background image

Manual 2100-317J
Page

34 of 39

Replacing ECM Control Module

To replace the control module for the GE variable-speed indoor blower motor
you need to take the following steps:

1. You MUST have the correct replacement module.  The controls are

factory programmed for specific operating modes.  Even though they look
alike, different modules may have completely different functionality.

USING THE WRONG CONTROL MODULE VOIDS ALL PRODUCT
WARRANTIES AND MAY PRODUCE UNEXPECTED RESULTS.

2. Begin by removing AC power from the furnace or air handler being

serviced.  

DO NOT WORK ON THE MOTOR WITH AC POWER

APPLIED.  

To avoid electric shock from the motor’s capacitors, disconnect

power and wait at least 5 minutes before opening motor.

3. It is usually not necessary to remove the motor from the blower

assembly.  However, it is recommended that the whole blower assembly,
with the motor, be removed from the furnace/air handler.  (Follow the
manufacturer’s procedures).  Unplug the two cable connectors to the motor.
There are latches on each connector.  

DO NOT PULL ON THE WIRES.

The plugs remove easily when properly released.

4. Locate the two standard ¼" hex head bolts at the rear of the control

housing (at the back end of the control opposite the shaft end).  

Refer to

Figure 17.  

Remove these two bolts from the motor and control

assembly while holding the motor in a way that will prevent the motor
or control from falling when the bolts are removed.  If an ECM2.0
control is being replaced (recognized by an aluminum casting rather
that a deep-drawn black steel can housing the electronics), remove only
the hex-head bolts.  

DO NOT REMOVE THE TORX-HEAD SCREWS.

5. The control module is now free of mechanical attachment to the

motor endshield but is still connected by a plug and three wires inside
the control.  Carefully rotate the control to gain access to the plug at the
control end of the wires.  With thumb and forefinger, reach the latch
holding the plug to the control and release it by squeezing the latch tab
and the opposite side of the connector plug and gently pulling the plug
out of the connector socket in the control.  

DO NOT PULL ON THE

WIRES.  GRIP THE PLUG ONLY.

6. The control module is now completely detached from the motor.

Verify with a standard ohmmeter that the resistance from each motor
lead (in the motor plug just removed) to the motor shell is >100K ohms.

Refer to Figure 18.  

(Measure to unpainted motor end plate.)  If any

motor lead fails this test, do not proceed to install the control module.

THE MOTOR IS DEFECTIVE AND MUST BE REPLACED.

Installing the new control module will cause it to fail also.

7. Verify that the replacement control is correct for your application.

Refer to the manufacturer's authorized replacement list.  

USING THE

WRONG CONTROL WILL RESULT IN IMPROPER OR NO
BLOWER OPERATION.

  Orient the control module so that the 3-

wire motor plug can be inserted into the socket in the control.
Carefully insert the plug and press it into the socket until it latches.  

A

SLIGHT CLICK WILL BE HEARD WHEN PROPERLY
INSERTED.

  Finish installing the replacement control per one of the three

following paragraphs, 8a, 8b or 8c.

8a. 

IF REPLACING AN ECM 2.0 CONTROL

 (control in cast

aluminum can with air vents on the back of the can) 

WITH AN ECM

2.3 CONTROL

 (control containing black potting for water protection

in black deep-drawn steel case with no vents in the bottom of the can),
locate the two through-bolts and plastic tab that are packed with the
replacement control.  Insert the plastic tab into the slot at the perimeter
of the open end of the can so that the pin is located on the inside of the
perimeter of the can.  Rotate the can so that the tab inserts into the tab
locater hole in the endshield of the motor.  Using the two through-bolts
provided with the replacement control, reattach the can to the motor.

THE TWO THROUGH-BOLTS PROVIDED WITH THE
REPLACEMENT ECM 2.3 CONTROL ARE SHORTER THAN
THE BOLTS ORIGINALLY REMOVED FROM THE ECM 2.0
CONTROL AND MUST BE USED IF SECURE ATTACHMENT
OF THE CONTROL TO THE MOTOR IS TO BE ACHIEVED.

DO NOT OVERTIGHTEN THE BOLTS.

8b. 

IF REPLACING AN ECM 2.3 CONTROL

 

WITH AN ECM 2.3

CONTROL

, the plastic tab and shorter through-bolts are not needed.

The control can be oriented in two positions 180° apart.  

MAKE SURE

THE ORIENTATION YOU SELECT FOR REPLACING THE
CONTROL ASSURES THE CONTROL'S CABLE CONNECTORS
WILL BE LOCATED DOWNWARD IN THE APPLICATION SO
THAT WATER CANNOT RUN DOWN THE CABLES AND INTO
THE CONTROL.

  Simply orient the new control to the motor's

endshield, insert bolts, and tighten.  

DO NOT OVERTIGHTEN THE

BOLTS.

8c. 

IF REPLACING AN ECM 2.0 CONTROL WITH AN ECM 2.0

CONTROL 

(It is recommended that ECM 2.3 controls be used for all

replacements), 

the new control must be attached to the motor using

through bolts identical to those removed with the original control.  

DO

NOT OVERTIGHTEN THE BOLTS.

9. Reinstall the blower/motor assembly into the HVAC equipment.

Follow the manufacturer's suggested procedures.

10. Plug the 16-pin control plug into the motor.  The plug is keyed.

Make sure the connector is properly seated and latched.

11. Plug the 5-pin power connector into the motor.  Even though the

plug is keyed, 

OBSERVE THE PROPER ORIENTATION.  DO NOT

FORCE THE CONNECTOR.

  It plugs in very easily when properly

oriented.  

REVERSING THIS PLUG WILL CAUSE IMMEDIATE

FAILURE OF THE CONTROL MODULE.

12. Final installation check.  Make sure the motor is installed as follows:

a. Unit is as far INTO the blower housing as possible.
b.Belly bands are not on the control module or covering vent holes.
c. Motor connectors should be oriented between the 4 o’clock and 8

o’clock positions when the blower is positioned in its final
location and orientation.

d.Add a drip loop to the cables so that water cannot enter the motor

by draining down the cables.  

Refer to Figure 19.

The installation is now complete.  Reapply the AC power to the HVAC
equipment and verify that the new motor control module is working
properly.  Follow the manufacturer's procedures for disposition of the old
control module.

TROUBLESHOOTING  GE  ECM

 MOTORS CONT’D.

Motor

Motor OK when

R > 100k ohm

ECM 2.0

Only remove

Hex Head Bolts

Connector Orientation

Between 4 and 8 o'clock

Drip Loop

Back of

Control

Figure 5

Winding Test

Figure 4

Note:              
Use the shorter 
bolts and 
alignment pin 
supplied when 
replacing an 
ECM 2.0 
control.

Figure 3

ECM 
2.3/2.5

Power Connector
(5-pin)

Control Connector
(16-pin)

Hex-head Screws

Motor Connector
(3-pin)

Motor Connector
(3-pin)

Control Disassembly

Drip Loop

Push until

Latch Seats
Over Ramp

From Motor

Circuit

Board

17

18

19

Содержание GSVS242-A

Страница 1: ...ures 45 75 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned Manual 2100 317J Supersedes 2100 317I File Volume I Tab 8 Date 05 16 08 INSTALLATION INSTRUCTIONS WAT...

Страница 2: ...rvice Service Hints 32 Unbrazing System Components 32 Troubleshooting GE ECM Motors 33 34 Accessories Add On DPM26A Pump Module Kit 35 General 35 Installation 35 Ground Source Heat Pump Performance Re...

Страница 3: ...rocedures for Ground Source IGSHPA Heat Pump Systems Soil and Rock Classification for IGSHPA the Design of Ground Coupled Heat Pump Systems Ground Source Installation Standards IGSHPA Closed Loop Geot...

Страница 4: ...1 1 0 6 S V S G 0 2 0 0 6 0 0 0 9 0 0 6 1 0 0 6 1 0 0 9 1 1 Motor will deliver consistent CFM through voltage supply range with no deterioration 197 253V for all 230 208V models 2 Continuous CFM is th...

Страница 5: ...m A t i u c r i C m u m i n i M 0 5 1 0 7 1 0 0 2 0 4 2 0 6 2 0 5 3 e z i S e r i W d l e i F 4 1 4 1 2 1 0 1 0 1 8 r e k a e r B t i u c r i C r o x a M e s u F y a l e D 0 2 5 2 0 3 5 3 0 4 5 5 8 0...

Страница 6: ...H t F 3 0 0 1 1 3 2 4 2 4 1 8 2 3 0 0 1 1 3 2 5 3 8 1 2 2 4 3 4 1 0 3 3 0 8 1 5 1 4 6 4 2 2 7 1 5 6 8 1 9 2 4 8 2 3 7 5 7 7 8 2 2 6 6 7 6 6 2 4 1 6 0 3 2 1 3 5 7 7 4 1 0 1 1 3 3 4 0 0 0 1 8 3 7 2 0 3...

Страница 7: ...86 F FIGURE 1 UNIT DIMENSIONS s t i n U h t d i W h t p e D t h g i e H y l p p u S n r u t e R t c u D e g n a l F h t d i W t h g i e H A B C D E F G H I J K L M N O P Q R S T U V W 2 4 4 2 S V S G...

Страница 8: ...C 4 1 A A V S G 3 H E 1 8 0 2 0 4 2 3 6 5 5 3 1 5 3 0 6 4 7 8 4 3 1 0 1 3 4 5 4 3 4 0 7 0 8 4 y l n O 0 6 8 4 S V S G s e g a k c a P r e t a e H d e l l a t s n I d l e i F l a n o i t p O s n o i t...

Страница 9: ...ire access clearance of two feet minimum Unit may be field converted to left hand return by removing four 4 screws that secure the control panel cover removing two 2 screws that hold the control panel...

Страница 10: ...LE DOORS ARE ON CONTROL PANEL SIDE AND SINGLE DOOR ON OPPOSITE SIDE 1 REMOVE 4 SCREWS SECURING COVER 2 REMOVE 2 SCREWS HOLDING CONTROL BOX TO CORNER PANEL REMOVE 2 SCREWS SECURING PANEL TO BASE 3 PASS...

Страница 11: ...on the pipe and dripping on finished floors or the ceiling under the unit A trap MUST BE installed in the drain line and the trap filled with water prior to start up The use of plugged tees in place o...

Страница 12: ...IGURE 4 PIPING ACCESS TO UNIT WATER IN CONNECTION 3 4 FPT GSVS24 42 MODELS 1 FPT GSVS48 60 MODELS PUMP MODULE CONNECTIONS 1 2 COPPER STUB WATER OUT CONNECTION 3 4 FPT GSVS24 42 MODELS 1 FPT GSVS48 60...

Страница 13: ...the control circuit transformer 2 The maximum total distance of the control circuit wiring Table 6 should be used to determine proper gauge of control circuit wring required Example 1 Control Circuit...

Страница 14: ...airflow in the dehumidify mode By reducing the airflow about 15 the air coil runs colder and thus extracts more moisture This can increase latent capacity from 5 to 13 based on the R H conditions of...

Страница 15: ...Manual 2100 317J Page 15 of 39 FIGURE 5 BLOWER CONTROL BOARD SEE HUMIDITY CONTROL SEE TABLE 8 SEE TABLE 8 SEE TABLE 8 SEE TABLE 8 SEE CFM LIGHT...

Страница 16: ...Manual 2100 317J Page 16 of 39...

Страница 17: ...Manual 2100 317J Page 17 of 39...

Страница 18: ...r system to overcome the pressure of head loss in 1 2 inch or 3 4 inch household plumbing A closed loop earth coupled heat pump system however is separated from the pressure of the household supply an...

Страница 19: ...ne the actual flow rate If the flow rate is too low recheck the selection of the loop pump module model for sufficient capacity If the module selection is correct there is probably trapped air or a re...

Страница 20: ...GPM 2 LOOP PUMP MODULE 0 5 10 15 20 25 30 35 0 5 10 15 20 25 30 35 Flow GPM Head Feet FIGURE 8 PERFORMANCE MODEL GPM 1 LOOP PUMP MODULE FIGURE 7 TEST PLUG CAP PETE S TEST PLUG SELF SEALING DIAL FACE...

Страница 21: ...ter lines to permit isolation of the unit from the plumbing system should future service work require this Globe valves should not be used as shutoff valves because of the excessive pressure drop inhe...

Страница 22: ...flow rate through the pipe The worksheet included in manual 2110 078 should guarantee that the well pump has enough capacity It should also ensure 5 8 9 6 7 12 10 11 that the piping is not undersized...

Страница 23: ...application Will there be enough water And how will the water quality affect the system Water quantity is an important consideration and one which is easily determined The well driller must perform a...

Страница 24: ...he rest of the system by the coil The acid should be pumped from a bucket into the hose bib and returned to the bucket through the other hose bib B Follow the manufacturer s directions for the product...

Страница 25: ...rom the dry well location J The drain line should be installed with a slope of 2 inches per 10 feet of run to provide complete drainage of the line when the ground water heat pump is not operating Thi...

Страница 26: ...rcuit with the electric heater time delay relay and the blower control The electric heater elements will remain energized until the second stage bulb is satisfied at which time the circuit between R a...

Страница 27: ...39 FIGURE 13 DESUPERHEAT COIL LOW PRESSURE SWITCHES REVERSING VALVE EXPANSION VALVE HIGH VOLTAGE IN LOW VOLTAGE IN WATER COIL DISCHARGE SERVICE PORT HIGH PRESSURE SWITCH COMPRESSOR SUCTION SERVICE PO...

Страница 28: ...Manual 2100 317J Page 28 of 39 FIGURE 15...

Страница 29: ...2 9 8 0 5 2 1 9 1 6 2 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 3 8 0 2 1 4 8 2 3 1 4 8 4 4 1 6 8 5 5 1 7 8 7 6 1 8 8 9 7 1 9 8 0 9 1 0 9 2 0 2 1 9 4 1 2 2 9 5 2 2 3 9 7 3 2 4 9 9 4 2...

Страница 30: ...1 2 3 8 9 1 2 8 8 5 2 2 3 9 0 3 2 A 2 0 3 S V S G B D g e d 0 7 e d i S w o L e d i S h g i H 5 3 1 8 1 0 4 7 8 1 5 4 4 9 1 0 5 1 0 2 6 5 7 0 2 1 6 4 1 2 6 6 1 2 2 2 7 7 2 2 7 7 4 3 2 2 8 1 4 2 7 8 7...

Страница 31: ...Defective Air Volume Low Air Filters Dirty Undersized or Restricted Ductwork Auxillary Heat Upstream of Coil Compressor Will Not Run No Power at Contactor Compressor Will Not Run Power at Contactor Co...

Страница 32: ...ressure the pressurized refrigerant and oil mixture could ignite when it escapes and contacts the brazing flame To prevent this occurrence it is important to check both the high and low side with mani...

Страница 33: ...motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check filter Use low pressure drop...

Страница 34: ...st aluminum can with air vents on the back of the can WITH AN ECM 2 3 CONTROL control containing black potting for water protection in black deep drawn steel case with no vents in the bottom of the ca...

Страница 35: ...l kit allows for heat recovery for hot water heating when connected to a home water heater The amount of annual hot water supplied and thus additional energy cost savings will depend on the amount of...

Страница 36: ...nstalled 5 User s Owner s Name Address 6 Unit Location WATER SYSTEM INFORMATION 7 Open Loop System Water Well Closed Loop System A If Open Loop where is water discharged 8 The following questions are...

Страница 37: ...contactor A 19 Amperage at compressor common terminal A 20 Suction line temperature 6 from compressor F 21 Superheat at compressor F 22 Liquid line temperature at metering device F 23 Coil subcooling...

Страница 38: ...Manual 2100 317J Page 38 of 39...

Страница 39: ...Manual 2100 317J Page 39 of 39...

Отзывы: