Manual
2100-317J
Page
23 of 39
SYSTEM START UP PROCEDURE FOR
OPEN LOOP APPLICATIONS
1. Be sure main power to the unit is OFF at disconnect.
2. Set thermostat system switch to OFF, fan switch to
AUTO.
3. Move main power disconnect to ON. Except as
required for safety while servicing –
DO NOT OPEN
THE UNIT DISCONNECT SWITCH.
4. Check system airflow for obstructions.
A. Move thermostat fan switch to ON. Blower runs.
B. Be sure all registers and grilles are open.
C. Move thermostat fan switch to AUTO. Blower
should stop.
5. Fully open the manual inlet and outlet valves.
6. Check water flow.
A. Connect a water flow meter to the drain cock
between the constant flow valve and the
solenoid valve. Run a hose from the flow meter
to a drain or sink. Open the drain cock.
B. Check the water flow rate through constant
flow valve to be sure it is the same as the unit
is rated for.
(Example: 4 GPM for a GSVS302-A.)
C. When water flow is okay, close drain cock and
remove the water flow meter. The unit is now
ready to start.
7. Start the unit in cooling mode. By moving the
thermostat switch to cool, fan should be set for
AUTO.
A. Check to see the solenoid valve opened.
8. Check the system refrigerant pressures against the
cooling refrigerant pressure table in the installation
manual for rated water flow and entering water
temperatures. If the refrigerant pressures do not
match, check for airflow problem that refrigeration
system problem.
9. Switch the unit to the heat mode. By moving the
thermostat switch to heat, fan should be set for
AUTO.
A. Check to see the solenoid valve opened again.
10. Check the refrigerant system pressures against the
heating refrigerant pressure table in installation
manual. Once again, if they do not match, check for
airflow problems and then refrigeration system
problems.
NOTE:
If a charge problem is determined (high or low):
A. Check for possible refrigerant loss.
B. Discharge all remaining refrigerant from unit.
C. Evacuate unit down to 29 inches of vacuum.
D. Recharge the unit with refrigerant by weight.
This is the only way to insure proper charge.
WATER CORROSION
Two concerns will immediately come to light when
considering a water source heat pump, whether for
ground water or for a closed loop application: Will
there be enough water? And, how will the water quality
affect the system?
Water quantity is an important consideration and one
which is easily determined. The well driller must
perform a pump down test on the well according to
methods described by the Nation Well Water
Association. This test, if performed correctly, will
provide information on the rate of low and on the
capacity of the well. It is important to consider the
overall capacity of the well when thinking about a water
source heat pump because the heat pump may be
required to run for extended periods of time.
The second concern, about water quality, is equally
important. Generally speaking, if the water is not
offensive for drinking purposes, it should pose no
problem for the heat pump. The well driller or local
water softening company can perform tests which will
determine the chemical properties of the well water.
Water quality problems will show up in the heat pump
in one of more of the following ways:
1. Decrease in water flow through the unit.
2. Decreased heat transfer of the water coil (entering to
leaving water temperature difference is less).
There are four main water quality problems associated
with ground water. These are:
1.
Biological Growth.
This is the growth of
microscopic organisms in the water and will show
up as a slimy deposit throughout the water system.
Shock treatment of the well is usually required and
this is best left up to the well driller. The treatment
consists of injecting chlorine into the well casing
and flushing the system until all growth is removed.
2.
Suspended Particles in the Water.
Filtering will
usually remove most suspended particles (fine sand,
small gravel) from the water. The problem with
suspended particles in the water is that it will erode
metal parts, pumps, heat transfer coils, etc. So long
as the filter is cleaned and periodically maintained,
suspended particles should pose no serious problem.
Consult with your well driller.
3.
Corrosion of Metal.
Corrosion of metal parts
results from either highly corrosive water (acid
water, generally not the case with ground water) of
galvanic reaction between dissimilar metals in the
presence of water. By using plastic plumbing or
dielectric unions, galvanic reaction is eliminated.
The use of corrosion resistant materials such as the
Cupronickel coil) through the water system will
reduce corrosion problems significantly.
Содержание GSVS242-A
Страница 16: ...Manual 2100 317J Page 16 of 39...
Страница 17: ...Manual 2100 317J Page 17 of 39...
Страница 28: ...Manual 2100 317J Page 28 of 39 FIGURE 15...
Страница 38: ...Manual 2100 317J Page 38 of 39...
Страница 39: ...Manual 2100 317J Page 39 of 39...