Manual 2100-742A
Page
50 of 54
1
V
alues listed are with ventilation package disabled
2
Return air temperature °F @ Default airflow (825 CFM) for AC tests and Balanced Climate airflow (600 CFM) for dehumidification tes
ts
3
Below 50°F
, unit requires a factory or field installed low ambient control.
4
Suction pr/- 4 psi, Discharge pr/- 10 psi
DB/WB
2
OD T
emp.
65°F
3
70°F
75°F
80°F
85°F
90°F
95°F
100°F
105°F
Mode
A/C
Dehum
A/C
Dehum
A/C
Dehum
A/C
Dehum
A/C
Dehum
A/C
Dehum
A/C
Dehum
A/C
Dehum
A/C
Dehum
75/62.5 (50% RH)
Total Cooling Btuh
25,800
12,100
25,100
10,500
24,300
8,500
23,400
7,000
22,600
5,000
21,700
2,900
20,800
700
19,800
18,800
Sensible Btuh
19,900
4,100
19,600
2,800
19,400
1,500
18,900
100
18,600
(1,300)
18,200
(2,700)
17,900
(4,100)
17,500
(5,600)
17,100
(7,100)
S/T
0.771
0.339
0.781
0.267
0.798
0.176
0.808
0.014
0.823
0
0.839
0
0.861
0
0.884
0
0.910
0
Latent Btuh
5,900
8,000
5,500
7,700
4,900
7,000
4,500
6,900
4,000
6,300
3,500
5,600
2,900
4,800
2,300
3,900
1,700
2,900
Lbs. H20/hr
.
5.6
7.5
5.2
7.3
4.6
6.6
4.2
6.5
3.8
5.9
3.3
5.3
2.7
4.5
2.2
3.7
1.6
2.7
Supply Air DB
53.1
65.7
53.5
67.7
53.8
69.6
54.3
71.6
54.7
73.7
55.1
75.8
55.6
77.9
56.0
80.1
56.4
82.4
Supply Air WB
51.7
56.2
52.1
57.1
52.4
58.1
52.9
59.0
53.3
60.0
53.7
61.1
54.1
62.2
54.5
63.4
54.8
64.6
Suction PSIG
4
127
121
128
121
129
122
131
123
132
124
133
126
134
129
135
132
136
135
Discharge PSIG
4
290
236
295
249
275
263
348
277
370
292
393
308
417
325
442
342
469
360
75/64.1 (55% RH)
Total Cooling Btuh
26,700
13,300
25,900
11,700
25,100
10,000
24,300
8,200
23,500
6,300
22,600
4,200
21,600
1,900
20,700
19,700
Sensible Btuh
18,900
5,600
18,500
4,300
18,200
3,000
17,900
1,600
17,500
300
17,200
(1,200)
16,800
(2,600)
16,400
(4,000)
16,000
(5,500)
S/T
0.708
0.42
0.714
0.37
0.725
0.30
0.737
0.20
0.745
0.05
0.761
0
0.778
0
0.792
0
0.812
0
Latent Btuh
7,800
7,700
7,400
7,400
6,900
7,000
6,400
6,600
6,000
6,000
5,400
5,400
4,800
4,500
4,300
3,600
3,700
2,600
Lbs. H20/hr
.
7.4
7.3
7.0
7.0
6.5
6.6
6.0
6.2
5.7
5.7
5.1
5.1
4.5
4.2
4.1
3.4
3.5
2.5
Supply Air DB
54.2
66.7
54.6
68.6
55.1
70.6
55.5
72.6
55.9
74.7
56.3
76.8
56.7
78.9
57.1
81.1
57.5
83.3
Supply Air WB
53.0
57.1
53.4
58.0
53.9
58.9
54.2
59.9
54.6
60.9
55.0
62.0
55.4
63.1
55.8
64.3
56.1
65.5
Suction PSIG
4
130
124
131
124
132
125
133
126
134
127
135
129
136
132
138
134
139
138
Discharge PSIG
4
265
239
283
252
303
265
323
280
345
295
368
311
392
327
417
345
444
362
75/65.5 (60% RH)
Total Cooling Btuh
27,500
14,500
26,800
13,000
26,000
10,900
25,200
9,400
24,300
7,500
23,400
5,400
22,500
3,200
21,600
800
20,600
Sensible Btuh
17,800
7,200
17,500
5,900
17,300
4,500
16,800
3,200
16,400
1,800
16,100
400
15,700
(1,000)
15,300
(2,500)
14,900
(4,000)
S/T
0.647
0.497
0.653
0.454
0.665
0.413
0.667
0.340
0.675
0.240
0.688
0.074
0.698
0
0.708
0
0.723
0
Latent Btuh
9,700
7,300
9,300
7,100
8,700
6,400
8,400
6,200
7,900
5,700
7,300
5,000
6,800
4,200
6,300
3,300
5,700
2,300
Lbs. H20/hr
.
9.2
6.9
8.8
6.7
8.2
6.0
7.9
5.8
7.5
5.4
6.9
4.7
6.4
4.0
5.9
3.1
5.4
2.2
Supply Air DB
55.4
67.7
55.8
69.6
56.1
71.6
56.6
73.6
57.0
75.6
57.5
77.7
57.9
79.9
58.3
82.1
58.7
84.3
Supply Air WB
54.3
58.0
54.7
58.9
55.0
59.9
55.5
60.8
55.9
61.8
56.3
62.9
56.7
64.0
57.1
65.2
57.4
66.4
Suction PSIG4
132
127
133
127
134
128
136
129
137
130
138
132
139
134
140
137
141
140
Discharge PSIG4
240
241
244
254
224
268
298
283
320
298
343
314
367
330
392
347
419
365
75/66.7 (65% RH)
Total Cooling Btuh
28,400
15,700
27,600
14,200
26,900
12,200
26,000
10,700
25,200
8,700
24,300
6,600
23,400
4,400
22,400
2,000
21,400
Sensible Btuh
16,700
8,700
16,400
7,400
16,200
6,100
15,700
4,700
15,400
3,300
15,000
1,900
14,600
500
14,200
(1,000)
13,800
(2,500)
S/T
0.588
0.55
0.594
0.52
0.602
0.50
0.604
0.44
0.611
0.38
0.617
0.29
0.624
0.11
0.634
0
0.645
0
Latent Btuh
11,700
7,000
11,200
6,800
10,700
6,100
10,300
6,000
9,800
5,400
9,300
4,700
8,800
3,900
8,200
3,000
7,600
2,000
Lbs. H20/hr
.
11.0
6.6
10.6
6.4
10.1
5.8
9.7
5.7
9.2
5.1
8.8
4.4
8.3
3.7
7.7
2.8
7.2
1.9
Supply Air DB
56.5
68.6
57.0
70.6
57.3
72.6
57.8
74.5
58.2
76.6
58.6
78.7
59.0
80.8
59.4
83.0
59.8
85.3
Supply Air WB
55.6
58.9
56.1
59.8
56.3
60.8
56.9
61.7
57.2
62.7
57.6
63.8
58.0
64.9
58.4
66.1
58.7
67.3
Suction PSIG
4
134
130
136
130
137
131
138
131
139
133
140
135
141
137
143
140
144
143
Discharge PSIG
4
215
244
219
257
199
271
273
285
294
300
317
316
342
333
367
350
393
368
75/68
(70% RH)
Total Cooling Btuh
29,300
16,900
28,500
15,400
27,700
13,400
26,900
11,900
26,000
9,900
25,200
7,800
24,200
5,600
23,300
3,200
22,300
700
Sensible Btuh
15,600
10,300
15,300
9,000
15,100
7,600
14,600
6,300
14,300
4,900
13,900
3,500
13,500
2,000
13,200
600
12,800
(900)
S/T
0.532
0.609
0.537
0.584
0.545
0.567
0.543
0.529
0.550
0.495
0.552
0.449
0.558
0.357
0.567
0.188
0.574
0
Latent Btuh
13,700
6,600
13,200
6,400
12,600
5,800
12,300
5,600
11,700
5,000
11,300
4,300
10,700
3,600
10,100
2,600
9,500
1,600
Lbs. H20/hr
.
12.9
6.2
12.5
6.0
11.9
5.5
11.6
5.3
11.0
4.7
10.7
4.1
10.1
3.4
9.5
2.5
9.0
1.5
Supply Air DB
57.7
69.6
58.1
71.5
58.5
73.5
58.9
75.5
59.4
77.6
59.8
79.7
60.2
81.8
60.6
84.0
61.0
86.2
Supply Air WB
56.9
59.8
57.4
60.7
57.6
61.7
58.2
62.6
58.5
63.7
58.9
64.7
59.3
65.8
59.7
67.0
60.0
68.2
Suction PSIG
4
137
132
138
132
139
133
140
134
142
136
143
138
144
140
145
143
146
146
Discharge PSIG
4
190
247
194
260
174
274
248
288
269
303
292
319
316
335
342
353
368
371
80/68.3 (55% RH)
Total Cooling Btuh
28,500
15,200
27,700
13,700
27,000
11,700
26,100
10,200
25,300
8,200
24,400
6,100
23,500
3,900
22,500
1,500
21,500
Sensible Btuh
16,700
6,400
16,300
5,100
16,100
3,800
15,700
2,400
15,300
1,100
15,000
(400)
14,600
(1,800)
14,200
(3,200)
13,800
(4,700)
S/T
0.586
0.42
0.588
0.37
0.596
0.32
0.602
0.24
0.605
0.13
0.615
0
0.621
0
0.631
0
0.642
0.00
Latent Btuh
11,800
8,800
11,400
8,600
10,900
7,900
10,400
7,800
10,000
7,100
9,400
6,500
8,900
5,700
8,300
4,700
7,700
3,700
Lbs. H20/hr
.
11.1
8.3
10.8
8.1
10.3
7.5
9.8
7.4
9.4
6.7
8.9
6.1
8.4
5.4
7.8
4.4
7.3
3.5
Supply Air DB
56.3
70.4
56.7
72.4
57.1
74.4
57.6
76.3
58.0
78.4
58.4
80.5
58.8
82.6
59.2
84.8
59.6
87.1
Supply Air WB
55.5
60.7
55.9
61.6
56.2
62.6
56.7
63.5
57.1
64.5
57.5
65.6
57.8
66.7
58.2
67.9
58.6
69.1
Suction PSIG
4
134
135
135
135
136
136
138
137
139
138
140
140
141
142
142
145
143
149
Discharge PSIG
4
323
249
327
262
307
275
380
290
402
305
425
321
449
337
475
354
501
372
Q24H4D Cooling and Dehumidification Application Data
1
Содержание 11EER QH Series
Страница 16: ...Manual 2100 742A Page 16 of 54 MIS 2471 A REMOVE KNOCK OUT FOR INDOOR DRAIN HOSE CONNECTOR FIGURE 18C If used ...
Страница 43: ...Manual 2100 742A Page 43 of 54 GRAPH 1 Q24H4 FAD Ventilation Delivery GRAPH 2 Q30H4 FAD Ventilation Delivery ...
Страница 44: ...Manual 2100 742A Page 44 of 54 GRAPH 3 Q36H4 FAD Ventilation Delivery ...