Manual 2100-694B
Page
20 of 62
TABLE 6B
HR36BP* Blower Speeds
Mode
Speed
Percentage
Controller
Output Volts
CFM
High Sensible
Full Load Cooling
94.0
9.4 v
1500
High Sensible
Part Load Cooling
54.0
5.4 v
1100
Standard Full
Load Cooling
63.0
6.3 v
1200
Standard Part
Load Cooling
43.0
4.3 v
950
Economizer Standard
Economizer High S/T
90.0
63.0
9.0 v
6.3 v
1450
1200
Heating
63.0
6.3 v
1200
Dehumidification
Mode
19.0
1.9 v
470
TABLE 6C
HR58BP* Blower Speeds
TABLE 7
Rated Airflow
Nominal Rated CFM
Nominal Rated ESP
High
Low
HR35BP*
1100
900
0.00
HR36BP*
1200
950
0.00
HR58BP*
1800
1400
0.10
Mode
Speed
Percentage
Controller
Output Volts
CFM
High Sensible Full
Load Cooling
75.0
7.5 v
2180
High Sensible Part
Load Cooling
50.0
5.0 v
1705
Standard Full Load
Cooling
55.0
5.5 v
1830
Standard Part Load
Cooling
35.0
3.5 v
1335
Economizer Standard
Economizer High S/T
45.0
75.0
4.5 v
7.5 v
1600
1950
Heating
35.0
3.5 v
1335
Dehumidification
Mode
35.0
3.5 v
1335
TABLE 8
Indoor Blower Performance
Speed
High
Low
ESP
(Inch H
2
0)
Dry
Coil
Wet
Coil
Dry
Coil
Wet
Coil
HR35BP*
0.00
1150
1100
940
900
HR36BP*
0.00
1260
1200
995
950
HR58BP*
0.10
1885
1800
1470
1400
TABLE 9
Maximum ESP of Operation
Electric Heat Only
* Unit is rated for free blow non-ducted
operation with SGR-5W Supply Grille
and RGR-5W Return Grille.
Model
Static Pressure*
-A0Z
-A05
.00"
.00"
-B0Z
-B06
.00"
.00"
Blower Status Switch
The unit is equipped with a differential pressure airflow
switch to monitor the blower (see Figure 30). If the
blower is turned on and the switch doesn't open to
indicate there is differential pressure between the inlet
and outlet of the blower, an alarm will be generated.
For switch settings, see Figure 30.
FIGURE 30
Dirty Filter Switch and Blower Status Switch
Dirty Filter
Switch
(set per Table 10)
Blower Status
Switch
(HR35 set @ 0.12,
HR36 set @ 0.12,
HR58 set @ 0.20)