CAUTION:

Disconnect power from unit before removing or replacing
connectors, or servicing motor.  To avoid electric shock from
the motor’s capacitors, disconnect power and wait at least 5
minutes before opening motor.

Symptom

Cause/Procedure

Motor rocks slightly

• 

This is normal start-up for ECM

when starting

Motor won’t start

• 

Check blower turns by hand

• No movement

• Check power at motor
• Check low voltage (24 Vac R to C) at motor
• Check low voltage connections
  (G, Y, W, R, C) at motor
• Check for unseated pins in connectors on
   motor harness
• Test with a temporary jumper between R - G
• Check motor for tight shaft
• Perform motor/control replacement check
• 

Perform Moisture Check

• Motor rocks,

• Check for loose or compliant motor mount

  but won’t start

• Make sure blower wheel is tight on shaft
• Perform motor/control replacement check

Motor oscillates up

• It is normal for motor to oscillate with no load

& down while being

  on shaft

tested off of blower

Motor starts, but
runs erratically

• Varies up and down

• Check line voltage for variation or “sag”

  or intermittent

• Check low voltage connections
  (G, Y, W, R, C) at motor, unseated pins in
  motor harness connectors
• Check “Bk” for erratic CFM command (in
   variable-speed applications)
• Check out system controls, Thermostat
• 

Perform Moisture Check

• “Hunts” or “puffs” at

• Does removing panel or filter reduce

  high CFM (speed)

  “puffing”?
 - Reduce restriction
 - Reduce max airflow

• Stays at low CFM

• Check low voltage (Thermostat) wires and

  despite system call

  connections

  for cool or heat CFM

• Verify fan is not in delay mode; wait until
   delay complete
• “R” missing/not connected at motor
• Perform motor/control replacement check

• Stays at high CFM

• “R” missing/not connected at motor
• Is fan in delay mode? - wait until delay time
  complete
• Perform motor/control replacement check

• Blower won’t shut off

• Current leakage from controls into G, Y or W?
  Check for Triac switched thermostat or solid-
  state relay

Excessive noise

• Determine if it’s air noise, cabinet, duct or
  motor noise; interview customer, if necessary

• Air noise

• High static creating high blower speed?
 - Is airflow set properly?
 - Does removing filter cause blower to slow
   down?  Check filter
 - Use low-pressure drop filter
 - Check/correct duct restrictions

Symptom

Cause/Procedure

• Noisy blower or cabinet

• 

Check for loose blower housing, panels, etc.

• High static creating high blower speed?

  - Check for air whistling through seams in
     ducts, cabinets or panels
  - Check for cabinet/duct deformation

• “Hunts” or “puffs” at

• 

Does removing panel or filter reduce

   high CFM (speed)

   “puffing”?
  - Reduce restriction
  - Reduce max. airflow

Evidence of Moisture

• Motor failure or

• Replace motor and 

Perform Moisture Check

  malfunction has occurred

  

and moisture is present

• Evidence of moisture

• 

Perform Moisture Check

  present inside air mover

Do

Don’t

• Check out motor, controls,

• 

Automatically assume the motor is bad.

  wiring and connections
  thoroughly before replacing
  motor
• Orient connectors down so • Locate connectors above 7 and 4 o’clock
  water can’t get in

   positions

 - Install “drip loops”
• Use authorized motor and

• Replace one motor or control model # with

  model #’s for replacement    another (unless an authorized replacement)
• Keep static pressure to a

• Use high pressure drop filters some have 

½"

  

minimum:

   H20 drop!

 - Recommend high

• Use restricted returns

   efficiency, low static filters
 - Recommend keeping filters
   clean.
 - Design ductwork for min.
   static, max. comfort
 - Look for and recommend
   ductwork improvement,
   where necessary

• Size the equipment wisely

• Oversize system, then compensate with low

    airflow

• Check orientation before

• Plug in power connector backwards

  inserting motor connectors

• Force plugs

Moisture Check

• Connectors are oriented “down” (or as recommended by equipment
  manufacturer)
• Arrange harness with “drip loop” under motor
• Is condensate drain plugged?
• Check for low airflow (too much latent capacity)
• Check for undercharged condition
• Check and plug leaks in return ducts, cabinet

Comfort Check

• Check proper airflow settings
• Low static pressure for lowest noise
• Set low continuous-fan CFM
• Use humidistat and 2-speed cooling units
• Use zoning controls designed for ECM that regulate CFM
• Thermostat in bad location?

TROUBLESHOOTING  GE  ECM

 MOTORS

Содержание GSVS242-A

Страница 1: ...ures 45 75 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned Manual 2100 317J Supersedes 2100 317I File Volume I Tab 8 Date 05 16 08 INSTALLATION INSTRUCTIONS WAT...

Страница 2: ...rvice Service Hints 32 Unbrazing System Components 32 Troubleshooting GE ECM Motors 33 34 Accessories Add On DPM26A Pump Module Kit 35 General 35 Installation 35 Ground Source Heat Pump Performance Re...

Страница 3: ...rocedures for Ground Source IGSHPA Heat Pump Systems Soil and Rock Classification for IGSHPA the Design of Ground Coupled Heat Pump Systems Ground Source Installation Standards IGSHPA Closed Loop Geot...

Страница 4: ...1 1 0 6 S V S G 0 2 0 0 6 0 0 0 9 0 0 6 1 0 0 6 1 0 0 9 1 1 Motor will deliver consistent CFM through voltage supply range with no deterioration 197 253V for all 230 208V models 2 Continuous CFM is th...

Страница 5: ...m A t i u c r i C m u m i n i M 0 5 1 0 7 1 0 0 2 0 4 2 0 6 2 0 5 3 e z i S e r i W d l e i F 4 1 4 1 2 1 0 1 0 1 8 r e k a e r B t i u c r i C r o x a M e s u F y a l e D 0 2 5 2 0 3 5 3 0 4 5 5 8 0...

Страница 6: ...H t F 3 0 0 1 1 3 2 4 2 4 1 8 2 3 0 0 1 1 3 2 5 3 8 1 2 2 4 3 4 1 0 3 3 0 8 1 5 1 4 6 4 2 2 7 1 5 6 8 1 9 2 4 8 2 3 7 5 7 7 8 2 2 6 6 7 6 6 2 4 1 6 0 3 2 1 3 5 7 7 4 1 0 1 1 3 3 4 0 0 0 1 8 3 7 2 0 3...

Страница 7: ...86 F FIGURE 1 UNIT DIMENSIONS s t i n U h t d i W h t p e D t h g i e H y l p p u S n r u t e R t c u D e g n a l F h t d i W t h g i e H A B C D E F G H I J K L M N O P Q R S T U V W 2 4 4 2 S V S G...

Страница 8: ...C 4 1 A A V S G 3 H E 1 8 0 2 0 4 2 3 6 5 5 3 1 5 3 0 6 4 7 8 4 3 1 0 1 3 4 5 4 3 4 0 7 0 8 4 y l n O 0 6 8 4 S V S G s e g a k c a P r e t a e H d e l l a t s n I d l e i F l a n o i t p O s n o i t...

Страница 9: ...ire access clearance of two feet minimum Unit may be field converted to left hand return by removing four 4 screws that secure the control panel cover removing two 2 screws that hold the control panel...

Страница 10: ...LE DOORS ARE ON CONTROL PANEL SIDE AND SINGLE DOOR ON OPPOSITE SIDE 1 REMOVE 4 SCREWS SECURING COVER 2 REMOVE 2 SCREWS HOLDING CONTROL BOX TO CORNER PANEL REMOVE 2 SCREWS SECURING PANEL TO BASE 3 PASS...

Страница 11: ...on the pipe and dripping on finished floors or the ceiling under the unit A trap MUST BE installed in the drain line and the trap filled with water prior to start up The use of plugged tees in place o...

Страница 12: ...IGURE 4 PIPING ACCESS TO UNIT WATER IN CONNECTION 3 4 FPT GSVS24 42 MODELS 1 FPT GSVS48 60 MODELS PUMP MODULE CONNECTIONS 1 2 COPPER STUB WATER OUT CONNECTION 3 4 FPT GSVS24 42 MODELS 1 FPT GSVS48 60...

Страница 13: ...the control circuit transformer 2 The maximum total distance of the control circuit wiring Table 6 should be used to determine proper gauge of control circuit wring required Example 1 Control Circuit...

Страница 14: ...airflow in the dehumidify mode By reducing the airflow about 15 the air coil runs colder and thus extracts more moisture This can increase latent capacity from 5 to 13 based on the R H conditions of...

Страница 15: ...Manual 2100 317J Page 15 of 39 FIGURE 5 BLOWER CONTROL BOARD SEE HUMIDITY CONTROL SEE TABLE 8 SEE TABLE 8 SEE TABLE 8 SEE TABLE 8 SEE CFM LIGHT...

Страница 16: ...Manual 2100 317J Page 16 of 39...

Страница 17: ...Manual 2100 317J Page 17 of 39...

Страница 18: ...r system to overcome the pressure of head loss in 1 2 inch or 3 4 inch household plumbing A closed loop earth coupled heat pump system however is separated from the pressure of the household supply an...

Страница 19: ...ne the actual flow rate If the flow rate is too low recheck the selection of the loop pump module model for sufficient capacity If the module selection is correct there is probably trapped air or a re...

Страница 20: ...GPM 2 LOOP PUMP MODULE 0 5 10 15 20 25 30 35 0 5 10 15 20 25 30 35 Flow GPM Head Feet FIGURE 8 PERFORMANCE MODEL GPM 1 LOOP PUMP MODULE FIGURE 7 TEST PLUG CAP PETE S TEST PLUG SELF SEALING DIAL FACE...

Страница 21: ...ter lines to permit isolation of the unit from the plumbing system should future service work require this Globe valves should not be used as shutoff valves because of the excessive pressure drop inhe...

Страница 22: ...flow rate through the pipe The worksheet included in manual 2110 078 should guarantee that the well pump has enough capacity It should also ensure 5 8 9 6 7 12 10 11 that the piping is not undersized...

Страница 23: ...application Will there be enough water And how will the water quality affect the system Water quantity is an important consideration and one which is easily determined The well driller must perform a...

Страница 24: ...he rest of the system by the coil The acid should be pumped from a bucket into the hose bib and returned to the bucket through the other hose bib B Follow the manufacturer s directions for the product...

Страница 25: ...rom the dry well location J The drain line should be installed with a slope of 2 inches per 10 feet of run to provide complete drainage of the line when the ground water heat pump is not operating Thi...

Страница 26: ...rcuit with the electric heater time delay relay and the blower control The electric heater elements will remain energized until the second stage bulb is satisfied at which time the circuit between R a...

Страница 27: ...39 FIGURE 13 DESUPERHEAT COIL LOW PRESSURE SWITCHES REVERSING VALVE EXPANSION VALVE HIGH VOLTAGE IN LOW VOLTAGE IN WATER COIL DISCHARGE SERVICE PORT HIGH PRESSURE SWITCH COMPRESSOR SUCTION SERVICE PO...

Страница 28: ...Manual 2100 317J Page 28 of 39 FIGURE 15...

Страница 29: ...2 9 8 0 5 2 1 9 1 6 2 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 3 8 0 2 1 4 8 2 3 1 4 8 4 4 1 6 8 5 5 1 7 8 7 6 1 8 8 9 7 1 9 8 0 9 1 0 9 2 0 2 1 9 4 1 2 2 9 5 2 2 3 9 7 3 2 4 9 9 4 2...

Страница 30: ...1 2 3 8 9 1 2 8 8 5 2 2 3 9 0 3 2 A 2 0 3 S V S G B D g e d 0 7 e d i S w o L e d i S h g i H 5 3 1 8 1 0 4 7 8 1 5 4 4 9 1 0 5 1 0 2 6 5 7 0 2 1 6 4 1 2 6 6 1 2 2 2 7 7 2 2 7 7 4 3 2 2 8 1 4 2 7 8 7...

Страница 31: ...Defective Air Volume Low Air Filters Dirty Undersized or Restricted Ductwork Auxillary Heat Upstream of Coil Compressor Will Not Run No Power at Contactor Compressor Will Not Run Power at Contactor Co...

Страница 32: ...ressure the pressurized refrigerant and oil mixture could ignite when it escapes and contacts the brazing flame To prevent this occurrence it is important to check both the high and low side with mani...

Страница 33: ...motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check filter Use low pressure drop...

Страница 34: ...st aluminum can with air vents on the back of the can WITH AN ECM 2 3 CONTROL control containing black potting for water protection in black deep drawn steel case with no vents in the bottom of the ca...

Страница 35: ...l kit allows for heat recovery for hot water heating when connected to a home water heater The amount of annual hot water supplied and thus additional energy cost savings will depend on the amount of...

Страница 36: ...nstalled 5 User s Owner s Name Address 6 Unit Location WATER SYSTEM INFORMATION 7 Open Loop System Water Well Closed Loop System A If Open Loop where is water discharged 8 The following questions are...

Страница 37: ...contactor A 19 Amperage at compressor common terminal A 20 Suction line temperature 6 from compressor F 21 Superheat at compressor F 22 Liquid line temperature at metering device F 23 Coil subcooling...

Страница 38: ...Manual 2100 317J Page 38 of 39...

Страница 39: ...Manual 2100 317J Page 39 of 39...

Отзывы: