperature or pressure.  When this
happens, enough carbon dioxide gas combines with
dissolved calcium or magnesium in the water and falls
out of solution until a new balance is reached.  The
change in temperature that this heat pump produces is
usually not high enough to cause the dissolved gas to
fall out of solution.  Likewise, if pressure drops are
kept to a reasonable level, no precipitation of carbon
dioxide should occur.

REMEDIES OF WATER PROBLEMS

Water Treatment.

  Water treatment can usually be

economically justified for close loop systems.
However, because of the large amounts of water
involved with a ground water heat pump, water
treatment is generally too expensive.

Acid Cleaning the Water Coil or Heat Pump
Recovery Unit.  

If scaling of the coil is strongly

suspected, the coil can be cleaned up with a solution of
Phosphoric Acid (food grade acid).  Follow the
manufacturer’s directions for mixing, use, etc.  Refer to
the “Cleaning Water Coil”, Figure 11.  The acid
solution can be introduced into the heat pump coil
through the hose bib A.  Be sure the isolation valves are
closed to prevent contamination of the rest of the system
by the coil.  The acid should be pumped from a bucket
into the hose bib and returned to the bucket through the
other hose bib B.  Follow the manufacturer’s directions

for the product used as to how long the solutions to be
circulated, but it is usually circulated for a period of
several hours.

LAKE AND POND INSTALLATIONS

Lakes and ponds can provide a low cost source of water
for heating and cooling with a ground water heat pump.
Direct usage of the water without some filtration is not
recommended as algae and turbid water can foul the
water to freon heat exchanger.  Instead, there have been
very good results using a dry well dug next to the water
line or edge.  Normal procedure in installing a dry well
is to backhoe a 15 to 20 foot hole adjacent to the body of
water (set backhoe as close to the water’s edge as
possible).  Once excavated, a perforated plastic casing
should be installed with gravel backfill placed around
the casing.  The gravel bed should provide adequate
filtration of the water to allow good performance of the
ground water heat pump.

The following is a list of recommendations to follow
when installing this type of system:

A. A lake or pond should be at least 1 acre (40,000 a

square feet) in surface area for each 50,000 BTUs of
ground water heat pump capacity or have 2 times the
cubic feet size of the dwelling that you are trying to
heat (includes basement if heated).

B. The average water depth should be a least 4 feet and

there should be an area where the water depth is at
least 12 to 15 feet deep.

C. If possible, use a submersible pump suspended in the

dry well casing.  Jet pumps and other types of
suction pumps normally consume more electrical
energy than similarly sized submersible pumps.
Pipe the unit the same as a water well system.

HOSE BIB (A)

HOSE BIB (B)

ISOLATION VALVE

ISOLATION VALVE

PUMP

Содержание GSVS242-A

Страница 1: ...ures 45 75 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned Manual 2100 317J Supersedes 2100 317I File Volume I Tab 8 Date 05 16 08 INSTALLATION INSTRUCTIONS WAT...

Страница 2: ...rvice Service Hints 32 Unbrazing System Components 32 Troubleshooting GE ECM Motors 33 34 Accessories Add On DPM26A Pump Module Kit 35 General 35 Installation 35 Ground Source Heat Pump Performance Re...

Страница 3: ...rocedures for Ground Source IGSHPA Heat Pump Systems Soil and Rock Classification for IGSHPA the Design of Ground Coupled Heat Pump Systems Ground Source Installation Standards IGSHPA Closed Loop Geot...

Страница 4: ...1 1 0 6 S V S G 0 2 0 0 6 0 0 0 9 0 0 6 1 0 0 6 1 0 0 9 1 1 Motor will deliver consistent CFM through voltage supply range with no deterioration 197 253V for all 230 208V models 2 Continuous CFM is th...

Страница 5: ...m A t i u c r i C m u m i n i M 0 5 1 0 7 1 0 0 2 0 4 2 0 6 2 0 5 3 e z i S e r i W d l e i F 4 1 4 1 2 1 0 1 0 1 8 r e k a e r B t i u c r i C r o x a M e s u F y a l e D 0 2 5 2 0 3 5 3 0 4 5 5 8 0...

Страница 6: ...H t F 3 0 0 1 1 3 2 4 2 4 1 8 2 3 0 0 1 1 3 2 5 3 8 1 2 2 4 3 4 1 0 3 3 0 8 1 5 1 4 6 4 2 2 7 1 5 6 8 1 9 2 4 8 2 3 7 5 7 7 8 2 2 6 6 7 6 6 2 4 1 6 0 3 2 1 3 5 7 7 4 1 0 1 1 3 3 4 0 0 0 1 8 3 7 2 0 3...

Страница 7: ...86 F FIGURE 1 UNIT DIMENSIONS s t i n U h t d i W h t p e D t h g i e H y l p p u S n r u t e R t c u D e g n a l F h t d i W t h g i e H A B C D E F G H I J K L M N O P Q R S T U V W 2 4 4 2 S V S G...

Страница 8: ...C 4 1 A A V S G 3 H E 1 8 0 2 0 4 2 3 6 5 5 3 1 5 3 0 6 4 7 8 4 3 1 0 1 3 4 5 4 3 4 0 7 0 8 4 y l n O 0 6 8 4 S V S G s e g a k c a P r e t a e H d e l l a t s n I d l e i F l a n o i t p O s n o i t...

Страница 9: ...ire access clearance of two feet minimum Unit may be field converted to left hand return by removing four 4 screws that secure the control panel cover removing two 2 screws that hold the control panel...

Страница 10: ...LE DOORS ARE ON CONTROL PANEL SIDE AND SINGLE DOOR ON OPPOSITE SIDE 1 REMOVE 4 SCREWS SECURING COVER 2 REMOVE 2 SCREWS HOLDING CONTROL BOX TO CORNER PANEL REMOVE 2 SCREWS SECURING PANEL TO BASE 3 PASS...

Страница 11: ...on the pipe and dripping on finished floors or the ceiling under the unit A trap MUST BE installed in the drain line and the trap filled with water prior to start up The use of plugged tees in place o...

Страница 12: ...IGURE 4 PIPING ACCESS TO UNIT WATER IN CONNECTION 3 4 FPT GSVS24 42 MODELS 1 FPT GSVS48 60 MODELS PUMP MODULE CONNECTIONS 1 2 COPPER STUB WATER OUT CONNECTION 3 4 FPT GSVS24 42 MODELS 1 FPT GSVS48 60...

Страница 13: ...the control circuit transformer 2 The maximum total distance of the control circuit wiring Table 6 should be used to determine proper gauge of control circuit wring required Example 1 Control Circuit...

Страница 14: ...airflow in the dehumidify mode By reducing the airflow about 15 the air coil runs colder and thus extracts more moisture This can increase latent capacity from 5 to 13 based on the R H conditions of...

Страница 15: ...Manual 2100 317J Page 15 of 39 FIGURE 5 BLOWER CONTROL BOARD SEE HUMIDITY CONTROL SEE TABLE 8 SEE TABLE 8 SEE TABLE 8 SEE TABLE 8 SEE CFM LIGHT...

Страница 16: ...Manual 2100 317J Page 16 of 39...

Страница 17: ...Manual 2100 317J Page 17 of 39...

Страница 18: ...r system to overcome the pressure of head loss in 1 2 inch or 3 4 inch household plumbing A closed loop earth coupled heat pump system however is separated from the pressure of the household supply an...

Страница 19: ...ne the actual flow rate If the flow rate is too low recheck the selection of the loop pump module model for sufficient capacity If the module selection is correct there is probably trapped air or a re...

Страница 20: ...GPM 2 LOOP PUMP MODULE 0 5 10 15 20 25 30 35 0 5 10 15 20 25 30 35 Flow GPM Head Feet FIGURE 8 PERFORMANCE MODEL GPM 1 LOOP PUMP MODULE FIGURE 7 TEST PLUG CAP PETE S TEST PLUG SELF SEALING DIAL FACE...

Страница 21: ...ter lines to permit isolation of the unit from the plumbing system should future service work require this Globe valves should not be used as shutoff valves because of the excessive pressure drop inhe...

Страница 22: ...flow rate through the pipe The worksheet included in manual 2110 078 should guarantee that the well pump has enough capacity It should also ensure 5 8 9 6 7 12 10 11 that the piping is not undersized...

Страница 23: ...application Will there be enough water And how will the water quality affect the system Water quantity is an important consideration and one which is easily determined The well driller must perform a...

Страница 24: ...he rest of the system by the coil The acid should be pumped from a bucket into the hose bib and returned to the bucket through the other hose bib B Follow the manufacturer s directions for the product...

Страница 25: ...rom the dry well location J The drain line should be installed with a slope of 2 inches per 10 feet of run to provide complete drainage of the line when the ground water heat pump is not operating Thi...

Страница 26: ...rcuit with the electric heater time delay relay and the blower control The electric heater elements will remain energized until the second stage bulb is satisfied at which time the circuit between R a...

Страница 27: ...39 FIGURE 13 DESUPERHEAT COIL LOW PRESSURE SWITCHES REVERSING VALVE EXPANSION VALVE HIGH VOLTAGE IN LOW VOLTAGE IN WATER COIL DISCHARGE SERVICE PORT HIGH PRESSURE SWITCH COMPRESSOR SUCTION SERVICE PO...

Страница 28: ...Manual 2100 317J Page 28 of 39 FIGURE 15...

Страница 29: ...2 9 8 0 5 2 1 9 1 6 2 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 3 8 0 2 1 4 8 2 3 1 4 8 4 4 1 6 8 5 5 1 7 8 7 6 1 8 8 9 7 1 9 8 0 9 1 0 9 2 0 2 1 9 4 1 2 2 9 5 2 2 3 9 7 3 2 4 9 9 4 2...

Страница 30: ...1 2 3 8 9 1 2 8 8 5 2 2 3 9 0 3 2 A 2 0 3 S V S G B D g e d 0 7 e d i S w o L e d i S h g i H 5 3 1 8 1 0 4 7 8 1 5 4 4 9 1 0 5 1 0 2 6 5 7 0 2 1 6 4 1 2 6 6 1 2 2 2 7 7 2 2 7 7 4 3 2 2 8 1 4 2 7 8 7...

Страница 31: ...Defective Air Volume Low Air Filters Dirty Undersized or Restricted Ductwork Auxillary Heat Upstream of Coil Compressor Will Not Run No Power at Contactor Compressor Will Not Run Power at Contactor Co...

Страница 32: ...ressure the pressurized refrigerant and oil mixture could ignite when it escapes and contacts the brazing flame To prevent this occurrence it is important to check both the high and low side with mani...

Страница 33: ...motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check filter Use low pressure drop...

Страница 34: ...st aluminum can with air vents on the back of the can WITH AN ECM 2 3 CONTROL control containing black potting for water protection in black deep drawn steel case with no vents in the bottom of the ca...

Страница 35: ...l kit allows for heat recovery for hot water heating when connected to a home water heater The amount of annual hot water supplied and thus additional energy cost savings will depend on the amount of...

Страница 36: ...nstalled 5 User s Owner s Name Address 6 Unit Location WATER SYSTEM INFORMATION 7 Open Loop System Water Well Closed Loop System A If Open Loop where is water discharged 8 The following questions are...

Страница 37: ...contactor A 19 Amperage at compressor common terminal A 20 Suction line temperature 6 from compressor F 21 Superheat at compressor F 22 Liquid line temperature at metering device F 23 Coil subcooling...

Страница 38: ...Manual 2100 317J Page 38 of 39...

Страница 39: ...Manual 2100 317J Page 39 of 39...

Отзывы: